background image

– 23 –

45-EN

46-EN

 

Using the remote control 
to review the address and 
position of an indoor unit

How to determine an indoor unit address if 
the unit position is known.

This instruction works for indoor units that have 
individual, or group control. This must be done while 
the units are operating.

2,4

ON / OFF

TEMP.

TIME

SET CL

FILTER

RESET TEST

TIMER SET

CODE No.

UNIT   No.

No.

°F

1

3

1

  If the unit is “OFF” turn it “ON” 

ON / OFF

.

2

  Push the left end of the “UNIT LOUVER 

” button.

3

  Unit number will be indicated on the 

control LCD as shown above. The numbers 
will disappear after a few seconds. The 
numbers indicate the system address 
and the unit address for the indoor unit in 
question.

4

  If 2 or more indoor units are connected to 

a group control the address for the next 
consecutive unit will appear each time the 
left end of the “UNIT LOUVER 

” 

button is pushed.

How to determine an indoor unit position if
the unit address is known.

This instruction works for group controlled units only.
This instruction must be done while the units are not 
operating.

ON / OFF

TEMP.

TIME

SET CL

FILTER

RESET TEST

TIMER SET

CODE No.

UNIT   No.

SETTING

DATA

SET

R.C.

No.

6
2

3

1

4,5

1

  If the unit is “ON” turn it “OFF” 

ON / OFF

.

2

  Simultaneously push and hold the “VENT 

VENT

” and “TEST 

TEST

” buttons for more 

than 4 seconds.

3

 “ALL 

” will appear on the control LCD 

display. The fans and louvers of all the 
indoor units in the control group will be 
activated.

4

  Push the left end of the “UNIT LOUVER 

” button.

5

  Each time the left of the button is pushed 

the next consecutive indoor unit address 
(in the group) will be displayed. While the 
address is displayed the fan and louvers 
for that indoor unit will operate. For all 
other units in the group the fan and louvers 
will stop.

6

  Push the “TEST 

TEST

” button to 

fi

 nish the 

procedure. All the indoor units in the 
control group will stop.

ON / OFF

TEMP.

TIME

SET CL

FILTER

RESET TEST

TIMER SET

CODE No.

UNIT   No.

SETTING

DATA

SET

R.C.

No.

11

4, 7, 10

2, 5, 8

3, 6, 9

1

SET DATA

CODE No.

Turn on the power.

1

  Push and hold the 

SET

CL

, and 

TEST

 buttons 

at the same time for more than 4 seconds.

The LCD display will start 

fl

 ashing.

To set-line (system) address

2

  Push the TEMP. 

/

 buttons 

repeatedly to set the CODE No. to 

.

3

  Push the TIME 

/

 buttons repeatedly to 

set a system address.

(Match the address with the address on the 
interface P.C. board of the header outdoor unit in 
the same refrigerant line.)

4

 Push 

SET

 button.

(This saves the setting.)

To set-indoor unit address

5

  Push the TEMP. 

/

 buttons 

repeatedly to set the CODE No. to 

.

6

  Push the TIME 

/

 buttons repeatedly to 

set an indoor unit address.

7

 Push 

the 

SET

 button.

(This saves the setting.)

To set-group address

8

  Push the TEMP. 

/

 buttons 

repeatedly to set the CODE No. to 

.

9

  Push the TIME 

/

 buttons repeatedly to 

set a group address. If the indoor unit is 
individual, set the address to 

header unit, 

; follower unit, 

.

Individual

: 0000

Header unit

: 0001

}

 In case of group 

control

Follower unit

: 0002

10

 Push the 

SET

 button.

(This saves the setting.)

11

 Push the 

TEST

 button.

The address setting is complete.
(

SETTING

 

fl

 ashes. The unit can be controlled after 

SETTING

 has disappeared.)

NOTE

1. Do not use address numbers 

29

 or 

30

 when setting 

system addresses using the remote control.
These 2 address numbers cannot be used on
outdoor units and the CODE No. [

E04

] (Indoor/

outdoor communication trouble) will appear if they 
are mistakenly used.

