75
4
Push the TIME
/
buttons repeatedly to change the value indicated in the SET DATA section
to that you want.
5
Push the
button.
6
Push the
button (left side of the button) repeatedly to select another indoor UNIT No. to
change.
Repeat steps
4
to
6
to change the indoor unit addresses so as to make each of them unique.
7
Push the
button (left side of the button) to check the changed addresses.
8
If the addresses have been changed correctly, push the
button to finish the procedure.
▼
To change all the indoor unit addresses using an arbitrary wired remote control.
(The method is available when the addresses have already been set automatically.)
(When communication wirings of 2 or more refrigerant lines are interconnected for central control)
NOTE
You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote control.
* Enter the address check/change mode and change the addresses.
If no number appears on UNIT No., no outdoor unit exists on the line. Push
button and select another line
following step
2
.
(Execute it while the units are stopped.)
1
Push and hold the TIME
and
buttons at the same time for more than 4 seconds.
At first, the line 1 and CODE No.
(Address Change) are indicated on the LCD display.
2
Push
(left side of the button) and
buttons repeatedly to select a system address.
Cancels the line selection
Summary of Contents for MMY-MAP0724HT6UL
Page 229: ...228 15Exploded Diagram Parts Price List SMMS i OUTDOOR UNIT MMY MAP0724HT6UL ...
Page 230: ...229 MMY MAP0724HT6UL ...
Page 232: ...231 SMMS i OUTDOOR UNIT MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 233: ...232 MMY MAP0964HT6UL MMY MAP1144HT6UL ...
Page 237: ...236 SMMS i INV SERVICE PARTS LIST MMY MAP0724HT6UL 4 pieces PC board ...
Page 238: ...237 SMMS i INV SERVICE PARTS LIST MMY MAP0964HT6UL MMY MAP1144HT6UL 4 pieces PC board ...
Page 241: ...Copyright 2011 TOSHIBA CARRIER CORPORATION ALL Rights Reserved ...