52
<SW07 Bit 2 OFF (two-step control)>
Power peak-cut control is enabled as long as SW1, as shown on the wiring diagram, is ON (continuously).
Note 1: Specifications of display relay contact
• The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).
7-2-2. Power peak-cut control (extended)
Operation
An external power peak-cut control signal limits the peak capacity of the outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch*1
SW2: Power peak-cut control OFF switch*1
*1 The inputs of SW1 and SW2 can be either pulse (100 msec or wider) or step signals.
* Be sure to provide a contact for each terminal.
Extended power peak-cut control settings
Specifications of display relay contact
Note 1: Specifications of display relay contact
• The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).
Jumper wire
J16
Input
SW1
SW07 Bit 1
Indicator relay
Bit 1 OFF
Bit 1 ON
(L1)
Cut
ON
0% (forced stop)
60% capacity (upper limit regulated)
OFF
OFF
100% (normal operation)
100% (normal operation)
ON
<Electrical Rating>
24 V or less (AC / DC), 10 mA or more, 1 A or less (non-conductive load)
Indication lamp
External power peak-cut control
signals
Peak capacity
I/F SW07 Bit 1
L1
SW1
SW2
OFF
ON
OFF
OFF
OFF
100% (normal operation)
100% (normal operation)
ON
ON
OFF
80% (upper limit regulated)
85% (upper limit regulated)
ON
OFF
ON
60% (upper limit regulated)
75% (upper limit regulated)
ON
ON
ON
0% (forced stop)
60% (upper limit regulated)
<Electrical Rating>
24 V or less (AC / DC), 10 mA or more, 1 A or less (non-conductive load)
Header outdoor unit
L1: Display lamp suring power peak cut control
Locally procured
Outdoor unit
interface PCB
Connection cable
Shield wire
Shield wire
Display
relay
Optional PCB
[OPERATION]
Power
supply
For SW1 and SW2, be sure to provide
no-voltage contacts for each terminal.
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...