207
4
Inverter assembly
WARNING
Wear a pair of gloves.
Otherwise, you will risk an injury involving
a replacement part or some other object.
1. Detachment
1) Stop the air conditioner operation, and turn
off the circuit breaker.
2) Remove the inverter cover.
(M4 × 0.1’ (10 mm), 2 pcs.)
3) Remove the wiring.
(e.g. the power supply wire, compressor
leads, coils, sensors and heaters)
5) Remove the wire guard.
(M4 × 0.1’ (10 mm), 1 pc.)
6) Remove the screws securing the box.
(M5 × 0.1’ (10 mm), 1 pc. each for top and
bottom)
7) Disengage the hook by gently pressing
down the locking lever with your finger.
(The lower part of the box moves forward.)
8) Hold the top board with both hands to
disengage the top hook.
No. Part to be replaced
Work procedure
Remarks
4) Steps only applicable to a 096 type, 114 type
• Remove the reactor lead cover.
(M4 × 0.1’ (10 mm), 1 pc.)
• Remove the screws securing the box.
(M4 × 0.1’ (10 mm), 1 pc.)
• Detach the reactor leads.
(6 terminal block bolts and 2 faston
connectors)
In the case of a 096 type, 114 type: M5 × 0.1’
(10 mm), 1 pc. for top and 2 pcs for bottom
4) Screw (with arrow mark)
Removable design
4) Screw
(with arrow mark)
4) Connector
for fan reactor
4) Reactor
lead cover
4) Reactor terminal block
5) Screw
5) Wire guard
6) Screw
6) Screw with
arrow mark
(2 locations)
Pull it forward
7) Locking lever
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...