Function CODE No. (DN Code) Table (Includes All Functions Needed to Perform Applied Control on Site)
DN
Item
Description
At shipment
01
Filter display delay timer 0000: None
0002: 2500H
0004: 10000H
0001: 150H
0003: 5000H
According to type
02
Dirty state of filter
0000: Standard
0001: High degree of dirt (Half of standard time)
0000: Standard
03
Central control address
0001: No.1 unit
0099: Unfixed
to
0064: No.64 unit
0099: Unfixed
04
Specific indoor unit
priority
0000: No priority
0001: Priority
0000: No priority
06
Heating temp shift
0000: No shift
0002: +2°C
to
0001: +1°C
0010: +10°C
(Up to +6 recommended)
0002: +2°C
(Floor type 0000: 0°C)
0d
Existence of [AUTO]
mode
0000: Provided
0001: Not provided (Automatic selection from connected outdoor unit)
0001: Not provided
0F
Cooling only
0000: Heat pump
0001: Cooling only (No display of [AUTO] [HEAT])
0000: Heat pump
10
Type
0001: 4-way Air Discharge Cassette
Depending on model
type
11
Indoor unit capacity
0000: Unfixed
0001 to 0034
According to capacity
type
12
Line address
0001: No.1 unit
to
0030: No.30 unit
0099: Unfixed
13
Indoor unit address
0001: No.1 unit
to
0064: No.64 unit
0099: Unfixed
14
Group address
0000: Individual
0002: Follower unit of group
0001: Header unit of group
0099: Unfixed
19
Louver type
(Air direction
adjustment)
0000: No louver
0001: Swing only
According to type
0002: (1-way Air Discharge Cassette type, Under Ceiling type)
0003: (2-way Air Discharge Cassette type)
0004: (4-way Air Discharge Cassette type)
1E
Temp difference of
[AUTO] mode selection
COOL
$
HEAT,
HEAT
$
COOL
0000: 0 deg
to
0010: 10 deg
0003: 3 deg
(Ts±1.5)
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)
28
Automatic restart of
power failure
0000: None
0001: Restart
0000: None
2A
Selection of option/error
input (CN70)
0000: Filter input
0002: None
0001: Alarm input (Air washer, etc.)
0002: None
2E
HA terminal (CN61)
select
0000: Usual
0002: Fire alarm input
0001: Leaving-ON prevention control 0000: Usual
(HA terminal)
31
Ventilating fan control
0000: Unavailable
0001: Available
0000: Unavailable
32
TA sensor selection
0000: Body TA sensor
0001: Remote controller sensor
0000: Body TA sensor
33
Temperature unit select
0000: °C (at factory shipment)
0001: °F
0000: °C
F0
Swing mode
0001: Standard
0003: Cycle swing
0002: Dual swing
0001: Standard
F1
Louver fixed position
(Louver No.1)
0000: Release
0005: Downward discharge position
0001: Horizontal discharge position
0000: Not fixed
F2
Louver fixed position
(Louver No.2)
0000: Release
0005: Downward discharge position
0001: Horizontal discharge position
0000: Not fixed
F3
Louver fixed position
(Louver No.3)
0000: Release
0005: Downward discharge position
0001: Horizontal discharge position
0000: Not fixed
F4
Louver fixed position
(Louver No.4)
0000: Release
0005: Downward discharge position
0001: Horizontal discharge position
0000: Not fixed