background image

– 28 –

4

Push the TIME 

 / 

 buttons repeatedly to 

change the value indicated in the SET DATA 
section to that you want.

5

Push the 

 button.

6

Push the 

 button (left side of the 

button) repeatedly to select another indoor 
UNIT No. to change.

Repeat steps 

4

 to 

6

 to change the indoor unit 

addresses so as to make each of them unique.

7

Push the 

 button (left side of the 

button) to check the changed addresses.

8

If the addresses have been changed 
correctly, push the 

 button to finish the 

procedure.

To change all the indoor unit addresses using 
an arbitrary wired remote controller.
(The method is available when the addresses 
have already been set automatically.)

(When communication wirings of 2 or more 
refrigerant lines are interconnected for central 
control) 

NOTE

You can change the addresses of indoor units in each 
refrigerant line using an arbitrary wired remote controller.

* Enter the address check / change mode and change 

the addresses. 

If no number appears on UNIT No., no outdoor unit exists on 
the line. Push 

 button and select another line following 

step 

2

(Execute it while the units are stopped.)

1

Push and hold the TIME 

 and 

 buttons 

at the same time for more than 4 seconds.
At first, the line 1 and CODE No. 

 

(Address Change) are indicated on the LCD 
display.

2

Push 

 (left side of the button) and 

 buttons repeatedly to select a system 

address.

3

Push the 

 button.

• The address of one of the indoor units 

connected to the selected refrigerant line is 
indicated on the LCD display and the fan and 
louvers of the unit are activated.
At first, the current indoor unit address is 
displayed in 

SET DATA

.

(No system address is indicated.)

SET

TEST

3

1

ON / OFF

TEMP.

TIME

SET CL

FILTER

RESET TEST

TIMER SET

CODE No.

UNIT   No.

SETTING

DATA

SET

R.C.

No.

2

Cancels the line selection

CL

TEST

SWING/FIX

SET

4

Push the TIME 

 / 

 buttons repeatedly to 

change the value of the indoor unit address 
in SET DATA.
Change the value in SET DATA to that of a 
new address. 

5

Push the 

 button to confirm the new 

address on SET DATA. 

6

Push the 

 button (left side of the 

button) repeatedly to select another address 
to change. Each time you push the button, 
the indoor unit numbers in a refrigerant line 
are indicated one after another. Only the fan 
and louvers of the selected indoor unit are 
activated. 

Repeat steps 

4

 to 

6

 to change the indoor unit 

addresses so as to make each of them unique.

7

Push the 

 button.

(All the segments on the LCD display light up.)

8

Push the 

 button to finish the procedure.

Resetting the address
(Resetting to the factory 
default (address undecided))

Method 1

Clearing each address separately using a wired remote 
controller.
Set the system address, indoor unit address and group 
address to “0099” using a wired remote controller.
(For the setting procedure, refer to the address setting 
procedures using the wired remote controller on the previous 
pages.)

Method 2

Clearing all the indoor unit addresses on a refrigerate line at 
once from the outdoor unit.

1

Turn off the refrigerant line to reset to the 
factory default and set the header outdoor 
unit of the line as below.

1) Disconnect the relay connectors between the 

[U1, U2] and [U3, U4] terminals.
(Leave them as they are if they have already 
been disconnected.)

2) Turn on dip switch 2 of SW30 on the interface 

P.C. board of the header outdoor unit if the 
switch is OFF.
(Leave it as it is if it has already been set to 
ON.)

4
8

5, 7 

ON / OFF

TEMP.

TIME

SET CL

FILTER

RESET TEST

TIMER SET

CODE No.

UNIT   No.

SETTING

DATA

SET

R.C.

No.

6

Press to finish 

setting.

Finish

SET

SET

TEST

55-EN

56-EN

Summary of Contents for MMY-MAP0804FT8-E

Page 1: ...me MMY MAP0804FT8 E MMY MAP1004FT8 E MMY MAP1204FT8 E MMY MAP1404FT8 E MMY MAP0804FT8Z E MMY MAP1004FT8Z E MMY MAP1204FT8Z E MMY MAP1404FT8Z E MMY MAP0804FT8ZG E MMY MAP1004FT8ZG E MMY MAP1204FT8ZG E MMY MAP1404FT8ZG E Installation Manual For commercial use ...

