131
▼
Points to Note When Servicing Compressor
(1) When checking the outputs of inverters, remove the wiring from all the compressors.
▼
How to Check Inverter Output
(1) Turn off the power supply.
(2) Remove compressor leads from the IPDU P.C. board (A3-IPDU). (Be sure to remove all the leads.)
(3) Turn on the power supply and start cooling or heating operation.
Be careful not to make simultaneous contact with two or more faston connectors for compressor leads or a
faston connector and some other object (e.g. the unit cabinet).
(4) Check the output voltage across each pair of inverter-side (CN201, CN202, CN203).
If the result is unsatisfactory according to the judgment criteria given in the table below, replace the IPDU P.C.
board.
* When connecting the compressor leads back to the compressor terminals after checking the output, check the
faston connectors thoroughly to ensure that they are not crooked. If there is any loose connector, tighten it with
a pair of pliers, etc. before connecting the lead.
▼
How to Check Resistance of Compressor Winding
(1) Turn off the power supply.
(2) Remove compressor leads from the compressors.
(3) With each compressor, check the phase-to-phase winding resistances and winding-to-outdoor cabinet
resistance using a multimeter.
• Earth fault?
➝
It is normal if the winding-to-outdoor cabinet resistance is 10 M
Ω
or more.
• Inter-winding short circuit?
➝
It is normal if the phase-to-phase resistances are in the 0.1-0.4
Ω
range. (Use a digital multimeter.)
▼
How to Check Outdoor Fan Motor
(1) Turn off the power supply.
(2) Remove fan motor leads from the IPDU P.C. board for the outdoor fan (CN703-CN705).
(3) Rotate the fan by hand. If the fan does not turn, the fan motor is faulty (locked up). Replace the fan motor.
If the fan turns, measure the phase-to-phase winding resistances using a multimeter. It is normal if the
measurements are in the 1.14-1.70
Ω
range. (Use a digital multimeter.)
No.
Measured
Criterion
1
CN201 - CN202
400 V - 650 V
2
CN202 - CN203
400 V - 650 V
3
CN203 - CN201
400 V - 650 V
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...