2. If addresses to indoor units are set in 2 or more 

refrigerate lines manually by using the remote 
control and will control them centrally, set the header
outdoor unit of each line as below.
•  Set a system address for the header outdoor unit 

of each line with SW13 and 14 of their interface 
P.C. boards.

•  Turn off DIP switch 2 of SW30 on the interface 

P.C. boards of all the header outdoor units 
connected to the same central control, except the 
unit that has the lowest address. (For unifying the 
termination of the wiring for the central control of 
indoor and outdoor units)

•  Connect the relay connectors between the [U1,

U2] and [U3, U4] terminals on the header outdoor
unit of each refrigerate line.

•  After finishing all the settings above, set the

address of the central control devices. (For the
setting of the central control address, refer to the
installation manuals of the central control
devices.)

1122001001-2_EN-FR.indb   23

1122001001-2_EN-FR.indb   23

2/18/17   11:44 AM

2/18/17   11:44 AM

Summary of Contents for MMY-MAP0726FT6P-UL

Page 1: ... UL MMY MAP0966FT6P UL MMY MAP1206FT6P UL MMY MAP1446FT6P UL MMY MAP1686FT6P UL 1122001001 2 English Français Installation Manual 1 Manuel d installation 32 For OUTDOOR USE only Pour une UTILISATION EN EXTÉRIEUR uniquement 1122001001 2_EN FR indb 1 1122001001 2_EN FR indb 1 2 18 17 11 44 AM 2 18 17 11 44 AM ...

Page 2: ...d on tags stickers and labels attached to the equipment Follow all safety codes Wear safety glasses and work gloves Use care in handling rigging and setting bulky equipment Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit Consult local building codes and National Electrical Code NEC for special requirements Recognize safety info...

Page 3: ...ar this protective gear may result in electric shocks When executing address setting test run or troubleshooting through the checking window on the electric parts box put on insulated heat proof gloves insulated shoes and other clothing to provide protection from electric shock Otherwise you may receive an electric shock Use wiring that meets the specifications in the Installation Manual NEC and t...

Page 4: ...igerant is vulnerable to impurities such as water oxidizing membranes or oils because the pressure of R410A refrigerant is higher than that of the former refrigerant by approximately 1 6 times As well as the adoption of the new refrigerant the refrigerating oil has been also changed Therefore pay attention so that water dust former refrigerant or refrigerating oil does not enter the refrigerating ...

Page 5: ...nication equipment is set Malfunction or abnormal control of the air conditioner or interference to devices listed above may occur Places where discharged air from the outdoor unit blows against the windows of a neighbour s house Places unable to bear the weight of the unit Places with poor ventilation Installation space Unit in mm Leave space necessary for running installation and servicing Air d...

Page 6: ...or unit carefully observing the following items To use a forklift or other machinery for loading unloading in transportation insert the fork of the forklift into the rectangular holes for handling as shown below To lift up the unit insert a rope capable of bearing the weight of the unit into the rectangular holes shown below Tie the unit from 4 sides Apply padding in positions where the rope comes...

Page 7: ...or bolt 4 positions unit 0 8 20 Anchor bolt positions are as shown below A A A B A C B B L L B Continuous hole 0 6 0 8 15 20 long hole L 11 4 290 L 11 4 290 29 7 755 31 1 790 Only MAP144 MAP168 type has holes for additional strength Model type A B C L MAP0726 27 6 700 39 0 990 Recommendation 7 9 200 at least 0 8 20 or more MAP0966 MAP1206 36 2 920 47 6 1210 MAP1446 MAP1686 51 6 1310 63 0 1600 59 0...

Page 8: ...hape branch joints for the liquid side there is no restriction for its angle A B Horizontal line Horizontal line A arrow view B arrow view Within 15 degrees Within 15 degrees Do not connect a branch unit vertically 19 7 500mm or more At a level position In case of using the Y shaped branching joint for connecting between outdoor units Discharge gas joint and Suction gas joint please keep the strai...

Page 9: ...gerant pipes and perform piping work so that water or dust does not contaminate the refrigerant Be sure to use two spanners to loosen or tighten the flare nut If a single spanner is used the required level of tightening cannot be obtained Tighten the flare nut with the specified torque If it is hard to loosen or tighten the flare nut of the balance pipe or packed valve of the liquid side with two ...

