Address setting procedure 2
1
Set a system address for each system using SW 13 and 14 on the interface P.C. board for the
header outdoor unit of each system.
(Factory default: Address 1)
NOTE
Set a unique address for each system. Do not reuse any address from another system (refrigerant line).
Interface P.C. board on the header outdoor unit
SW06
SW07
SW09
SW10
SW11
SW12
SW13
SW14
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
1 2 3 4
Switch settings for a line (system) address on the interface P.C. board for the outdoor unit
(
✕
: switch OFF)
Line (system) address
SW13
SW14
4
1
2
3
4
1
✕
✕
✕
✕
✕
2
✕
ON
✕
✕
✕
3
✕
✕
ON
✕
✕
4
✕
ON
ON
✕
✕
5
✕
✕
✕
ON
✕
6
✕
ON
✕
ON
✕
7
✕
✕
ON
ON
✕
8
✕
ON
ON
ON
✕
9
✕
✕
✕
✕
ON
10
✕
ON
✕
✕
ON
11
✕
✕
ON
✕
ON
12
✕
ON
ON
✕
ON
13
✕
✕
✕
ON
ON
14
✕
ON
✕
ON
ON
15
✕
✕
ON
ON
ON
16
✕
ON
ON
ON
ON
17
ON
✕
✕
✕
✕
18
ON
ON
✕
✕
✕
19
ON
✕
ON
✕
✕
20
ON
ON
ON
✕
✕
21
ON
✕
✕
ON
✕
22
ON
ON
✕
ON
✕
23
ON
✕
ON
ON
✕
24
ON
ON
ON
ON
✕
25
ON
✕
✕
✕
ON
26
ON
ON
✕
✕
ON
27
ON
✕
ON
✕
ON
28
ON
ON
ON
✕
ON
◆
Address setting procedure 1
1
Energize indoor units
fi
rst, and then energize outdoor units.
2
About one minute after energizing the outdoor units, con
fi
rm that the 7-segment display on the
interface P.C. board of the header outdoor unit indicates
U. 1. L08
. The U.1. will be
fl
ashing.
3
Press SW 15 to start the automatic address setting.
It normally takes 5 minutes, but may takes as long as 10 minutes to complete the auto address setting for 1
refrigerant line.
4
The 7 segment display will indicate
Auto 1
→
Auto 2
→
Auto 3
.
When the address sequence has covered all the fan coils for a refrigerant line auto - the 7
segment display will indicate
U. 1.
fl
ashing.
When the
fl
ashing stops and the display indicates
U. 1.
without
fl
ashing, the address setting is
complete.
Interface P.C. board on the header outdoor unit
SW04
SW05
SW15
SW01
SW02
SW03
D600 D601 D602 D603 D604
3
2,4
REQUIREMENT
• When 2 or more refrigerant lines are controlled as a group (using, 1 remote control), be sure to turn on all the
indoor units in the group before setting the addresses.
(Note: the group control of more than two refrigerant systems is possible only when all the FS units are single
port type.)
• If the unit address of each refrigerant line is set separately, then the header unit for each line will be set
separately. In this case the remote control will display CODE No. “L03” indicating “indoor header unit overlap”
when the system starts running. When this happens the group address must be changed to make only one unit
the header unit. This operation is done using the wired remote control.
(Example)
Controlling 2 or more refrigerant lines as a group
System wiring
diagram
Outdoor
Indoor
Indoor
Indoor
Indoor
Outdoor
Remote
control
(Group control)