119
Check code
Location
of
detection
Description
System status
Error detection condition(s)
Check items (locations)
Wired
remote
control
Outdoor 7-segment display
Check
code
Sub-code
E12
E12
01:
Indoor-outdoor
communication
02:
Outdoor-
outdoor
communication
I/F
Automatic
address starting
error
All stop
• Indoor automatic address setting
is started while automatic
address setting for equipment in
other refrigerant line is in
progress.
• Outdoor automatic address
setting is started while automatic
address setting for indoor units is
in progress.
• Perform automatic address
setting again after disconnecting
communication cable to that
refrigerant line.
E15
E15
–
I/F
Indoor unit not
found during
automatic
address setting
All stop
Indoor unit cannot be detected after
indoor automatic address setting is
started.
• Check connection of indoor-
outdoor communication line.
• Check for error in indoor power
supply system.
• Check for noise from other
devices.
• Check for power failure.
• Check for defect in indoor P.C.
board.
E16
E16
00:
Overloading
01-:
No. of units
connected
I/F
Too many
indoor units
connected
All stop
• Combined capacity of indoor
units exceeds 125 % of combined
capacity of outdoor units.
Note:
If this code comes up after
backup setting for outdoor
unit failure is performed,
perform “No overloading
detected” setting.
<“No overloading detected” setting
method>
Turn on SW09/Bit 2 on I/F P.C.
board of outdoor header unit.
• More than 48 indoor units are
connected.
• Check capacities of indoor units
connected.
• Check combined HP capacities of
indoor units.
• Check HP capacity settings of
outdoor units.
• Check No. of indoor units
connected.
• Check for defect in outdoor P.C.
board (I/F).
E18
–
–
Indoor
unit
Error in
communication
between indoor
header and
follower units
Stop of
corresponding
unit
Periodic communication between
indoor header and follower units
cannot be maintained.
• Check remote control wiring.
• Check indoor power supply
wiring.
• Check P.C. boards of indoor
units.
E19
E19
00:
No header unit
02:
Two or more
header units
I/F
Error in number
of outdoor
header units
All stop
• There is more than one outdoor
header unit in one line.
• There is no outdoor header unit in
one line.
Outdoor header unit is outdoor unit
to which indoor-outdoor tie cable
(U1,U2) is connected.
• Check connection of indoor-
outdoor communication line.
• Check for defect in outdoor P.C.
board (I/F).
E20
E20
01:
Connection of
outdoor unit
from other line
02:
Connection of
indoor unit from
other line
I/F
Connection to
other line found
during
automatic
address setting
All stop
Equipment from other line is found
to have been connected when
indoor automatic address setting is
in progress.
Disconnect inter-line tie cable in
accordance with automatic address
setting method explained in
“Address setting” section.
E23
E23
–
I/F
Outdoor-
outdoor
communication
transmission
error
All stop
Signal cannot be transmitted to
other outdoor units for at least 30
seconds continuously.
• Check power supply to outdoor
units. (Is power turned on?)
• Check connection of tie cables
between outdoor units for bad
contact or broken wire.
• Check communication
connectors on outdoor P.C.
boards.
• Check for defect in outdoor P.C.
board (I/F).
• Check termination resistance
setting for communication
between outdoor units.
E25
E25
–
I/F
Duplicated
follower outdoor
address
All stop
There is duplication in outdoor
addresses set manually.
Note:
Do not set outdoor addresses
manually.
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...