Page 10: ...3 11 0 39 10 0 0063 or less 0 16 or less 0 032 0 82 Ø1 1 8 28 58 1 1 8 0 0012 28 58 0 04 1 13 0 0024 0 0008 28 75 0 06 0 02 0 51 13 0 47 12 0 0079 or less 0 20 or less 0 039 1 00 Ø1 3 8 34 92 1 3 8 0 0012 34 90 0 04 1 38 0 0016 0 0016 35 11 0 04 0 04 0 55 14 0 51 13 0 0098 or less 0 25 or less 0 047 1 20 Ø1 5 8 41 28 1 5 8 0 0012 41 28 0 05 1 63 0 0031 0 0008 42 28 0 08 0 02 0 59 15 0 55 14 0 0110...

Page 11: ...012 type 12 015 type 15 4 018 type 18 021 type 21 024 type 24 027 type 27 030 type 30 036 type 36 042 type 42 048 type 48 054 type 54 072 type 72 096 type 96 Table 2 Outdoor unit capacity type Outdoor unit capacity code Maximum number of indoor units 1 Height difference between indoor units 49 ft 15 m or less Over 49 ft 15 m 072 type 72 12 10 096 type 96 16 13 120 type 120 21 16 144 type 144 25 19...

Page 12: ...BM HY1083UL 134 to below 240 RBM HY2083FUL RBM HY2083UL 9 Outdoor unit connection piping kit Total capacity code of the outdoor units at downstream side 1 7 Model name Below 247 RBM BT14FUL 247 or more RBM BT24FUL 10 Flow Selector unit 9 Single port type 10 Single port long piping type 11 Total capacity code of outdoor units on downstream side from FS unit Model name Below 38 RBM Y0383FUL RBM Y112...

Page 13: ...its H1 H3 t n i o j g n i h c n a r b d e p a h s Y g n i h c n a r b t s r i F Indoor unit connecting pipe Indoor unit The longest piping length L The longest piping length from the first branch Li The longest piping length in Flow selector unit group Ln Flow Selector unit Indoor unit H4 Height difference between indoor units H2 CAUTION Please use the appropriate pipe when the pipe size is Ø3 4 o...

Page 14: ...e first branch Li H1 9 8 ft 164 L3 L4 L5 L6 L7 L8 o L3 L9 L10 L11 t L3 L9 L12 L13 v H1 9 8 ft 213 Farthest equivalent piping length between outdoor units LO 49 LA Lc LA Lb Maximum equivalent piping length of pipes connected to outdoor units 33 Lc La Lb Maximum real length of terminal branching section to indoor units 98 a f b g c h d i e j k l L6 L7 L8 o Ln Maximum real length of between Flow Sele...

Page 15: ... the amount and charge it additionally Model name Refrigerant amount charged in factory MMY MAP 0726FT6P UL 24 3 lbs 0966FT6P UL 1206FT6P UL 1446FT6P UL 1686FT6P UL 2 Additional refrigerant charge please calculate from the calculation of additional refrigerant charge amount Airtightness test After the refrigerant piping has been finished execute an airtight test For an airtight test connect a nitr...

Page 16: ...ates minus as the result of calculation use the air conditioner without additional refrigerant Table1 Compensation by capacity of outdoor unit Outdoor unit capacity type Model name Standard Model Compensation by capacity type outdoor unit lbs 072 type MMY MAP0726FT6P UL 4 4 096 type MMY MAP0966FT6P UL 6 6 120 type MMY MAP1206FT6P UL 17 6 144 type MMY MAP1446FT6P UL 24 3 168 type MMY MAP1686FT6P UL...

Page 17: ...rant can added to the system the charging process is finished 4 If the total calculated amount of refrigerant cannot be added to the system close the valve on the refrigerant bottle move the charging hose from the liquid line service port to the suction line service port 5 Open the suction and liquid service valves on the header unit and start the system in cooling mode 6 Slowly open the valve on ...

