MG-CTT: Magnet contactor
Check code
Location
of
detection
Description
System status
Error detection condition(s)
Check items (locations)
Wired
remote
control
Outdoor 7-segment display
Check
code
Sub-code
L30
L30
Detected indoor
address
Indoor
unit
External
interlock of
indoor unit
Stop of
corresponding
unit
• Signal is present at external error
input terminal (CN80) for 1
minute.
When external device is
connected to CN80 connector:
1) Check for defect in external
device.
2) Check for defect in indoor P.C.
board.
When external device is not
connected to CN80 connector:
1) Check for defect in indoor P.C.
board.
–
L31
–
I/F
Extended IC
error
Continued
operation
There is part failure in P.C. board (I/
F).
Check outdoor P.C. board
(I/F).
P01
–
–
Indoor
unit
Indoor fan
motor error
Stop of
corresponding
unit
• Check the lock of fan motor (AC
fan).
• Check wiring.
P03
P03
–
I/F
Discharge
temperature
TD1 error
All stop
Discharge temperature (TD1)
exceeds 239 °F (115 °C).
• Check outdoor service valves
(gas side, liquid side) to confirm
full opening.
• Check outdoor PMVs (PMV1, 2,
4) for clogging.
• Check resistance characteristics
of TD1 sensor.
• Check for insufficiency in
refrigerant quantity.
• Check for defect in 4-way valve.
• Check for leakage of SV4 circuit.
• Check SV4 circuit (wiring or
installation error in SV41, SV42 or
SV43).
P04
P04
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
IPDU
Activation of
high-pressure
SW
All stop
High-pressure SW is activated.
• Check connection of high-
pressure SW connector.
• Check for defect in Pd pressure
sensor.
• Check outdoor service valves
(gas side, liquid side) to confirm
full opening.
• Check for defect in outdoor fan.
• Check for defect in outdoor fan
motor.
• Check outdoor PMVs (PMV1, 2)
for clogging.
• Check indoor/outdoor heat
exchangers for clogging.
• Check for short-circuiting of
outdoor suction/discharge air
flows.
• Check SV2 circuit for clogging.
• Check for defect in outdoor P.C.
board (I/F).
• Check for error in indoor fan
system (possible cause of air flow
reduction).
• Check opening status of indoor
PMV.
• Check indoor-outdoor
communication line for wiring
error.
• Check for faulty operation of
check valve in discharge pipe
convergent section.
• Check gas balancing SV4 valve
circuit.
• Check SV5 valve circuit.
• Check for refrigerant
overcharging.
P05
P05
00: I/F
Detection
of
open phase/
phase
sequence
All stop
• Open phase is detected when
power is turned on.
• Inverter DC voltage is too high
(overvoltage) or too low
(undervoltage).
• Check for defect in outdoor P.C.
board (I/F).
01: Compressor
1 side
02: Compressor
2 side
03: Compressor
3 side
Inverter DC
voltage (Vdc)
error
(compressor)
MG-CTT error
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...