8-5. Diagnosis procedure for each check code
Y
es
No
Y
es
Y
es
Y
es
No
Y
es
No
No
No
Y
es
No
[E
0
1
] /
[
–
]
(AI-NET)
Check code
Cause
Check code name
Check code
Cause
Check code name
Check code
Cause
Check code name
*
The check code is not indicated on the central control device or the 7-segment indication on the outdoor unit.
Y
es
No
[E
0
2
] /
[
–
]
(AI-NET)
[E03] / [97]
(AI-NET)
Communication error between the
indoor unit and remote controller
(detected on the remote
controller)
Signal transmission error on the
remote controller
Communication error between the
indoor unit and remote controller
(detected on the indoor unit)
1.
Remote controller inter-unit wire error
2.
Indoor power error
3.
Indoor P
.C. board error
4.
Remote controller address setup error
5.
Remote controller P
.C. board error
Unable to send signals to indoor units
No communication from the remote
controller/communication adapter
Is the
inter-unit wire of
remote controllers (A/B)
normal?
The
communication wiring
between the remote
controller and indoor units
is connected properly
.
Is there no
disconnection or
connector contact error on
harness out of terminal
block of indoor
unit?
Is a group control
operation?
Is power of each indoor
unit turned on?
Is power applied
to remote controller?
AB terminals:
Approx.
DC18V
Is setup of two
remote controllers
without header remote
controller?
Correct inter-unit cable of
remote controller
.
Connect the wiring properly
.
The transmission circuit in the
remote controller malfunctions.
➝
Replace the remote controller
.
Correct connector connection
and check circuit wiring.
Check power connection
status of indoor unit. (T
urn on
power again.)
Check indoor P
.C. board.
Defect
➝
Replace
Check remote controller P
.C.
board.
Defect
➝
Replace
Change one to header/other to
follower
. (Remote controller
address connector)
The error is detected when the indoor unit cannot receive the signal from the wired remote controller
.
Check the communication wiring from the remote controller
A
and B.
The check code [E03] is not indicated on the remote controller as its communication is down.
However
, the code is indicated on the compliant manager of
TCC-LINK.