Page 18: ... specifications Every outdoor unit must have a dedicated power supply L1L2L3 L1L2L3 L1L2L3 Main power circuit breaker Disconnect per NEC and local codes Power wiring selection MCA Minimum Circuit Amps MOCP Maximum Overcurrent Protection Amps Model name Standard Model Power Supply Voltage Range MCA A MOCP A Nominal Voltage Phase and frequency Min V Max V MMY MAP0726FT6P UL 460 V 3 60 Hz 414 506 11 ...

Page 19: ...6m If the length between indoor unit and Flow selector unit exceeds 16 ft 5 m connect by using the Connection cable kit sold separately RBC CBK15UL Restriction of control wiring Be sure to keep the rule of below tables about size and length of control wiring L6 L7 L3 L5 L1 L4 L2 A B A B A B L8 U1 U2 A B U3 U4 U1 U2 U5 U6 U3 U4 U1 U2 U5 U6 U3 U4 U1 U2 U5 U6 U3 U4 U1 U2 U5 U6 U1 U2 A B U1 U2 A B U1 ...

Page 20: ...ntrally controlled Address setting procedure See procedure 1 See procedure 2 Control wiring diagram Outdoor Indoor Indoor Indoor Indoor Outdoor Central control Remote control Remote control Remote control Central control Outdoor Indoor Indoor Indoor Indoor Outdoor Remote control Remote control Remote control Central control Access cover Electrical control box cover Access cover screw Screw size an...

Page 21: ...ut may takes as long as 10 minutes to complete the auto address setting for 1 refrigerant line 4 The 7 segment display will indicate Auto 1 Auto 2 Auto 3 When the address sequence has covered all the fan coils for a refrigerant line auto the 7 segment display will indicate U 1 flashing When the flashing stops and the display indicates U 1 without flashing the address setting is complete Interface ...

Page 22: ...ning energizing the outdoor units confirm that the 7 segment display on the interface P C board of the header outdoor unit indicates U 1 L08 The U 1 will be flashing 5 Press SW15 to start the automatic address setting It normally takes 5 minutes but may take as long as 10 minutes to complete the auto address setting for 1 refrigerant line 6 The 7 segment display will indicate Auto 1 Auto 2 Auto 3 ...

Page 23: ...1 Header unit 2 Follower unit 2 Follower unit 2 Follower unit 2 Follower unit Switch setting setting example when controlling 2 or more refrigerant lines centrally Outdoor units setting manually The items in bold font must be set manually Outdoor unit s interface P C board Header unit Follower unit Header unit Follower unit Header unit Factory default SW13 14 See chart on page 20 Line system addre...

Page 24: ... 4 seconds The LCD display will start flashing To set line system address 2 Push the TEMP buttons repeatedly to set the CODE No to 3 Push the TIME buttons repeatedly to set a system address Match the address with the address on the interface P C board of the header outdoor unit in the same refrigerant line 4 Push SET button This saves the setting To set indoor unit address 5 Push the TEMP buttons ...

Page 25: ...L FILTER RESET TEST TIMER SET CODENo UNIT No SETTING DATA SET R C No 2 7 1 4 6 5 3 1 Simultaneously push and hold the TIME and TEST TEST buttons for more than 4 seconds 2 The LCD will display LINE and CODE No 3 Push the left end of the UNIT LOUVER button and the SWING FIX SWING FIX repeatedly to select a system address 4 Push the SET SET button to confirm the address selection The address of an in...

Page 26: ...necting with one indoor unit or one group in one branching it is necessary to set up 0 Heating prioritized Factory default 1 Cooling prioritized Resetting to factory default address Method 1 Follow steps 1 through 11 by using a direct wired remote control page 22 to reset line system address indoor unit addresses and group addresses to 0099 Method 2 Clearing all the indoor unit addresses on a sing...

Page 27: ...tween indoor unit and FS unit Within 49 ft 15 m Remote control Indoor unit Indoor unit Multi port type FS unit 1 Remote control Group control Piping Group control In case of connecting two group operations of indoor units 14 1 2 1 2 0E 1 1 1 1 FE 1 1 1 1 FD 0 0 0 0 0E 1 1 1 1 14 1 2 1 2 FE 1 1 1 1 FD 0 0 0 0 Single port type FS unit Piping Control wiring between indoor unit and FS unit Within 49 f...

