Toshiba
– 7 –
SMMS 4-way Air Discharge Cassette Type
Installation Manual
REQUIREMENT
• When using the air conditioner with 2-way/3-way discharge system, a strong wind blows directly if the
ceiling height is lower than the standard.
Therefore, change the setting switch according to height of the ceiling.
• When using the high ceiling (1) or (3) with 4-way discharge system, the draft is apt to be felt due to
drop of the discharge temperature.
• AP0092H Type and AP0122H Type air conditioners cannot be installed on a high ceiling.
▼
Height list of ceiling possible to be installed
(Unit: m)
The lighting time of the filter sign (notification of filter cleaning) on the remote controller can be changed
according to installation conditions.
When it is difficult to obtain satisfactory heating due to location place of the indoor unit or the structure of
the room, the detection temperature of heating can be raised.
Discharge direction
As shown in the figure below, air discharge directions can be selected according to the shape of the room
and the location of the indoor unit installation.
• Use a shielding plate kit (sold separately) to change discharge directions.
Discharge directions are limited. Follow the Installation Manual supplied with the shielding plate kit.
Model MMU-
AP0092H to
AP0122H
AP0152H to
AP0182H
AP0242H to
AP0302H
AP0362H to
AP0562H
Setup of
high ceiling
Discharge direction
4-way 3-way 2-way 4-way 3-way 2-way 4-way 3-way 2-way 4-way 3-way 2-way
SET DATA
Standard (At shipment)
2.7
2.8
3.0
2.8
3.2
3.5
3.0
3.3
3.6
3.9
4.2
4.5
0000
High ceiling (1)
—
—
—
3.2
3.5
3.8
3.3
3.5
3.8
4.2
4.4
4.6
0001
High ceiling (3)
—
—
—
3.5
3.8
—
3.6
3.8
—
4.5
4.6
—
0003
3 directions
2 directions
Shielding plate
(sold separately)
7-EN