73
To find an indoor unit’s position from its address
▼
When checking unit numbers controlled as a group
(Execute it while the units are stopped.)
The indoor unit numbers in a group are indicated one after another. The fan and louvers of the indicated units are
activated.
1
Push and hold the
and
buttons at the same time for more than 4 seconds.
•
appears on UNIT No. on the LCD display.
• The fans and louvers of all the indoor units in the group are activated.
2
Push the
button (left side of the button). Each time you push the button, the indoor unit
numbers are indicated one after another.
• The first-indicated unit number is the address of the header unit.
• Only the fan and louvers of the indicated indoor unit are activated.
3
Push the
button to finish the procedure.
All the indoor units in the group stop.
▼
To check all the indoor unit addresses using an arbitrary wired remote control.
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
(Execute it while the units are stopped.)
You can check indoor unit addresses and positions of the indoor units in a single refrigerant line.
When an outdoor unit is selected, the indoor unit numbers of the refrigerant line of the selected unit are indicated
one after another and the fan and louvers of the indicated indoor units are activated.
Stop
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...