Function to Start/Stop (ON/OFF)
29
The following functions of the indoor unit can start or stop by the switches on the interface P.C. board of the header unit.
No
1
2
3
4
Function
Cooling test
operation
Heating test
operation
Batch start
Batch stop
Individual start
Individual stop
Individual test
operation
Outline
Changes the mode of all the
connected indoor units collectively
to cooling test operation.
Note)
Control operation same as usual
test operation from remote
control is performed.
Changes the mode of all the
connected indoor units collectively
to heating test operation.
Note)
Control operation same as usual
test operation from remote
control is performed.
Starts all the connected indoor
units collectively.
Note)
The contents follow to the setup
of remote controller.
Stops all the connected indoor
units collectively.
Starts the specified indoor unit.
Notes)
• The contents follow to the
setup of remote controller.
• The other indoor units keep the
status as they are.
Stops the specified indoor unit.
Note)
The other indoor units keep the
status as they are.
Operates the specified indoor unit.
Note)
The other indoor units keep the
status as they are.
Setup/Release
[Setup]
Set SW01/SW02/SW03 to [2/5/1], and
push SW04 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
[Setup]
Set SW01/SW02/SW03 to [2/6/1], and
push SW04 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
[Setup]
Set SW01/SW02/SW03 to [2/7/1], and
push SW04 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1]
[Setup].
Set SW01/SW02/SW03 to [2/7/1], and
push SW05 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1].
[Setup]
Set SW01 to [16], set SW02 and SW03 to
address No. (1 to 64) to be started, and
push SW04 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
[Setup]
Set SW01 to [16], set SW02 and SW03 to
address No. (1 to 64) to be stopped, and
push SW05 for 2 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
[Setup]
Set SW01 to [16], set SW02 and SW03 to
address No. to be operated, and push
SW04 for 10 seconds or more.
[Release]
Return SW01/SW02/SW03 to [1/1/1].
7-segment display
Section A
Section B
[C. ]
[
⎯
C ]
Section A
Section B
[H. ]
[
⎯
H ]
Section A
Section B
[C. H]
[ 11 ]
[00] is displayed on Section
B for 5 seconds.
Section A
Section B
[C. H]
[00]
[00] is displayed on Section
B for 5 seconds.
Section A
Section
[ ]
[ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ 11] for 5 seconds
from operation-ON.
Section A
Section
[ ]
[ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ 00] for 5 seconds
from operation-OFF.
Section A
Section
[ ]
[ ]
Section A:
Displays the corresponding
indoor address.
Section B:
Displays [ FF] for 5 seconds
from test operation-ON.
NOTES
1) This start/stop function only sends the signals from the outdoor unit to the indoor unit, such as start, stop, operation mode, etc.
It does not resend the signals even if the indoor unit does not follow the sent signals.
2) The above controls are not used during abnormal stop.
SW02 SW03
SW01
SW04
SW05
7-segment display [A]
7-segment display [B]
<Rotary switches>