– 31 –
FILE NO. SVM-
16041
No.
18
Item
Louver control
(Continued):
Outline of specifications
• If there is the locked louver in the unit, [
] goes on the
remote controller screen.
• While the following controls are performed, the louvers
operate even if executing the louver lock.
Remarks
For the setting operation,
refer to [How to set louver
lock] of Installation Manual.
• The real louver corresponding to the louver No. displayed
on the remote controller screen during setting of louver
lock operates swinging.
�
�
�
�
�
Control which ignores lock
Operation stop
When heating operation started
Heating thermo. OFF
During defrost operation
Initialize operation
Objective louver No.
Horizontal discharge position
Horizontal discharge position
Horizontal discharge position
Horizontal discharge position
Full-close position
It is position check operation
and it does not link with the
real louver and air direction
setup (Illustration on the
remote controller screen).
19
DC motor
1) When the fan stator, positioning is performed for the
starter and the rotor. (Vibrate slightly)
2) DC motor operates according to the command from
the indoor controller.
(Note) If the fan rotates by entry of outside air, etc while
the air conditioner stopped, the indoor unit may
operate as the fan motor stops.
(Note) If the fan lock was detected, the operation of the
indoor unit stops and the error is displayed.
Check code [P12]
20
Save operation
1) The function [Save operation] is not provided to the
Super Modular Multi series models.
• If pushing [SAVE] button
“ ” on the remote
controller, “No function”
is displayed.