SMMS 4-way Air Discharge Cassette Type
Installation Manual
EN
When wireless remote
controller is used
Change the high-ceiling and filter settings with the
DIP switch on the receiver section P.C. board.
For details, refer to the manual of the wireless
remote controller kit. The settings can also be
changed with the switch on the indoor
microcomputer P.C. board.
* Once the setting is changed, setting to 0001 or
0003 is possible, however setting to 0000
requires a setting data change to 0000 using the
wired remote controller (separately sold) with
the normal switch setting (factory setting).
To restore the factory settings
To return the DIP switch settings to the factory
settings, set SW501-1 and SW501-2 to OFF,
connect a separately sold wired remote controller,
and then set the data of CODE No. [5d] to “
0000
”
in “When installing separately sold filters” on this
page.
Change of lighting time of
filter sign
According to the installation condition, the lighting
time of the filter sign (Notification of filter cleaning)
can be changed.
Follow the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
).
• For the CODE No. in Procedure
3
, specify [01].
• For the SET DATA in Procedure
4
, select the
SET DATA of filter sign lighting time from the
following table.
SET DATA
SW501-1
SW501-2
0000
(Factory setting)
OFF
OFF
0001
ON
OFF
0003
OFF
ON
SW501-1
MCU(IC501)
SW501-2
SET DATA
Filter sign lighting time
0000
None
0001
150H
0002
2500H (Factory setting)
0003
5000H
0004
10000H