Page 28: ...l TEST 4 Push the ON OFF button to stop running after finishing the trial run The indication on the LCD display returns to the status of procedure 1 5 Push the TEST button to exit the test mode TEST disappears on the LCD display and the status changes to normal stopped mode In case of connecting one group operation of indoor units and two indoor units 0E 1 1 0 0 14 1 2 0 0 FE 1 1 1 1 FD 0 0 0 0 0E...

Page 29: ...isplay A U1 B 2 Set the rotary switches on the interface P C board of the header outdoor unit SW01 to 16 SW02 and SW03 to the address of the indoor unit to be tested SW02 SW03 Indoor unit address 1 to 16 1 1 to 16 Set number of SW02 1 to 16 2 17 to 32 Set number of SW02 16 1 to 16 3 33 to 48 Set number of SW02 32 1 to 16 4 49 to 64 Set number of SW02 48 7 segment display A Address display of the c...

Page 30: ...hooting In addition to the CODE No on the remote control of an indoor unit you can diagnose failure type of an outdoor unit by checking the 7 segment display on the interface P C board Use the function for various checks Set every DIP switch to OFF after checking 7 Segment display and check code Rotary switch setting value Indication LED D600 A B D601 D602 D603 D604 SW01 SW02 SW03 1 1 1 Outdoor un...

Page 31: ...age trouble 1 Position detection circuit trouble 2 Input current sensor trouble 3 Motor lock trouble C Sensor temperature trouble No TH sensor 4 Motor current trouble D Sensor short circuit release trouble No TH sensor 5 Synchronization step out trouble Put in Fan IPDU No in mark Outdoor fan IPDU trouble P26 01 Compressor 1 02 Compressor 2 IPM short protection trouble P29 01 Compressor 1 02 Compre...

Page 32: ...th a gas leakage detector in the smallest room where the density limit is exceeded the volume of the next smallest room becomes the object Refrigerant piping Outdoor unit Indoor unit Mechanical ventilation device Gas leak detector Small room Medium room Large room Very small room SMMS wave tool SMMS wave tool is an application software Application for the Android OS smartphone and for those who in...

Page 33: ...et les autocollants apposés sur l appareil Porter des lunettes et des gants de protection Faites attention lors de la manipulation et du montage des appareils lourds et encombrants Lisez attentivement des instructions et respectez les consignes et précautions figurant dans la documentation fournie Consultez les codes locaux de construction et le National Electrical Code NEC pour connaître les exig...

Page 34: ...ge exigeant d accéder aux pièces électriques du panneau portez des gants de protection contre la chaleur des chaussures isolantes et des vêtements adéquats afin de ne pas être exposé aux secousses électriques Dans le cas contraire vous vous exposez à une secousse électrique Utilisez un câblage respectant les spécifications du Manuel d installation de NEC et de la législation locales Assurez vous q...

Page 35: ...iles car sa pression est d environ 1 6 fois celle du précédent fluide frigorigène Avec l adoption de ce nouveau fluide frigorigène l huile pour machine frigorifique a aussi été changée Par conséquent pendant les travaux d installation veillez à ce que de l eau de la poussière de l ancien fluide frigorigène ou de l huile pour machine frigorifique ne pénètrent pas dans le cycle de réfrigération d un...

Page 36: ...ertisseur alternateur appareil médical équipements de communications Une anomalie de fonctionnement ou un défaut de contrôle du climatiseur sont possibles dans les situations envisagées Un endroit tel que l air évacué par l unité extérieure est dirigé vers une fenêtre d un bâtiment voisin Un endroit qui ne peut pas supporter le poids de l unité Un endroit peu ventilé Espace d installation Unité de...

Page 37: ...eur ou un autre équipement pour les travaux de charge ou de décharge lors du transport engagez les fourches dans les découpes rectangulaires pour manutention comme le montre l illustration ci dessous Pour soulever l unité engagez dans les découpes rectangulaires indiquées ci dessous une corde capable de supporter le poids de l unité Serrez l unité sur les 4 côtés Posez des garnitures aux emplaceme...

Page 38: ...tion 7 9 200mm au moins 0 8 20mm ou plus L L Boulon d ancrage M12 4 positions unité 0 8 20 Les positions des boulons d ancrage sont indiquées ci dessous A A A B A C B B L L B Trou continu Trou 0 6 0 8 15 20 de long L 11 4 290 L 11 4 290 29 7 755 31 1 790 Seuls les types MAP144 et MAP168 comportent des trous pour une force supplémentaire Type de modèle A B C L MAP0726 27 6 700 39 0 990 Recommandati...

Page 39: ...as des raccords en T côté liquide il n existe aucune restriction en termes d inclinaison A B 19 7 500mm ou plus Horizontalement Si vous utilisez le raccord en forme de Y pour raccorder les unités extérieures entre elles raccord de gaz côté évacuation et raccord de gaz côté aspiration veuillez conserver la partie droite sur au moins 19 7 500mm à l entrée Ligne horizontale Ligne horizontale Vue selo...

Page 40: ... Les tuyaux de réfrigérant doivent être neufs et propres de manière que l eau et les poussières ne contaminent pas le réfrigérant Assurez vous d utiliser deux clés pour serrer ou desserrer l écrou évasé Avec une seule clé le serrage prescrit ne peut pas être obtenu Serrez l écrou évasé au couple prescrit Si vous avez des difficultés à serrer ou desserrer l écrou du tuyau d équilibre ou de la vanne...

Page 41: ...tées diffère selon la différence de hauteur entre les unités intérieures Si la différence de hauteur entre les unités intérieures est de 15 m 49 ft ou moins Le code de capacité intérieure totale doit être compris entre 50 et 135 de la capacité de l unité extérieure Si la différence de hauteur entre les unités intérieures est supérieure à 15 m 49 ft Le code de capacité doit être compris entre 50 et...

Page 42: ...60 360 63 49 Type 384 384 64 52 Type 408 408 64 55 Type432 432 64 59 Type 456 456 64 63 Pour l association des unités extérieures reportez vous à Association d unités extérieures 1 Sous commande centralisée 54 unités maximum 1 1 1 9 4 5 7 7 2 9 4 10 5 4 10 5 4 4 3 6 6 4 5 10 7 7 4 4 10 4 3 7 4 3 7 6 6 6 1 Ø3 8 Unité principale A Unité secondaire B Unité secondaire C Unité extérieure 8 Branchement ...

Page 43: ...rieures Codes de capacité totale des unités extérieures côté sortie vers le bas 1 7 Modèle Au dessous de 247 RBM BT14FUL 247 ou plus RBM BT24FUL 10 Sélecteur de débit 9 Port simple 10 Type à port unique à tuyauterie longue 11 Code de capacité totale des unités extérieures du côté en aval depuis l unité de sélecteur de débit Modèle Au dessous de 38 RBM Y0383FUL RBM Y1124FUL 38 à moins de 61 RBM Y06...

Page 44: ...ence de hauteur entre unités intérieures et extérieures Raccord de branchement en Y Longueur maximum de tuyau pour la première branche Premier branchement p q r s t Sélecteur de débit à port multiple Tuyau de connexion des unités intérieures Raccord de branchement en Y Unité intérieure L9 L11 H5 L10 L12 u v H6 L13 Sélecteur de débit à port simple Modèle à tuyauterie longue PRÉCAUTION Veuillez util...

Page 45: ...L11 t L3 L9 L12 L13 v H1 9 8 ft 213 Longueur de tuyau maximale équivalente entre les unités extérieures LO 49 LA Lc LA Lb Longueur maximum équivalente de tuyau connecté aux unités extérieures 33 Lc La Lb Longueur maximum réelle de la section de branchement de bornes aux unités intérieures 98 a f b g c h d i e j k l L6 L7 L8 o Ln Longueur maximum réelle entre le sélecteur de débit et l unité intéri...

Page 46: ... injecté à l usine MMY MAP 0726FT6P UL 24 3 lbs 0966FT6P UL 1206FT6P UL 1446FT6P UL 1686FT6P UL 2 Pour la quantité de réfrigérant supplémentaire veuillez calculer cela à partir du calcul de la quantité de réfrigérant supplémentaire Test d étanchéité à l air Lorsque la tuyauterie de réfrigérant est terminée procédez à un essai d étanchéité à l air Pour effectuer un test d étanchéité connectez un ré...

