Toshiba
– 8 –
SMMS 4-way Air Discharge Cassette Type
Installation Manual
EN
4
INSTALLATION
REQUIREMENT
Strictly comply with the following rules to prevent damage of the indoor units and human injury.
• Do not put a heavy article on the indoor unit. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by
necessity, be sure to use buffering cloth, etc. to not damage the unit.
• To move the indoor unit, hold the hooking metals (4 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).
• Carry the package by two or more persons, and do not bundle it with plastic band at positions other
than specified.
External view
(Unit:mm)
(mm)
Model MMU
A
B
C
D
Model MMU
A
B
C
D
AP0092H to AP0122H
256
Ø6.4
Ø9.5
120
AP0242H to AP0302H
256
Ø9.5
Ø15.9
120
AP0152H to AP0182H
256
Ø6.4
Ø12.7
120
AP0362H to AP0562H
319
Ø9.5
Ø15.9
183
Ceiling bottom
surface
Knockout square hole
for divide duct
For Ø150
Knockout square
hole for divide duct
For Ø150
840 Unit external dimension
Ceiling bottom surface
Electric parts
box
Refrigerant pipe
connecting port
(Liquid) B
Refrigerant pipe
connecting port
(Gas) C
Take-in port
of wires
Ceiling
bottom
surface
Drain pipe
connecting
port
Knockout square hole
for divide duct
For Ø150
Hanging bolt M10 or Ø3/8
(To be procured locally)
Knockout square hole for divide duct
For Ø150
690 ± 20 Hanging bolt pitch
860 to 910 Ceiling opening dimension
950 Panel external dimension
Knockout square hole for humidifier
Ceiling panel (sold separately)
Ceiling bottom surface
Z view
Knockout for
simple OA
For Ø100
Ceiling bottom
surface
8
6
0 to
9
1
0 Ce
ilin
g
o
pe
n
in
g
d
im
e
n
sio
n
780
H
angi
n
g bol
t pi
tch
950 P
a
ne
l exter
nal
di
m
ensi
o
n
8-EN