81
7-2-2. Applied Control in Outdoor Unit
The following functions are available by using a separately supplied P.C. board.
Set up the switches on the outdoor unit (U1).
Outdoor unit interface P.C. board
SW07
Bit 1
Bit 2
For power peak-cut control selection
For power peak-cut control (expansion) selection
CN508
Red
CN509
Black
CN510
White
CN513
Blue
CN511
Green
Connector position detail
Switch position detail
No.
1
2
3
4
5
6
Function
Power peak-cut control (Standard)
Power peak-cut control (Expansion)
Snowfall fan control
External master ON/OFF control
Night operation control
Operation mode selection control
Switch No.
SW07
SW07
—
—
—
—
Bit
1
1,2
—
—
—
—
Connector No.
CN513
CN513
CN509
CN512
CN508
CN510
Used control P.C. board
TCB-PCDM2E
TCB-PCDM2E
TCB-PCMO2E
TCB-PCMO2E
TCB-PCMO2E
TCB-PCMO2E