180
10-2.Compressor backup operation setting
<Outline>
If a fault occurs to one of the compressors installed in outdoor unit, follow the procedure described below to back
up the faulty compressor by using the remaining, normal compressor(s).
<Work Procedure>
(1) Turn off the power supply to all the outdoor units connected to the system.
(2) Set the DIP switches of SW06, provided on the interface P.C. board of the outdoor unit with the faulty
compressor, as shown in the table below.
(3) Turn on the power supply to all the units connected to the system.
This is the end of compressor backup operation setting.
Three-compressor model
SW06
Bit 1
Bit 2
Bit 3
Bit 4
Factory default setting
OFF
OFF
OFF
OFF
When compressor No. 1 (front left) is faulty
ON
OFF
OFF
OFF
When compressor No. 2 (front center) is faulty
OFF
ON
OFF
OFF
When compressor No. 3 (front right) is faulty
OFF
OFF
ON
OFF
Two-compressor model
SW06
Bit 1
Bit 2
Bit 3
Bit 4
Factory default setting
OFF
OFF
OFF
OFF
When compressor No.1 (front left) is faulty
ON
OFF
OFF
OFF
When compressor No.2 (front right) is faulty
OFF
ON
OFF
OFF
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...