Page 2: ...e 6 5 Carrying in the outdoor unit 7 6 Installation of the outdoor unit 8 7 Refrigerant piping 10 8 Electric wiring 19 9 Address setting 23 10 How to set up the cooling only indoor unit 30 11 Test run 31 12 Troubleshooting 32 13 Machine card and logbook 34 ADOPTION OF NEW REFRIGERANT This Air Conditioner uses R410A an environmentally friendly refrigerant 1 EN 2 EN ...

Page 3: ...k at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work Qualified service person The qualified service person is a person who insta...

Page 4: ...nditioner If the compressor is operated with the valve open and without refrigerant pipe the compressor sucks air and the refrigeration cycles is over pressurized which may cause a injury Tighten the flare nut with a torque wrench in the specified manner Excessive tighten of the flare nut may cause a crack in the flare nut after a long period which may result in refrigerant leakage Ventilate the a...

Page 5: ...ied Installer or Qualified Service Person CAUTION New refrigerant air conditioner installation This air conditioner adopts the new HFC refrigerant R410A which does not destroy ozone layer The characteristics of R410A refrigerant are easy to absorb water oxidizing membrane or oil and its pressure is approx 1 6 times higher than that of refrigerant R22 Accompanied with the new refrigerant refrigerat...

Page 6: ...former refrigerant by approximately 1 6 times As well as the adoption of the new refrigerant the refrigerating oil has been also changed Therefore pay attention so that water dust former refrigerant or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation To prevent mixing of refrigerant or refrigerating oil the size of the charge port ...

Page 7: ...ent temperature falls below 15 C for more than 72 hours running The outdoor heat exchanger may be damaged by the frost The cooling performance may decline considerably when total operating capacity of cooling indoor units is less than 4HP while ambient temperature is below 0 C Installation space Leave space necessary for running installation and servicing NOTE If there is an obstacle above the out...

Page 8: ... comes into contact with the outdoor unit so that no damage is caused to the outer surface of the outdoor unit There are reinforcing plates on the side surfaces so the rope cannot be passed through Front Back GOOD NO GOOD NO GOOD Plaster Rope Plaster Rectangular holes for lifting Reinforcing plate Prongs of the forklift Rectangular holes for handling GOOD NO GOOD Side Weight centre and weight Weig...

Page 9: ...and the air discharge Leave enough space for the snowfall hood so that it will not be an obstacle for the air intake and the air discharge 1 To install multiple outdoor units arrange them with 20 mm or more spaces in between Fix each outdoor unit with M12 anchor bolts at 4 positions 20 mm projection is appropriate for an anchor bolt Snowfall hood for air discharge locally procured Snowfall hood fo...

Page 10: ... 15 degrees Horizontal line Within 15 degrees Horizontal line A arrow view At a level position B arrow view Do not connect a branch unit vertically Header unit A Follower unit B Follower unit C Main pipe To indoor unit Liquid joint Discharge gas joint Good Header unit A Follower unit B Follower unit C To indoor unit Main pipe No Good Liquid joint Discharge gas joint Suction gas pipes Suction gas j...

Page 11: ...a brazing work of the refrigerant pipes be sure to use nitrogen gas in order to prevent oxidation of the inside of the pipes otherwise clogging of the refrigerating cycle due to oxidized scale may occur Use clean and new pipes for the refrigerant pipes and perform piping work so that water or dust does not contaminate the refrigerant Remove all flux after brazing Be sure to use a double spanner to...

Page 12: ...pipe Liquid pipe Suction side gas pipe Suction side gas pipe Section to be cut L shaped pipe Socket Pipe Pipe Attachment pipe Attachment pipe Pipe Socket Socket B Extruding margin of copper pipe with flare tools A Unit mm When using the conventional flare tool to connect R410A pipes with flaring make a margin approx 0 5 mm longer than that of an R22 pipe so that the flare size matches the one spec...

Page 13: ...HP 56 33 AP2214 22 HP 61 5 37 AP2414 24 HP 68 40 AP2614 26 HP 73 43 AP2814 28 HP 78 5 47 AP3014 30 HP 85 48 AP3214 32 HP 90 48 AP3414 34 HP 96 48 AP3614 36 HP 101 48 AP3814 38 HP 106 5 48 AP4014 40 HP 112 48 AP4214 42 HP 118 48 NOTE Compared with the capacity code of the outdoor unit the total value of capacity codes of the connectable indoor units differs based on the height difference between th...