Page 47: ...cette quantité est négative utilisez le climatiseur tel qu il est Tableau 1 Compensation par capacité de l unité extérieure Type de capacité de l unité extérieure Nom du modèle Modèle standard Compensation par capacité d unité extérieure lbs Type 072 MMY MAP0726FT6P UL 4 4 Type 096 MMY MAP0966FT6P UL 6 6 Type 120 MMY MAP1206FT6P UL 17 6 Type 144 MMY MAP1446FT6P UL 24 3 Type 168 MMY MAP1686FT6P UL ...

Page 48: ...uite de liquide sur l unité principale 3 Si la quantité calculée de réfrigérant peut être ajoutée au système le processus de charge est terminé 4 Si la quantité calculée de réfrigérant ne peut pas être ajoutée au système fermez la soupape du réservoir de réfrigérant déplacez le tuyau de remplissage du port de service de la conduite de liquide au port de service de la conduite d aspiration 5 Ouvrez...

Page 49: ...mande de groupe Caractéristiques de l alimentation électrique Chaque unité extérieure doit posséder une ligne d alimentation dédiée L1L2L3 L1L2L3 L1L2L3 Disjoncteur d alimentation principale Déconnexion conformément à NEC et à la législation locale Sélection du câblage MCA Ampères minimum dans le circuit MOCP Protection maximum de surintensité A Nom du modèle Modèle standard Alimentation électriqu...

Page 50: ... d accessoires de l unité FS Longueur de câble 6 m Si la longueur entre l unité intérieure et le sélecteur de débit dépasse 16 ft 5 m effectuez le raccordement avec le kit de câble de connexion vendu séparément RBC CBK15UL Restriction du câblage de commande Respectez les indications des tableaux ci dessous en matière de section et de longueur des câbles de communication L6 L7 L3 L5 L1 L4 L2 A B A ...

Page 51: ...mmande centralisée de 2 lignes ou plus de réfrigérant Procédure de réglage des adresses Voir la procédure 1 Voir la procédure 2 Schéma de câblage de commande Extérieure Intérieure Intérieure Intérieure Intérieure Extérieure Commande centralisée Télécommande Télécommande Télécommande Commande centralisée Extérieure Intérieure Intérieure Intérieure Intérieure Extérieure Télécommande Télécommande Tél...

Page 52: ... l adressage automatique d une ligne de réfrigérant mais cela peut prendre parfois jusqu à 10 minutes 4 L écran à 7 bâtonnets indique Auto 1 Auto 2 Auto 3 Quand la séquence d adressage a atteint tous les ventilo convecteurs pour une ligne de réfrigérant auto U 1 clignote sur l écran à 7 bâtonnets Quand le clignotement s arrête te que U 1 reste allumé le réglage des adresses est terminé Carte d int...

Page 53: ...ension les unités extérieures 4 Une minute environ après la mise sous tension des unités extérieures assurez vous que l écran à 7 bâtonnets de la carte d interface de l unité extérieure principale indique U 1 L08 U1 clignote 5 Appuyez sur SW15 pour démarrer le réglage automatique des adresses Il faut normalement 5 minutes pour réaliser l adressage automatique d une ligne de réfrigérant mais cela p...

Page 54: ...3 1 2 Adresse de groupe 1 Unité principale 2 Unité secondaire 2 Unité secondaire 2 Unité secondaire 2 Unité secondaire Réglage de commutateur exemple pour la commande centralisée de 2 lignes de réfrigérant ou plus Unités extérieures réglage manuel Les postes en gras doivent être réglés manuellement Carte d interface de l unité extérieure Unité principale Unité secondaire Unité principale Unité sec...

Page 55: ...resse de ligne système 2 Appuyez sur les boutons TEMP de manière répétée pour régler le CODE No sur 3 Appuyez sur les boutons TIME de manière répétée pour régler l adresse système Faites correspondre l adresse à l adresse de la carte d interface de l unité extérieure principale de la même ligne de réfrigérant 4 Appuyez sur la touche SET Cela permet de sauvegarder le réglage Pour régler l adresse d...

Page 56: ...EMP TIME SET CL FILTER RESET TEST TIMER SET CODENo UNIT No SETTING DATA SET R C No 2 7 1 4 6 5 3 1 Appuyez simultanément sur les boutons TIME et TEST TEST et maintenez les enfoncés pendant plus de 4 secondes 2 LINE et CODE No sont affichés sur l écran LCD 3 Appuyez répétitivement sur le côté gauche du bouton UNIT LOUVER et SWING FIX SWING FIX pour sélectionner une adresse de système 4 Appuyez sur ...

Page 57: ...cas autres que le raccordement à une unité intérieure ou un groupe dans un branchement la configuration est nécessaire 0 Chauffage prioritaire Défaut usine 1 Refroidissement prioritaire Réinitialisation aux adresses par défaut Méthode 1 Suivez les étapes 1 à 11 à l aide de la télécommande câblée directe page 53 pour réinitialiser l adresse de la ligne système les adresses des unités intérieures et...

Page 58: ...ie Câbles de commande entre les unités intérieures et unité FS Moins de 49 ft 15 m Unité intérieure Unité intérieure SD à port multiple 1 Télécommande Commande de groupe Tuyauterie Commande de groupe En cas de raccordement de deux opérations de groupe d unités intérieures 0E 1 1 1 1 14 1 2 1 2 FE 1 1 1 1 FD 0 0 0 0 0E 1 1 1 1 14 1 2 1 2 FE 1 1 1 1 FD 0 0 0 0 SD à port simple Tuyauterie Câbles de c...

Page 59: ...onnement Les codes de vérification sont détectés comme d habitude TEST 4 Appuyez sur ON OFF pour arrêter le fonctionnement à la fin de l essai L indication sur l écran à cristaux liquides redevient celle de la procédure 1 5 Appuyez sur la bouton TEST pour quitter le mode d essai TEST disparaît de l écran à cristaux liquides et l état retourne au mode d arrêt normal En cas de raccordement d une seu...

Page 60: ...acez les commutateurs rotatifs de la carte d interface de l unité extérieure principale SW01 à 16 SW02 et SW03 sur les adresses des unités intérieures à tester SW02 SW03 Adresse d unité intérieure De 1 à 16 1 De 1 à 16 Nombre réglé de SW02 De 1 à 16 2 De 17 à 32 Nombre réglé de SW02 16 De 1 à 16 3 De 33 à 48 Nombre réglé de SW02 32 De 1 à 16 4 De 49 à 64 Nombre réglé de SW02 48 Écran à 7 bâtonnets...

Page 61: ...31 Problèmes du compresseur IPDU 11Résolution des problèmes Outre le CODE No sur la télécommande de l unité intérieure vous pouvez diagnostiquer une panne de l unité extérieure en consultant l écran à 7 bâtonnets de la carte d interface Utilisez la fonction pour les essais variés Réglez chaque DIP switch sur OFF après vérification Écran à 7 bâtonnets et mode de vérification Valeur de réglage des c...

Page 62: ...étection de la position 2 Problème du capteur de courant en entrée 3 Problème verrouillage moteur C Problème de température du capteur pas de capteur TH 4 Problème de courant dans le moteur D Court circuit du capteur Problème de déverrouillage pas de capteur TH 5 Problème de synchronisation sortie Accompagner le nº de ventilateur IPDU du symbole Problème IPDU ventilation unité extérieure P26 01 Co...

Page 63: ...yenne Grande pièce Très petite pièce SMMS wave tool SMMS wave tool est un programme d application Application pour smartphone Android OS destiné aux personnes qui installent et effectuent des travaux de maintenance sur des équipements de climatisation compatibles L Application permet de vérifier certains points du système ainsi que certaines données et de mener des tests sur les équipements de cli...

Page 64: ...HAILAND CO LTD 144 9 MOO 5 BANGKADI INDUSTRIAL PARK TIVANON ROAD TAMBOL BANGKADI AMPHUR MUANG PATHUMTHANI 12000 THAILAND 1122001001 2 1122001001 2_EN FR indb 1 1122001001 2_EN FR indb 1 2 18 17 11 45 AM 2 18 17 11 45 AM ...

Reviews: