– 17 –
Table 2
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Equivalent
HP
Model name of
outdoor unit
MMY-
Combination of outdoor unit
MMY-
Corrective of
refrigerant
(kg)
Unit 1
Unit 2
Unit 3
8 HP
MAP0804
✽
MAP0804
✽
–
–
2
10 HP
MAP1004
✽
MAP1004
✽
–
–
3
12 HP
MAP1204
✽
MAP1204
✽
–
–
8
14 HP
MAP1404
✽
MAP1404
✽
–
–
10
16 HP
AP1614
✽
MAP0804
✽
MAP0804
✽
–
0
18 HP
AP1814
✽
MAP1004
✽
MAP0804
✽
–
1.5
20 HP
AP2014
✽
MAP1004
✽
MAP1004
✽
–
3.5
22 HP
AP2214
✽
MAP1204
✽
MAP1004
✽
–
7.5
24 HP
AP2414
✽
MAP1404
✽
MAP1004
✽
–
8.5
26 HP
AP2614
✽
MAP1404
✽
MAP1204
✽
–
11
28 HP
AP2814
✽
MAP1404
✽
MAP1404
✽
–
12
30 HP
AP3014
✽
MAP1004
✽
MAP1004
✽
MAP1004
✽
2.5
32 HP
AP3214
✽
MAP1204
✽
MAP1004
✽
MAP1004
✽
5
34 HP
AP3414
✽
MAP1404
✽
MAP1004
✽
MAP1004
✽
6
36 HP
AP3614
✽
MAP1204
✽
MAP1204
✽
MAP1204
✽
8
38 HP
AP3814
✽
MAP1404
✽
MAP1204
✽
MAP1204
✽
9.5
40 HP
AP4014
✽
MAP1404
✽
MAP1404
✽
MAP1204
✽
11
42 HP
AP4214
✽
MAP1404
✽
MAP1404
✽
MAP1404
✽
12.5
Full opening of the valve
Open the valves of the outdoor unit fully.
After opening the valves fully, be sure to close the caps.
When you close the valve shaft, its cap and service port cap, see below chart.
MAP080
MAP100
MAP120
MAP140
Balance pipe
Ø9.5 packed valve
Using a 4 mm-hexagonal wrench, fully open the valve shaft.
Liquid side
Ø12.7 packed valve
Using a 4 mm-hexagonal wrench, fully open the
valve shaft.
Ø15.9 packed valve
Using a 5 mm-hexagonal wrench, fully open the
valve shaft.
Discharge gas
side
Ø19.1 ball valve
Using a flathead screwdriver, turn it counterclockwise by 90° until it hits the stopper. (Full open)
Suction gas side
Ø25.4 ball valve
Using a wrench, turn the valve shaft counterclockwise by 90° until it hits the stopper. (Full open)
Valve size
Tightening torque
Valve shaft cap (N·m)
Service port cap (N·m)
Valve shaft (N·m)
Ø9.5 packed valve
14 to 18
14 to 18
7 to 9
Ø12.7 packed valve
20 to 25
14 to 18
7 to 9
Ø15.9 packed valve
33 to 42
14 to 18
14 to 16
Ø19.1 ball valve
20 to 25
14 to 18
–
Ø25.4 ball valve
20 to 25
14 to 18
–
Using flathead screwdriver, turn
it counterclockwise by 90° until
it hits the stopper. (Full open)
Service port
Flare nut
Valve
unit
(1)
(2)
Fully closed
Fully opened
Slot
Position of screwdriver slot
*
When opened fully, do not apply excessive torque
after the screwdriver hits the stopper; otherwise a
problem may be caused on the valve. (5 N•m or less)
Fully closed
Fully opened
33-EN
34-EN