Page 14: ...flow selector unit and the dedicated cooling circuit 3 Select the branch pipe of the first branch according to the outdoor capacity code 4 Select according to the outdoor unit capacity code if the total of the indoor capacity codes exceeds the outdoor unit capacity code 5 It is possible to select up to a maximum capacity code total AP056 6 hp for the first circuit after the header branch When usin...

Page 15: ...etween outdoor units LO 15 m System restriction Limit on connecting multiple indoor units to flow selector unit Cautions for installation Set the outdoor unit first connected to the bridging pipe to the indoor units as the header unit Install the outdoor units in order of their capacity codes A header unit B C When connecting gas pipes to indoor units use Y shaped branching joints to keep pipes le...

Page 16: ... m Airtightness test After the refrigerant piping has been finished execute an airtight test For an airtight test connect a nitrogen gas canister as shown in the figure below and apply pressure Be sure to apply pressure from the service ports of the packed valves or ball valves at the liquid side discharge gas side suction gas side and balance pipe side An airtight test can only be performed at th...

Page 17: ...ing of refrigerant To protect the world s environment do not release chlorofluorocarbons into the atmosphere Do not do an air purge including used refrigerant P VL VH Connected to indoor unit Main pipe Low pressure gauge High pressure gauge Brazed Fully closed Fully closed Connected to other follower units Balanced pipe side valve fully closed Service port Vacuum pump Gauge manifold Service port H...

Page 18: ...MAP1404 MAP1204 11 42 HP AP4214 MAP1404 MAP1404 MAP1404 12 5 Full opening of the valve Open the valves of the outdoor unit fully After opening the valves fully be sure to close the caps When you close the valve shaft its cap and service port cap see below chart MAP080 MAP100 MAP120 MAP140 Balance pipe Ø9 5 packed valve Using a 4 mm hexagonal wrench fully open the valve shaft Liquid side Ø12 7 pack...

Page 19: ...ns for refrigerant leaks may be required depending on European or local legislation 7 Contact dealers installers etc for any questions R410A kg kg kg Pre charged Refrigerant at Factory kg specified in the nameplate Additional Charge on Installation Site kg Heat insulation for pipe Apply heat insulation of pipe separately at the liquid gas and balance sides Be sure to use heat insulator resistant u...

Page 20: ...pipes has finished Refer to the installation manuals of indoor unit and flow selector unit for power wiring and communication wiring of indoor unit and flow selector unit Power supply specifications Do not bridge the power between outdoor units through the equipped terminal blocks L1 L2 L3 N Power supply for outdoor units NO GOOD Power wiring selection Standard model MCA Minimum Circuit Amps MOCP ...

Page 21: ... Group control Control wiring between indoor units Shield wire Flow selector unit Flow selector unit Flow selector unit Flow selector unit Be sure to keep the rule of below tables about size and length of communication wiring 1 Total length of Communication wiring length for all refrigerant circuits L1 L2 L3 L4 Table 1 Communication wiring between indoor and outdoor units L1 L2 L3 Central control ...

Page 22: ...ut for the power wire Knockout for the communication wire Power supply wire connection 1 Insert the power supply wire through the cutout on the side of the electrical control box and connect the power supply wire to the power supply terminal block and the earth wire to the earth screw After that fix the power supply wire with the 2 cord clamps 2 Be sure to use round type crimping terminals for pow...

Page 23: ...s greater than or equal to Ssc 1 at the interface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to Ssc 1 Furthermore when similar equipment or ot...

Page 24: ...rocedure 2 Example When controlling a single refrigerant line centrally When controlling 2 or more refrigerant lines centrally Address setting procedure To procedure 1 To procedure 2 System wiring diagram Access door cover Fixing screw for the access door cover Cover of the electrical control box Outdoor Indoor Indoor Indoor Indoor Outdoor Central remote controller Central remote controller Remote...

Page 25: ...ol Factory default disconnected 3 Turn on indoor units first and then turn on outdoor units 4 About 1 minute after turning the power on confirm that the 7 segment display on the interface P C board of the header outdoor unit indicates 5 Press SW 15 to start the automatic address setting It may take up to 10 minutes normally about 5 minutes to complete one line s setting 6 The 7 segment display ind...

