7-2-6. Operation mode selection control
NOTE
SW1: COOL mode selection switch
SW2: HEAT mode selection switch
* The display
“
(
Operation mode selection control in progress)” appears on the remote control.
Indoor unit operation intervention function
The statuses of indoor units operating in a mode different from the selected operation mode can be changed by
changing the status of a jumper wire (J01) provided on the interface P.C. board of the header outdoor unit.
The optional P.C. board should be connected to the header outdoor unit (U1).
Input signal
Operation
Remarks
COOL (SW1)
HEAT (SW2)
ON
OFF
Only cooling
operation allowed
*
OFF
ON
Only heating
operation allowed
*
OFF
OFF
Normal operation
Jumper wire
Description of intervention
J01 connected
(factory default)
All indoor units operating in a mode different from the selected operation mode (prohibited-mode indoor units)
become non-priority units (thermostat OFF).
Prohibited-mode indoor units
J01 cut
The selected operation mode is imposed on all indoor units operating in a different mode.
Header outdoor unit
Locally procured
Outdoor unit
interface PCB
Shield
wire
Optional PCB
Connection
cable
SW1: Cooling mode specified input switch
SW2: Heating mode specified input switch
Operation mode
Operation status
Remote control
display
COOL
Fan operation at air flow rate set via remote control
“
” operation ready
HEAT
Fan operation at extremely low air flow rate
FAN
Fan operation at air flow rate set via remote control as
normal
Mode selected at P.C. board
Remote control operation / display
Normal
All modes (COOL, DRY, HEAT and
FAN) available
COOL
Only COOL, DRY and FAN available “
operation mode control”
(turned on during remote
controller operation)
HEAT
Only HEAT and FAN available
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...