Page 26: ...er unit Follower unit Header unit Follower unit Header unit Factory default SW13 14 Line system address 1 No setting required 2 No setting required 3 1 Dip switch 2 of SW30 Terminator of indoor outdoor communication line and central control line ON No setting required Set to OFF after setting addresses No setting required Set to OFF after setting addresses ON Relay connector Connect after setting ...

Page 27: ...oor unit address 5 Push the TEMP buttons repeatedly to set the CODE No to 6 Push the TIME buttons repeatedly to set an indoor unit address 7 Push the button It is OK if the display turns on Group address 8 Push the TEMP buttons repeatedly to set the CODE No to 9 Push the TIME buttons repeatedly to set a group address If the indoor unit is individual set the address to header unit follower unit 10 ...

Page 28: ...r units in a single refrigerant line When an outdoor unit is selected the indoor unit numbers of the refrigerant line of the selected unit are indicated one after another and the fan and louvers of the indicated indoor units are activated 1 Push and hold the TIME and buttons at the same time for more than 4 seconds At first the line 1 and CODE No Address Change are indicated on the LCD display Sel...

Page 29: ...ET CL FILTER RESET TEST TIMER SET CODENo UNIT No SETTING DATA SET R C No 2 Cancels the line selection CL TEST SWING FIX SET 4 Push the TIME buttons repeatedly to change the value of the indoor unit address in SET DATA Change the value in SET DATA to that of a new address 5 Push the button to confirm the new address on SET DATA 6 Push the button left side of the button repeatedly to select another ...

Page 30: ...ntrol controller Header unit Follower unit Follower unit Remote controller Remote controller Remote controller Remote controller Indoor units to have their addresses initialized Header unit Header unit Setting when connecting multiple indoor units to a FS Flow Selector unit Cautions to connection of indoor unit When connecting the multiple indoor units to a single FS unit it is necessary to set up...

Page 31: ...it No in the group control is displayed successively In this time the position of the indoor unit of which setup is to be changed can be confirmed because the fan and louver of the selected indoor unit work 3 Use and buttons of the set temperature to specify the CODE No 0F 4 Use and buttons of the timer time to select the setup data 0001 5 Push button In this time if the display changes from flash...

Page 32: ...unning after finishing the trial run The indication on the LCD display returns to the status of procedure 1 5 Push the button to exit the trial mode TEST disappears on the LCD display and the status changes to normal stopped mode 1 5 3 2 4 ON OFF TEMP TIME SET CL FILTER RESET TEST TIMER SET TEST TEST ON OFF MODE TEST ON OFF TEST When executing a test run using the interface P C board on the outdoo...

Page 33: ...unit Indicated when SW01 1 SW02 1 and SW03 1 Rotary switch setting value Indication LED SW01 SW02 SW03 1 1 1 Outdoor unit check code A Outdoor unit number U1 to U3 B Check code display Check code Check code name Indication on 7 segment display on the outdoor unit Auxiliary code E06 Number of indoor units which received normally Decrease of number of indoor units E07 Indoor outdoor communication ci...

Page 34: ...t address External interlock of indoor unit L31 Other compressor errors P03 Discharge temperature TD1 error Check code Check code name Indication on 7 segment display on the outdoor unit Auxiliary code 1PDU number information 01 Compressor 1 02 Compressor 2 03 Compressors 1 and 2 04 Compressor 3 05 Compressors 1 and 3 06 Compressors 2 and 3 07 Compressors 1 2 and 3 08 Fan 09 Compressor 1 and fan 0...

Page 35: ...burn centres Logbook Update the log periodically after maintenance as defined in EN378 4 Describe the following items on the logbook 1 details of the maintenance and repair works 2 quantities kind of new reused recycled refrigerant which have been charged on each occasion the quantities of refrigerant which have been transferred from the system on each occasion see also EN378 4 3 if there is an an...

Page 36: ...tioners is 0 3 kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10 kg The possible amount of leaked refrigerant gas in rooms D E and F is 15 kg NOTE 2 The standards for minim...

Page 37: ...EH99889397 ...

Reviews: