background image

255

11

REPLACING COMPRESSORS

11-1.Compressor Replacement Procedure (Outline)

NO

YES

YES

NO

START

Is the outdoor unit the only one in the system?

Recover refrigerant 
from the failed unit in 
accordance with “10 
OUTDOOR UNIT 
REFRIGERANT 
RECOVERY 
METHOD”.

Manually open PMV1, 2 
and 4 of the failed unit 
(by short-circuiting the 
pins of CN30 on I/F P.C. 
board and turning off the 
power switch), and 
recover refrigerant using 
a refrigerant recovery 
device (*1).

Turn off the power switch of the failed outdoor unit.

Dismantle the faulty compressor.

Check the color of the oil in the faulty compressor.
ASTM grade: Is it 4 or above?
(Judge the condition of the oil against color samples, 
and decide whether to replace the faulty compressor 
only or all compressors.)

Replace both the faulty compressor and the normal 
compressor(s).

Measure the amount of oil in the normal compressor(s).

Adjust the amount of oil according to the oil quantity 
measurement result(s).

Install the new compressor(s) (*2).

Perform a leakage check of the failed outdoor unit.

Perform vacuum drying in the failed outdoor unit.

Refrigerant charging

END

Measure the amount of oil in the faulty compressor.

Replace the faulty compressor only.

WARNING

In situations such as indoor unit relocation and repairs, 
it is not possible to recover all the refrigerant held by the 
system in the outdoor units.
It could cause a serious accident, such as blow out or 
injury.
Be sure to perform refrigerant recovery using a 
refrigerant recovery device.

WARNING

When detaching a pipe by heating with a burner a 
welded joint, take care as any oil left in the piping may 
burn in a momentary flash of fire when the weld filler 
metal melts.

*1 The full-opening of PMV1, 2 and 4 via short-circuiting of the CN30 

pins is automatically undone after 2 minutes, causing the valves 
to fully close. To maintain fully open state, turn off the power 
switch of the outdoor unit within 2 minutes.

*2 The SMMS-i (4 series) and the SMMS (3 series) use different 

types of compressors.
Be sure to check the service part code.

This flowchart only shows the standard compressor 
replacement procedure. Since the situation can differ 
site by site, perform the task in accordance with the 
following judgment criteria: 
(1) New compressors are charged with 1900cc of oil 

per unit.

(2) The amount of oil held by an outdoor unit is as 

shown below.

(3) When a compressor is dismantled, it usually 

contains 800-1400cc oil.
The amount of oil held by an oil separator is usually 
0-1000cc for MAP0804

#

, MAP1004

#

, and MAP1204

#

 

and 0-1500cc for MAP1404

#

 and MAP1604

#

.

MAP0804

#

, 1004

#

, 1204

#

MAP1404

#

, 1604

#

Amount of oil 4300cc

6700cc

Summary of Contents for MMY-MAP0804HT7 Series

Page 1: ...pe 2 series MMK AP 2H A05 005 High wall Type 3 series MMK AP 3H SVM 09059 Other indoor units SMMS 1 series A03 009 A03 010 MMY MAP0804HT8 Z ZG E MMY MAP1004HT8 Z ZG E MMY MAP1204HT8 Z ZG E MMY MAP1404HT8 Z ZG E MMY MAP1604HT8 Z ZG E MMY MAP0804HT8 Z ZG TR MMY MAP1004HT8 Z ZG TR MMY MAP1204HT8 Z ZG TR MMY MAP1404HT8 Z ZG TR MMY MAP1604HT8 Z ZG TR MMY MAP0804HT8 Z ZG MMY MAP1004HT8 Z ZG MMY MAP1204H...

Page 2: ...ies 37 1 2 13 Floor Standing Cabinet Type 38 1 2 14 Floor Standing Concealed Type 39 1 2 15 Floor Standing Type 40 1 2 16 Fresh Air Intake Indoor Unit for S MMS 41 2 Parts Rating 43 2 1 Outdoor Unit 50Hz model MMY MAP 4HT8 E MAP 4HT8 TR MAP 4HT8 MAP 4T8 SG 43 2 2 Outdoor Unit 60Hz model MMY MAP 4HT7 44 2 3 Outdoor Inverter 50Hz model MMY MAP 4HT8 E MAP 4HT8 TR MAP 4HT8 MAP 4T8 SG 45 2 4 Outdoor In...

Page 3: ... 3 Optional Connector Specifications of Indoor P C Board 97 6 4 Test Operation of Indoor Unit 98 6 5 Method to Set Indoor Unit Function DN Code 99 6 6 Applied Control of Indoor Unit 103 6 7 Applied control for Outdoor Unit 106 6 7 1 Outdoor Fan High Static Pressure Shift 106 6 7 2 Priority Operation Mode Setting 107 6 8 Applied Control of Outdoor Unit 109 6 8 1 Power peak cut Control Standard 110 ...

Page 4: ... Close Function in Indoor Unit 158 7 7 6 Pulse Motor Valve PMV Forced Open Fully Close fully Function in Outdoor Unit 158 7 7 7 Solenoid Valve Forced Open Close Function in Outdoor Unit 159 7 7 8 Fan Operation Check in Outdoor Unit 160 7 7 9 Abnormal Outdoor Unit Discrimination Method By Fan Operating Function 161 7 7 10 Manual Adjustment Function of Outside Temperature TO Sensor 162 7 7 11 Monito...

Page 5: ...1 REPLACING COMPRESSORS 255 11 1 Compressor Replacement Procedure Outline 255 11 2 Replacement of Compressors 256 11 3 Check Procedure to Search Cause of Compressor Oil Shortage 260 12 OUTDOOR UNIT PARTS REPLACEMENT METHODS 263 13 P C BOARD EXCHANGE PROCEDURES 276 13 1 Replacement of Indoor P C Boards 276 13 2 Replacement of Outdoor P C Boards 283 13 2 1 List of service P C boards 283 13 2 2 Confi...

Page 6: ... matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such matters by an individual or i...

Page 7: ...lectric shock Work done at heights 50 cm or more Helmets for use in industry Transportation of heavy objects Shoes with additional protective toe cap Repair of outdoor unit Gloves to provide protection for electricians and from heat Indication Explanation DANGER Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when a...

Page 8: ...e aluminium fins of the unit Doing so may result in injury CAUTION BURST HAZARD Open the service valves before the operation otherwise there might be the burst CAUTION Do not climb onto the fan guard Doing so may result in injury WARNING ELECTRICAL SHOCK HAZARD Disconnect all remote electric power supplies before servicing WARNING Moving parts Do not operate unit with grille removed Stop the unit ...

Page 9: ...n Take steps to ensure that the power will not be turned on by marking out of service near the circuit breaker for instance until qualified service person arrives Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure Electric shock hazard When you access inside of the service panel to repair electric part...

Page 10: ...ollow the procedure in the ladder s instructions Also wear a helmet for use in industry as protective gear to undertake the work When working at heights put a sign in place so that no one will approach the work location before proceeding with the work Parts and other objects may fall from above possibly injuring a person below When executing address setting test run or troubleshooting through the ...

Page 11: ...d abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused When the air conditioner has been installed or relocated follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle Failure to purge the air completely may cause the air conditioner to mal...

Page 12: ...under condition that the valve closes causes an abnormal high pressure resulted in damage of the parts of the compressor and etc and moreover if there is leak of refrigerant at connecting section of pipes the air is sucked and causes further abnormal high pressure resulted in burst or injury Check after reinstallation Only a qualified installer 1 or qualified service person 1 is allowed to relocat...

Page 13: ...s instructions to install the air conditioner Be sure to use the company specified products for the separately purchased parts Use of non specified products may result in fire electric shock water leakage or other failure Have the installation performed by a qualified installer Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit Capacity overflow ...

Page 14: ... Denomination Air Conditioner Model type Outdoor unit Heat Pump Model MMY MAP0804HT8 Z ZG E MMY MAP1004HT8 Z ZG E MMY MAP1204HT8 Z ZG E MMY MAP1404HT8 Z ZG E MMY MAP1604HT8 Z ZG E MMY MAP0804HT8 Z ZG TR MMY MAP1004HT8 Z ZG TR MMY MAP1204HT8 Z ZG TR MMY MAP1404HT8 Z ZG TR MMY MAP1604HT8 Z ZG TR Cooling Only Model MMY MAP0804T8 Z ZG E MMY MAP1004T8 Z ZG E MMY MAP1204T8 Z ZG E MMY MAP1404T8 Z ZG E MM...

Page 15: ...Y MAP1604HT8ZGTR 83 84 330 MMY MAP0804HT8 MMY MAP0804HT8Z MMY MAP0804HT8ZG 77 78 242 MMY MAP1004HT8 MMY MAP1004HT8Z MMY MAP1004HT8ZG 78 79 242 MMY MAP1204HT8 MMY MAP1204HT8Z MMY MAP1204HT8ZG 82 83 242 MMY MAP1404HT8 MMY MAP1404HT8Z MMY MAP1404HT8ZG 82 83 330 MMY MAP1604HT8 MMY MAP1604HT8Z MMY MAP1604HT8ZG 83 84 330 MMY MAP0804HT7 MMY MAP0804HT7Z MMY MAP0804HT7ZG 77 78 242 MMY MAP1004HT7 MMY MAP100...

Page 16: ...MAP1204T8 MMY MAP1204T8Z MMY MAP1204T8ZG 82 241 MMY MAP1404T8 MMY MAP1404T8Z MMY MAP1404T8ZG 82 330 MMY MAP1604T8 MMY MAP1604T8Z MMY MAP1604T8ZG 83 330 MMY MAP0804T8 SG 77 241 MMY MAP1004T8 SG 78 241 MMY MAP1204T8 SG 82 241 MMY MAP1404T8 SG 82 330 MMY MAP1604T8 SG 83 330 Model Sound power level dBA Weight kg Cooling Heating ...

Page 17: ... able to bear the unit s weight into the rectangular holes for handling and tie the unit from 4 sides Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused to the outer surface of the outdoor unit There are reinforcing plates on the side surfaces so the rope cannot be passed through Front Back GOOD NO GOOD NO GOOD Plaster Rope Plaster Rectan...

Page 18: ...Model type X mm Y mm Z mm Weight kg Heat pump model Cooling only model A MAP080 500 390 645 242 241 MAP100 MAP120 B MAP140 605 350 700 330 330 MAP160 Z X Z X Y Y A B Anchor bolt position 700 Anchor bolt position 920 Anchor bolt position 755 Anchor bolt position 755 ...

Page 19: ...0 12 70 12 70 0 03 12 81 9 8 0 10 or less 0 70 15 88 15 88 0 03 16 00 9 8 0 13 or less 0 80 19 05 19 05 0 03 19 19 11 10 0 15 or less 0 80 22 22 22 22 0 03 22 36 11 10 0 16 or less 0 82 28 58 28 58 0 04 28 75 13 12 0 20 or less 1 00 34 92 34 90 0 04 35 11 14 13 0 25 or less 1 20 38 10 38 10 0 05 38 31 15 14 0 27 or less 1 26 41 28 41 28 0 05 41 50 15 14 0 28 or less 1 35 Screw size Tightening torq...

Page 20: ...es minus as the result of calculation use the air conditioner without additional refrigerant Table 1 Heat pump type Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160 Charging amount kg 11 5 Cooling only type Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160 Charging amount kg 10 5 10 5 10 5 11 5 11 5 Additional refrigerant charge amount at local site Real length of liquid pipe Additional ref...

Page 21: ...P HP Combined outdoor units HP C Corrective amount of refrigerant kg Standard type 8 8HP 1 5 10 10HP 2 5 12 12HP 3 5 14 14HP 8 5 16 16HP 10 5 18 10HP 8HP 0 0 20 10HP 10HP 3 0 22 12HP 10HP 5 0 24 12HP 12HP 7 5 26 16HP 10HP 8 5 28 16HP 12HP 9 5 30 16HP 14HP 11 5 32 16HP 16HP 12 5 34 12HP 12HP 10HP 3 0 36 12HP 12HP 12HP 4 0 38 16HP 12HP 10HP 6 0 40 16HP 12HP 12HP 7 0 42 16HP 14HP 12HP 8 0 44 16HP 16H...

Page 22: ...others do not mix in because pipes are affected by impurities such as water oxide scales oil etc Use the clean pipes Be sure to brazing with flowing nitrogen gas Never use gas other than nitrogen gas 4 For the earth protection use a vacuum pump for air purge 5 R410A refrigerant is azeotropic mixture type refrigerant Therefore use liquid type to charge the refrigerant If using gas for charging comp...

Page 23: ...ng refrigerant Unusable Use the Refrigerant charging balance Gas leak detector Checking gas leak Exclusive to R410A Vacuum pump Vacuum drying Usable if a counter flow preventive adapter is attached Vacuum pump with counterflow Vacuum drying R22 Existing article Flare tool Flare processing of pipes Usable by adjusting size Bender Bending processing of pipes R22 Existing article Refrigerant recovery...

Page 24: ...23 1 Wiring Diagrams 1 1 Outdoor Unit Models MMY MAP0804 MAP1004 and MAP1204 ...

Page 25: ...24 Models MMY MAP1404 and MAP1604 ...

Page 26: ...K CN66 WHI 1 2 1 2 CN40 BLU BLU BLU BLK BLK Outdoor unit RED WHI Power supply single phase 220 240V 50Hz 220V 60Hz CN80 GRN 2 1 CN73 RED PNL EXCT OPTION FAN DRIVE GRL CN01 WHI 1 indicates the terminal block Letter at inside indicates the terminal number 2 A dotted line and broken line indicate the wiring site 3 indicates the control P C board CN02 BLU CN001 WHI Adapter for Wireless Remote controll...

Page 27: ...ircuit CN333 WHI Flow selector unit earth screw n o i t p O e v i r d n a F Adapter for wireless remote controller Wireed remote controller CN44 BRW CN50 WHI CN66 WHI CN32 WHI CN61 YEL Control P C board for Indoor unit MCC 1402 CN60 WHI CN81 BLK CN33 WHI CN20 BLU CN70 WHI CN73 RED CN80 GRN CN41 BLU CN40 BLU CN309 YEL CN101 BLK CN102 RED CN104 YEL CN34 RED CN100 BRW TC1 FS TA TCJ TC2 CN82 BLU LM1 L...

Page 28: ...t BLU BLU RED WHI BLK BLK U 1 U 2 U 1 Power supply circuit Network adaptor P C board Symbol FM RC TR LM TA TC1 TCJ RY001 RY002 RY004 RY005 007 FS DM PMV Parts name Fan motor Running capacitor Power transformer Louver motor Indoor temp sensor Temp sensor Flap motor control relay Drain pump control relay Heater control relay Fan motor control relay Float switch Drain pump motor Pulse Motor Valve LM ...

Page 29: ... 220 240V 50Hz 220V 60Hz Indoor unit earth screw Closed end connector Flow selector unit earth screw 5 4 1 5 5 5 4 3 3 3 2 1 1 1 CN333 WHI Fuse T3 15A 250V CN82 BLU CN112 WHI CN111 WHI CN110 WHI CN71 CHK High ceiling setup LM CN33 WHI CN334 WHI FM 1 2 3 4 5 6 1 1 1 2 1 2 1 2 1 2 1 2 1 2 2 2 3 3 3 4 4 4 5 3 CN34 RED FS 1 2 3 1 3 4 5 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5 5 5 6 6 6 PMV Motor drive circuit Fu...

Page 30: ...wer supply Single phase 220 240V 50Hz 220V 60Hz Indoor unit Earth screw Outdoor unit BLU BLU BLK BLK U 1 U 2 U 1 Flow selector unit earth screw Power supply circuit CN01 WHI CN02 YEL Sub P C board MCC 1520 Symbol FM RC TR LM TA TC1 TC2 TCJ RY001 RY002 RY004 RY005 007 FS DM PMV Parts name Fan motor Running capacitor Transformer Louver motor Indoor temp sensor Te mp sensor Louver control relay Drain...

Page 31: ...30 1 2 6 2 way Air Discharge Cassette Type 2 series Models MMU AP0072WH AP0092WH AP0122WH AP0152WH AP0182WH AP0242WH AP0272WH AP0302WH AP0482WH ...

Page 32: ...V DC15V DC12V DC7V P301 BLK RED WHI WHI WHI RED Wired remote controller 1 2 B A S N R L U 2 1 2 CN1 WHI CN001 WHI Indoor unit power supply Single phase 220 240V 50Hz 220V 60Hz Indoor unit Earth screw WHI Outdoor unit BLK WHI BLK BLK BLU BLU BLK BLK TR WHI U 1 U 2 U 1 DM Power supply circuit Motor drive circuit CN01 WHI CN02 BLU CN03 RED Network adaptor Option 1 2 1 2 1 2 1 2 X Y 3 3 2 2 1 1 Networ...

Page 33: ...TA CN104 YEL FS CN030 RED 1 2 1 2 RY001 TR OC EMG RC Fuse T5 0A T10A 250V 1 2 3 1 2 3 CN309 YEL 1 2 3 1 2 3 RED WHI H M L UL 1 indicates the terminal block letter at inside indicates the terminal number 2 A dotted line and broken line indicate the wiring at site 3 indicates the control P C board 4 When attaching a drain pump exchange CN030 connector with a connector of the float switch 5 A part is...

Page 34: ... 3 1 3 1 3 1 6 8 7 2 1 1 1 2 2 1 2 1 1 2 2 1 1 2 X Y 2 3 2 1 1 3 1 1 2 3 3 1 2 3 4 5 1 2 3 4 5 6 1 2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 CN066 WHI CN067 BLK AC IN RED WHI CN044 BRW EMG Remote Controller Power supply single phase 220 240V 50Hz 220V 60Hz Indoor unit earth screw Closed end connector Closed end connector Line Filter WHI RED RED WHI RED WHI WHI CN01 WHI CN03 RED CN02 BLU CN040 BLU CN04...

Page 35: ...LU 2 1 2 1 TC1 1 2 3 4 5 CN81 BLK 1 2 3 4 5 CN50 WHI CN309 YEL 1 2 3 4 5 CN60 WHI CN32 WHI Option 1 2 Fan drive 1 2 3 4 5 6 CN61 YEL CN41 BLU CN40 BLU CN44 BRW 1 2 3 4 5 6 1 1 2 2 1 1 2 3 3 BLU BLU BLK BLK 3 1 3 1 3 1 3 1 3 1 3 1 2 1 CN66 WHI WHI RED P301 CN67 BLK Motor drive circuit CN304 GRY RY302 CN68 BLU CN68 BLU Fuse T6 3A 250V Drain pump type SPH Type Non Drain pump type SH Type BLK RED WHI ...

Page 36: ...T6 3A 250V Fuse T3 15A DC15V DC12V DC7V P301 BLK RED WHI Closed end terminal RED WHI Wired remote controller Outdoor unit 1 2 B A U 2 U 1 U 2 U 1 1 2 CN1 WHI CN001 WHI Indoor unit Earth screw WHI BLK BLK WHI BLK TR BLU WHI BLU BLK BLK DM FM Power supply circuit Motor drive circuit CN01 WHI CN02 BLU CN03 RED Network adaptor Option 1 2 1 2 1 2 1 2 X Y 3 3 2 2 1 1 Network adaptor P C board Color iden...

Page 37: ...WHI CN1 WHI BLK DC 15V DC 0V DC 12V DC 7V BLK HBS BLK CN22 F S CN82 BLU WHI 1 3 1 3 10 9 8 7 6 5 4 3 2 1 10 9 8 7 4 3 2 1 2 3 4 5 6 7 10 11 1 2 3 4 5 6 1 2 3 4 5 1 2 3 4 5 6 1 2 3 4 5 6 2 3 4 5 6 1 2 3 4 5 6 1 3 4 5 6 1 3 4 5 6 7 8 9 9 5 4 3 2 1 5 4 3 2 1 6 5 4 3 2 1 2 1 6 5 4 3 2 1 3 2 1 4 3 2 1 6 5 4 3 2 1 5 4 3 2 1 2 1 5 4 3 2 1 WHI WHI RED BRW YEL WHI BRW YEL GRY PNK GRY ORN RED BLU Infrared r...

Page 38: ...37 1 2 12 High Wall Type 3 series Models MMK AP0073H AP0093H AP0123H AP0153H AP0183H AP0243H ...

Page 39: ... TCJ 2 1 2 1 CN101 BLK CN100 BRN 1 3 CN080 GRN TC2 PNL EXCT 2 1 CN073 RED 2 2 1 3 2 4 5 1 FILTER CN070 WHI CN081 BLK 2 1 2 1 2 1 1 1 2 2 1 1 2 2 1 1 2 X Y 2 3 2 1 1 3 1 1 2 3 3 1 2 3 4 5 1 2 3 4 5 6 1 2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 2 1 TC1 2 1 2 1 CN066 WHI CN067 BLK AC IN RED WHI CN040 BLU Outdoor unit Remote Controller Power supply single ph...

Page 40: ...z 220V 60Hz Indoor unit earth screw Closed end connector CN01 WHI CN03 RED CN02 BLU CN03 RED CN041 BLU CN050 WHI CN061 YEL CN032 WHI FAN DRIVE OPTION CN060 WHI EMG TR RED RED WHI WHI U1 U2 U1 U2 A B X Y Network adapter Option Control P C board for undoor unit MCC 1403 MCC 1401 For AP0071BH AP0091BH AP0121BH 1 1 2 2 CN1 1 1 3 3 CN074 WHI CN075 WHI Power supply circuit TR 1 1 3 3 CN068 BLU FAN CN083...

Page 41: ... TCJ 2 1 2 1 CN101 BLK CN100 BRW 1 3 CN080 GRN TC2 PNL EXCT 2 1 CN073 RED 2 2 1 FILTER CN070 WHI CN081 BLK 2 1 2 1 2 1 1 1 2 2 1 1 2 2 1 1 2 2 1 1 2 X Y 2 3 2 1 1 3 1 1 2 3 3 1 2 3 4 5 1 2 3 4 5 6 1 2 1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6 2 1 4 3 5 2 1 TC1 CN066 WHI AC IN CN044 BRW CN040 BLU Outdoor unit Remote Controller Power supply single phase 220 240V 50Hz 220V 60Hz Indoor unit earth screw Clos...

Page 42: ... WHI RED GRY WHI RED GRY WHI RED GRY RED T10A 250V CN044 BRW Power supply circuit Sub P C board MCC 1520 CN02 YEL CN01 WHI TR1 Control P C Board for Indoor Unit MCC 1403 B A BLK Parts name Fan Motor Running Capacitor Transformer Intake air temp sensor Blow temp sensor Temp sensor Fan motor control relay Drain control relay Pulse Motor Valve Fuse for fan motor Fan motor control relay Drin Pump moto...

Page 43: ...20 CN02 YEL CN01 WHI TR1 Control P C Board for Indoor Unit MCC 1403 B A BLK Parts name Fan Motor Running Capacitor Transformer Intake air temp sensor Blow temp sensor Temp sensor Fan motor control relay Drain control relay Pulse Motor Valve Fuse for fan motor Fan motor control relay Drin Pump motor Float Swotch Symbol FM1 FM2 RC1 RC2 TR1 TA TF TC1 TC2 TCJ RY005 007 RY002 PMV F1 F2 43F1 43F2 DP FS ...

Page 44: ... valve coil HAM MD12TF 6 DC12V O O O O O 4 2 way valve coil VPV AC220 240V 50Hz SV2 SV3A SV3B SV3C SV3D SV3E O O O AC220 240V 50Hz SV2 SV3A SV3B SV3C SV3D SV3E SV3F SV6 O O 5 2 way valve coil FQ G593 AC220 240V 50Hz SV41 SV42 SV5 O O O AC220 240V 50Hz SV41 SV42 SV43 O O 6 High pressure SW ACB 4UB32W OFF 3 73MPa ON 2 9MPa O O O O O 7 Pressure sensor For high pressure NSK BC038F 067 0 5 4 3V 0 3 73M...

Page 45: ... DC12V O O O O O 4 2 way valve coil VPV AC208 230V 60Hz SV2 SV3A SV3B SV3C SV3D SV3E O O O AC208 230V 60Hz SV2 SV3A SV3B SV3C SV3D SV3E SV3F SV6 O O 5 2 way valve coil FQ D640 AC208 230V 60Hz SV41 SV42 SV5 O O O AC208 230V 60Hz SV41 SV42 SV43 O O 6 High pressure SW ACB 4UB32W OFF 3 73MPa ON 2 9MPa O O O O O 7 Pressure sensor For high pressure NSK BC038F 067 0 5 4 3V 0 3 73MPa O O O O O 8 Pressure ...

Page 46: ...p MCC 1596 O O O O O 10 Fuse MCC 1596 GAC1 31 5A 31 5A AC500V P C Board O O O O O 11 Comp motor drive IPM MCC 1596 MCC 1596 PS22A76 25A DC1200V P C Board O O O O O 12 P C Board IPDU for fan MCC 1610 O O O O O 13 Fuse MCC 1610 GDT250V15A 15A AC250V O O O O O 14 Fan motor drive IPM MCC 1610 FSBB20CH60C 20A DC600V O O O O O 15 Magnet switch 50Hz FC 1S AC220 240V O O O O O 16 PTC thermistor MZ32 101RM...

Page 47: ...O O 10 Fuse MCC 1596 GAC1 31 5A 31 5A AC500V P C Board O O O O O 11 Comp motor drive IPM MCC 1596 MCC 1596 PS22A76 25A DC1200V P C Board O O O O O 12 P C Board IPDU for fan MCC 1610 O O O O O 13 Fuse MCC 1610 GDT250V15A 15A AC250V O O O O O 14 Fan motor drive IPM MCC 1610 FSBB20CH60C 20A DC600V O O O O O 15 Magnet switch 60Hz FC 1S AC200 220V O O O O O 16 PTC thermistor MZ32 101RMARD01E 13A AC500V...

Page 48: ...Motor for horizontal grille MP24ZN3N Pulse motor EDM MD12TF 3 Pulse motor valve EDM B60YGTF 1 TA sensor Lead wire length 310mm Vinyl tube TC1 sensor Ø4 size lead wire length 1200mm Vinyl tube Blue TC2 sensor Ø6 size lead wire length 1000mm Vinyl tube Black TCJ sensor Ø6 size lead wire length 1000mm Vinyl tube Red Float switch FS 0218 103 Drain pump motor MDP 1401 Model MMU AP 0071MH 0091MH 0121MH ...

Page 49: ...r Ø6 size lead wire length 1200mm Vinyl tube Black TCJ sensor Ø6 size lead wire length 1200mm Vinyl tube Red Model MMU AP 0241WH 0271WH 0301WH 0481WH Fan motor AF 200 53 4F AF 200 92 4B Running condenser for fan motor AC 450V 2 5µF AC 450V 3µF AC 450V 5µF Running capacitor for fan motor AC 450V 2 5µF AC 450V 3 5µF AC 500V 5µF Drain pump motor PJD 05230TF 1 Float switch FS 0208 608 Control P C boar...

Page 50: ...ire length 1100mm Vinyl tube Black TCJ sensor Ø6 size lead wire length 1100mm Vinyl tube Red Float switch FS 0218 103 Drain pump motor ADP 1409 Model MMD AP 0071BH 0091BH 0121BH 0151BH 0181BH Fan motor ICF 280 120 2 Drain pump motor ADP 1409 Float switch FS 0218 102 Pulse motor EDM MD12TF 3 Pulse motor valve EDM B25YGTF EDM B40YGTF TA sensor Lead wire length 618mm TC1 sensor Ø4 size lead wire leng...

Page 51: ...721H 0961H Fan motor STF 200 370 4A Running condenser for fan motor AC 450V 12µF Drain pump motor ADP 1409 Float switch FS 0218 102 6 Pulse motor EDM MD12TF 3 Pulse motor valve EDM BAOYGTF 1 TA sensor Lead wire length 818mm TC1 sensor Ø4 size lead wire length 2000mm Vinyl tube Blue TC2 sensor Ø6 size lead wire length 2000mm Vinyl tube Black TCJ sensor Ø6 size lead wire length 2000mm Vinyl tube Red...

Page 52: ...0mm 10k at 25 C 6 Heat exchanger sensor TCJ sensor Ø6 800mm 10k at 25 C Model MML AP 0071H 0091H 0121H 0151H 0181H 0241H Fan motor AF 200 19 4F AF 200 45 4F AF200 70 4K Running condenser for fan motor AC450V 1 2µF AC400V 1 8µF AC450V 2µF Transformer TT13 Pulse motor EDM MD12TF 3 Pulse motor valve EDM B25YGTF EDM B40YGTF TA sensor Lead wire length 818mm Vinyl tube TC1 sensor Ø4 size lead wire lengt...

Page 53: ...ength 2000mm Vinyl tube Black TCJ sensor Ø6 size lead wire length 1200mm Vinyl tube Red Model MMD AP 0481HFE 0721HFE 0961HFE Fan motor STF200 160 4AR Running capacitor for fan motor 400V 6µF 400V 4µF Transformer TT13 TA sensor Lead wire length 1200mm Lead wire length 818mm TF sensor Lead wire length 2500mm TC1 sensor Ø4 size lead wire length 1200mm Vinyl tube Blue Ø4 size lead wire length 2000mm V...

Page 54: ...ble plug SV41 valve TD2 sensor TD1 sensor TE1 sensor Accumulator Compressor 1 Compressor 2 4 way valve To sensor TS sensor TL sensor High pressure SW 1 High pressure SW 2 Check joint Low pressure PMV Pulse Motor Valve High pressure sensor Check joint High pressure Check joint Liquid pipe Front side Rear side TK5 sensor TK4 sensor SV3A valve TK1 sensor TK2 sensor Low pressure sensor ...

Page 55: ...re SW 3 TD1 sensor TD3 sensor TD2 sensor Accumulator Compressor 1 Compressor 2 Compressor 3 To sensor TE1 sensor TE2 sensor TS sensor Low pressure sensor PMV Pulse Motor Valve Check joint Low pressure High pressure sensor 4 way valve Check joint High pressure Check joint Liquid pipe SV3E valve SV3A valve SV3B valve TL sensor TK5 sensor Fusible plug TK4 sensor TK1 sensor TK2 sensor TK3 sensor Liqui...

Page 56: ... fan Fan IPDU MCC 1610 Inverter P C Board for Compressor 1 A3 IPDU MCC 1596 Inverter P C Board for Compressor 2 A3 IPDU MCC 1596 Interface P C board Outdoor control P C board MCC 1606 Power supply terminal block Noise Filter P C board MCC 1608 Communication terminal block Relay connector for central control Magnet switch ...

Page 57: ...ard Outdoor control P C board MCC 1606 Power supply terminal block Noise Filter P C board MCC 1608 Communication terminal block Relay connector for central control Magnet switch Inverter P C board for Compressor 1 MCC 1596 Inverter P C board for Compressor 2 MCC 1596 Inverter P C board for Compressor 3 MCC 1596 ...

Page 58: ... SV3D CN315 Jumper select For inter unit cable between indoor and outdoor units For inter unit cable between outdoor units PMV2 output PMV1 output Option input output Sensor input 7 segment LED PD sensor PS sensor Dina doctor connecting terminal 4 way valve output Accumulator heater Comp case heater 3 Comp case heater 2 Comp case heater 1 SV51 52 SV2 CN511 CN508 CN510 CN513 TD3 TD2 TD1 CN504 CN503...

Page 59: ...g CN851 UART communication CN852 UART communication CN02 CN01 CN03 CN211 CN212 CN213 Power supply input L2 Power supply input L1 Power supply input L3 Compressor output U phase CN10 Compressor output V phase CN09 Reactor connecting terminal Reactor connecting terminal Compressor output W phase ...

Page 60: ...03 CN705 CN704 CN703 CN504 CN505 Power supply input CN500 CN510 CN511 CN502 CN511 CN510 Fan motor output U phase Fan motor output V phase Fan motor output W phase UART communication between interfaces UART communication between A3 IPDU Reactor connecting terminal Reactor connecting terminal ...

Page 61: ...3 Oil header Oil separator Fan SV3C Reducer TO SV SV SV SV SV SV SV SV SV SV Heat exchanger Left side Fan motor FP Heat exchanger Fusible plug Check valve Check valve Check valve Check valve Check valve Check valve SV41 SV42 High pressure switch High pressure switch Compressor 1 Inverter Compressor 2 Inverter Liquid side packed valve Gas side service valve Balance pipe packed valve Symbol Solenoid...

Page 62: ...at exchanger at right side Fan motor FP SV Symbol Solenoid valve Capillary tube Check valve Check joint Strainer Temperature sensor Distributor Right side Left side Check valve Check valve 4 way valve High pressure sensor Fusible plug Liquid tank Oil separator High pressure switch High pressure switch High pressure switch Accumulator Oil header Compressor 1 Inverter Compressor 2 Inverter Compresso...

Page 63: ...nector CN303 Red 1 Exchange function between main and sub exchangers in cooling operation 2 Preventive function for high pressure rising in heating operation Oil separator 1 Prevention for rapid decreasing of oil Decreases oil flowing to the cycle 2 Reserve function of surplus oil Temp Sensor TD1 TD2 TD3 TD1 Connector CN502 White TD2 Connector CN503 Pink TD3 Connector CN504 Blue 1 Protection of co...

Page 64: ...ant oil in heating operation Temp Sensor 1 TA Connector CN104 2P Yellow 1 Detects indoor suction temperature 2 TC1 Connector CN100 3P Brown 1 Controls PMV super heat in cooling operation 3 TC2 Connector CN101 2P Black 1 Controls PMV under cool in heating operation 4 TCJ Connector CN102 2P Red 1 Controls PMV super heat in cooling operation 2 MMU AP007YH to AP012YH only Controls PMV under cool in he...

Page 65: ...SV2 SV5 TE1 FM SV3D PMV2 TK2 SV3B TK1 SV3A HPS HPS TD1 TK4 SV3 TK5 SV41 SV42 A3 SV3C TO SV SV SV SV SV SV SV SV SV TC2 TCJ TC1 TC2 TCJ TC1 TC2 TCJ TC1 TC2 TCJ TC1 Balance pipe Liquid pipe Liquid pipe Gas pipe Gas pipe PMV PMV PMV PMV Indoor unit Pressure sensor high pressure Liquid tank Liquid tank Pressure sensor low pressure Pressure sensor high pressure Pressure sensor low pressure Accumulator ...

Page 66: ...ressure Accumulator Compressor 1 Compressor 2 Compressor 3 Liquid tank Balance pipe Liquid pipe Gas pipe Liquid pipe Gas pipe 4 Way valve Pressure sensor low pressure Pressure sensor high pressure O S Liquid tank Accumulator Compressor 1 Compressor 2 Indoor unit High pressure gas or condensate liquid refrigerant Evaporative gas refrigerant low pressure gas Normal refrigerant line Note The header u...

Page 67: ...alve Pressure sensor high pressure O S Pressure sensor low pressure Accumulator Compressor 1 Compressor 2 Compressor 3 Liquid tank Balance pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Indoor unit O S Liquid tank Accumulator Compressor 1 Compressor 2 Pressure sensor low pressure Pressure sensor high pressure 4 Way valve FM High pressure gas or condensate liquid refrigerant Evaporative gas refrige...

Page 68: ...re Set Up as Temporary Header Unit during Emergency Operation Gas side service valve Full closure Balance pipe packed valve Full opening FM 4 Way valve Pressure sensor high pressure 4 Way valve Pressure sensor high pressure O S O S Pressure sensor low pressure Pressure sensor low pressure Accumulator Accumulator Compressor 1 Compressor 2 Compressor 3 Compressor 1 Compressor 2 Compressor 3 Liquid t...

Page 69: ...er Unit during Emergency Operation FM 4 Way valve Pressure sensor high pressure O S Pressure sensor low pressure Accumulator Liquid tank Compressor 1 Compressor 2 Compressor 3 Gas side service valve Full closure Balance pipe packed valve Full opening Balance pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Indoor unit FM 4 Way valve Pressure sensor high pressure O S Pressure sensor low pressure Accu...

Page 70: ...pressure Accumulator Liquid tank Compressor 1 Compressor 2 Compressor 3 Balance pipe Liquid pipe Gas pipe Liquid pipe Gas pipe Indoor unit FM 4 Way valve Liquid line bypass Pressure sensor high pressure Pressure sensor low pressure O S Accumulator Compressor 1 Compressor 2 Liquid tank Balance pipe packed valve Full opening Gas side service valve Full opening Full closure 10 minutes after system st...

Page 71: ...anges in response to an operation selection command issued via the remote controller Ts Temperature setting Ta Room temperature 3 Room temp control 1 Adjustment range remote controller temperature setting C 2 In heating operation the temperature setting may be fine tuned via the DN code 06 Factory default Shift in heating suction temperature not applicable to remote controller thermo operation 4 A...

Page 72: ...ame Heating Figures inside applies to remote controller thermo operation Figures outside applies to body thermo operation Speed modes shown in apply to heating operation under AUTO air conditioner operation mode DN code 32 0000 Body thermo 0001 Remote controller thermo In AUTO fan speed mode the fan speed remains the same for 1 minute each time a speed change occurs However a speed change command ...

Page 73: ...reeze mode until it moves into zone I The control is terminated under the following conditions Termination conditions 1 TC1 12 C TC2 12 C and TCJ 12 C 2 Passage of 20 minutes after stoppage 2 During cooling the air conditioner is operated in the manner described below according to the temperature readings of the TC2 and TCJ sensors If zone M operation is detected for 45 minutes the air conditioner...

Page 74: ...e indoor unit 10 Defrosting control While the outdoor unit is engaged in defrosting control the indoor units perform the following control tasks 1 Open the indoor PMV to a certain degree 2 Control the indoor fan according to the operation mode Indoor units operating in heating thermo ON OFF state Let the indoor fan continue operating for a while but turn it off as the temperature of the indoor hea...

Page 75: ... COOL DRY mode under priority cooling setting bit 1 of SW11 on outdoor I F P C board ON 3 All indoor units not able to engage in any of the above operations stand by in thermo OFF state 4 The indoor fan has been turned off because the system is engaged in a heat refrigerant oil recovery operation OPERATION STANDBY displayed No display provided on wireless remote controller Heating standby Displaye...

Page 76: ...individually or collectively 3 Set louver positions 18 DC motor 1 When the fan is turned on the positions of the stator and rotor are determined The motor turns in incremental steps 2 The fan operates in accordance with commands issued by the indoor controller Note If the fan is rotating while the air conditioner is turned off due to an inflow of outside air or some other reason the indoor unit ma...

Page 77: ... thermo OFF state or upon being turned off normally or shut down due to an abnormality 2 PMV4 control applicable only to 14 and 16 HP outdoor units MMY MAP1404 and MAP1604 1 When using a small capacity split type heat exchanger mainly a sub heat exchanger to a combination of a sub heat exchanger and main heat exchanger during cooling the pulse count of the PMV pulse motor valve is controlled betwe...

Page 78: ...r unit at rest The fan is operated at mode 1 to prevent the accumulation of refrigerant inside the outdoor heat exchanger 3 Capacity control 1 The compressors of the header and follower units are controlled on the basis of capacity demand issued by indoor controllers 2 The two or three compressors featured in an outdoor unit operate on a rotational basis so that every time they come to a stop thei...

Page 79: ...enever at least one compressor is in operation Oil level detection takes place regardless of the number of compressors whether it be one two or three Rough guide for oil level judgment 1 If TK1 TK4 14 C oil level of compressor 1 is optimum 2 If TK2 TK4 14 C oil level of compressor 2 is optimum 3 If TK3 TK4 14 C oil level of compressor 3 is optimum Item Description of operation numerical data and o...

Page 80: ...naged by the header outdoor unit 1 Control commencement conditions When cooling operation has continued for at least 2 hours When cooling operation has started compressors have just been turned on though this does not always happen depending on outside air temperature conditions 2 Control details All compressors currently in operation are operated at the minimum speed with those currently not in o...

Page 81: ...he target rotational speed for defrosting control To protect the refrigerating cycle circuit the fan mode may be controlled during defrosting 3 Defrosting termination conditions Defrosting termination conditions are met when the TE1 temperature sensor measurement reaches a specified value roughly 12 C a certain period of time after the commencement of defrosting control In that event defrosting te...

Page 82: ...operation at low speeds of up to 36 rps 2 Control details When Pd pressure becomes 3 4 MPa SV2 is opened When Pd pressure becomes 2 8 MPa SV2 is closed 3 Termination conditions Shutdown thermo OFF defrosting operation or cooling operation The number of header unit compressors in operation increases to two or more At least one follower unit compressor is turned on The speed of the compressor rises ...

Page 83: ... details Compressors are shut down when Pd pressure reaches or exceeds P0 The compressor restart prevention timer 2 minutes 30 seconds is set and the control terminated When Pd P0 3 45 MPa compressor No 2 or No 3 the last one of three compressors in terms of startup order in a three compressor configuration is shut down When Pd P0 3 5 MPa compressor No 1 the first compressor in terms of startup or...

Page 84: ...r unit fan abnormality blockage of the cooling duct and IPDU P C board fault The TH temperature used in this control function is the highest registered by A3 IPDU1 A3 IPDU2 and A3 IPDU3 3 Overcurrent protection control 1 When the overcurrent protection circuit on an IPDU P C board detects an abnormal current the compressor is shut down 2 The compressor is restarted 2 minutes and 30 seconds later w...

Page 85: ...urate opening 3 When transporting relocating the set do not under any circumstances keep the actuator separated It may damage the valve by causing it to close and exposing it to pressure from sealed liquid 4 When reattaching the actuator after its removal push it in firmly until a click sound is heard Then turn the power off and back on again Schematic diagram for oil equation control Header unit ...

Page 86: ...U1 U2 Display LED Display LCD Function setting Key switch Power supply circuit Central control remote controller optional Network adaptor P C board MCC 1401 Remote controller communication circuit Remote controller communication circuit AI NET communication circuit Louver motor Drain pump Indoor fan motor Fan motor control circuit In operation Alarm Getting ready Thermostat ON COOL HEAT FAN Driver...

Page 87: ...ication circuit AI NET communication circuit 1 In case of AI NETWORK CPU H8 3687 Indoor control P C board MCC 1402 PMV Louver motor Drain pump Indoor fan motor Not applicable to concealed duct standard type Slim Duct Type Power supply circuit Fan motor control circuit CPU TMP88CH 47FG TMP88PH 47FG External output In operation Alarm Getting ready Thermostat ON COOL HEAT FAN AC synchronization signa...

Page 88: ...on circuit Transformer Indoor control P C board MCC 1403 CPU H8 3687 PMV Louver motor Drain pump Indoor fan motor Not applicable to concealed duct high static pressure type 1 way Type only Not applicable to concealed duct high static pressure type Not applicable to 1 way air discharge cassette type compact Driver Remote controller communication circuit CPU H8 3039 TA sensor TCI sensor TC2 sensor T...

Page 89: ...communication circuit TA sensor TCI sensor TC2 sensor TCJ sensor Float input Not applicable to concealed duct high static pressure type In operation Alarm Getting ready Thermostat ON COOL HEAT FAN AC synchronization signal input circuit BUS communication circuit External output Indoor outdoor communication Outdoor unit Power source 1Ø 220 240V 50Hz 1Ø 220V 60Hz Outdoor unit Outdoor unit Power sour...

Page 90: ...uit Fan motor control circuit CPU TMP88CH 47FG TMP88PH 47FG Remote controller communication circuit Driver TA sensor TCI sensor TC2 sensor TCJ sensor Float input Not applicable to concealed duct high static pressure type In operation Alarm Getting ready Thermostat ON COOL HEAT FAN AC synchronization signal input circuit BUS communication circuit External output Indoor outdoor communication Outdoor...

Page 91: ...ts can be connected 1 1 Only up to 7 units if a network adaptor is installed with 2 wireless remote controller kits connected 2 The network adaptor can only be installed in one unit Indoor outdoor communication Outdoor unit Power source 1Ø 220 240V 50Hz 1Ø 220V 60Hz Wireless remote controller kit Remote controller communication circuit Sensor section Display section PMV Louver motor Drain pump Ind...

Page 92: ... NETWORK Indoor control P C board MCC 1570 PMV Louver motor Drain pump Indoor fan motor 4 Power supply circuit Fan motor control circuit TA sensor TCI sensor TC2 sensor TCJ sensor Float input Driver Remote controller communication circuit Not applicable to concealed duct high static pressure type In operation Alarm Getting ready Thermostat ON COOL HEAT FAN AC synchronization signal input circuit B...

Page 93: ...ntroller Emergency operation SW Wireless remote controller kit Sensor P C board Power supply circuit Remote controller communication circuit Buzzer Sensor circuit Display LED Function setting SW Indoor outdoor communication Outdoor unit Power source 1Ø 220 240V 50Hz 1Ø 220V 60Hz TA sensor TCI sensor TC2 sensor TCJ sensor Float input Driver Remote controller communication circuit Not applicable to ...

Page 94: ...e connected to a sub remote controller Indoor outdoor communication Outdoor unit Power source 1Ø 220 240V 50Hz 1Ø 220V 60Hz Central control remote controller optional In case of AI NETWORK Indoor unit 1 Network adaptor optional Switch setting Power supply circuit Network adaptor P C board MCC 1401 Remote controller communication circuit AI NET communication circuit Transformer CPU H8 3687 Indoor c...

Page 95: ...oor communication CN40 blue DC fan return CN334 white HA T10 CN61 yellow DC12V Remote controller CN41 blue DC20V Remote controller communication LED D504 green High ceiling adjustment SW SW501 TC1 sensor CN100 brown DC5V Float SW CN34 red DC12V FILTER CN70 white DC5V Drain pump CN504 white DC12V Indoor outdoor cum central control communication D503 yellow Remote controller power source LED D403 re...

Page 96: ...put Optional output HA T10 CHK DISP Used for servicing Used for servicing EXCT TCJ sensor TCI sensor TC2 sensor External error input Remote controller jumper Indoor outdoor communication doubling as central control communication Indoor outdoor communication backup Drain pump output Optional power supply Power supply EEPROM High ceiling adjustment input Filter optional error input Microcomputer ope...

Page 97: ...T Louver Power supply Power supply transformer secondary side AC 11 14 20V EEPROM Indoor outdoor communication TCI sensor PMV output Used for servicing Short plug inserted in concealed duct External error input Filter optional error input Power supply transformer primary side Indoor outdoor communication backup Remote controller power source LED Remote controller jumper doubling as central control...

Page 98: ...AUTO mode ON while air conditioner in heating operation HEAT or heating under AUTO mode ON while indoor fan ON air cleaner in use or via interlock wiring Specification Remarks Generates test code L30 and automatically shuts down air conditioner only if condition persists for 1 minute Factory default setting to be humidifier evaporative drain pump OFF Used for control of optional error input displa...

Page 99: ... short circuiting DISP pin CN72 on the indoor P C board in addition to short circuit of CHK pin CN71 on the indoor P C board the minimum opening degree 30pls can be set to the indoor PMV only When open DISP pin the maximum opening degree 1500pls can be obtained again How to clear Open CHK pin While the system is operating it stops once but automatically returns to operation after several minutes T...

Page 100: ...ed one of the indoor unit Nos under group control is displayed in turn Then the fan and louver of the selected indoor unit move 3 Use the button to select the CODE No DN code of the desired function 4 Use the button to select the desired SET DATA associated with the selected function 5 Push the button The display changes from flashing to steady To change the selected indoor unit go back to step 2 ...

Page 101: ...ng only According to type 0002 1 way Air Discharge Cassette type Under Ceiling type 0003 2 way Air Discharge Cassette type 0004 4 way Air Discharge Cassette type 1E Temp difference of AUTO mode selection COOL HEAT HEAT COOL 0000 0 deg to 0010 10 deg 0003 3 deg Ts 1 5 For setup temperature reversal of COOL HEAT by Data value 2 28 Automatic restart of power failure 0000 None 0001 Restart 0000 None 2...

Page 102: ...gh static pressure 3 60 Timer setting wired remote controller 0000 Available can be performed 0001 Unavailable cannot be performed 0000 Available DN Item Description At shipment Value Type AP015 AP018 AP024 0000 Standard factory default 3 5 m or less 3 8 m or less 0001 High ceiling 1 4 0 m or less 4 0 m or less 0003 High ceiling 3 4 2 m or less 4 2 m or less Value Type AP007 AP030 AP036 AP056 0000...

Page 103: ... Concealed Duct Standard MMD AP BH 0005 Slim Duct MMD AP SPH SH 0006 Concealed Duct High Static Pressure MMD AP H 0007 Under Ceiling MMC AP H 0008 High Wall MMK AP H 0010 Floor Standing Cabinet MML AP H 0011 Floor Standing Concealed MML AP BH 0013 Floor Standing MMF AP H Compact 4 way Air Discharge Cassette MMU AP MH 0016 Fresh Air Intake indoor unit Duct type MMD AP HFE Value Capacity 0000 Invali...

Page 104: ...l operation 3 Error signal Output present while alarm e g serial communication error or operation of protective device for indoor outdoor unit being activated Wiring diagram of control system using remote control interface TCB IFCB4E2 Input IFCB4E2 No voltage ON OFF serial signal Output No voltage contact in operation and error indication Contact capacity Max AC 240V 0 5A 1 2 3 4 5 6 1 2 3 4 CN61 ...

Page 105: ...ime the fan of the selected indoor unit only turns on 3 Using the setup temp or button specify the CODE No 31 4 Using the timer time or button select the SET DATA At shipment The setup data are as follows 5 Push button OK if display goes on To change the selected indoor unit go to the procedure 2 To change the item to be set up go to the procedure 3 6 Pushing returns the status to the usual stop s...

Page 106: ...ller Status that card is taken out from the card switch box When the card switch box does not perform the above contact operation convert it using a relay with b contact 2 Operation Handle the wired remote controller switch in the following procedure Use the wired remote controller switch during stop of the system 1 Push concurrently buttons for 4 seconds or more 2 Using the setup temp or button s...

Page 107: ...ll the units to the same maximum external static pressure as the one with the lowest maximum external static pressure see table2 Table 1 Maximum External Static Pressures of Base Outdoor Units Calculate duct resistance from outdoor unit air flow Table 2 Maximum External Static Pressures for Combined Use of Base Units 1 Standard models Model MMY MAP0804 MAP1004 MAP1204 MAP1404 MAP1604 Maximum exter...

Page 108: ... 1 Unit 2 Unit 3 16 MAP1604 MAP1604 40 24 AP2424 MAP1204 MAP1204 50 26 AP2624 MAP1604 MAP1004 40 28 AP2824 MAP1604 MAP1204 40 30 AP3024 MAP1604 MAP1404 40 32 AP3224 MAP1604 MAP1604 40 34 AP3424 MAP1204 MAP1204 MAP1004 50 36 AP3624 MAP1204 MAP1204 MAP1204 50 38 AP3824 MAP1604 MAP1204 MAP1004 40 40 AP4024 MAP1604 MAP1204 MAP1204 40 42 AP4224 MAP1604 MAP1404 MAP1204 40 44 AP4424 MAP1604 MAP1604 MAP12...

Page 109: ... Use the button to select the CODE No 04 4 Use the button to select the SET DATA 0001 Priority set 0001 No priority set 0000 5 Push the button The setup is finished when the display changes from flashing to steady 6 Upon finishing the setup push the button This finalizes the setting When the button is pushed the display goes blank and the system returns to normal off state Note that the system doe...

Page 110: ...1 Power peak cut Control For one input function Header unit CN513 blue SW07 1 J16 2 Power peak cut Control Enhanced Functions Header unit CN513 blue SW07 1 2 3 Snowfall Fan Control Header unit CN509 black 4 External master ON OFF Control Header unit CN512 blue 5 Night operation sound reduction Control Header unit CN508 red 6 Operation Mode Selection Control Header unit CN510 white Operation Mode S...

Page 111: ...header outdoor unit has been removed Power peak cut control P C board SW1 SW2 L1 Interface P C board of header outdoor unit SW07 Bit 1 OFF SW07 Bit 1 ON Power peak cut control ON signal received ON OFF ON 0 forced stop 60 capacity upper limit regulated Power peak cut control OFF signal received OFF ON OFF 100 normal operation 100 normal operation PJ17 CN513 SW07 TB1 ON OFF TB2 COM ON COM OFF Bit 2...

Page 112: ... When connecting a conductive load e g relay coil to the display relay load insert a surge killer CR for an AC power supply or a diode for preventing back electromotive force for a DC power supply on the bypass circuit The optional P C board should be connected to the header outdoor unit U1 Jumper wire J16 Input SW1 SW07 Bit 1 Indicator relay Bit 1 OFF Bit 1 ON L1 Cut OFF 0 forced stop 60 capacity...

Page 113: ...T SW2 terminals simultaneously 2 Be sure to provide a contact for each terminal External signal No voltage pulse contact The optional P C board should be connected to the header outdoor unit U1 Terminal Input signal Operation COOL SW1 Snowfall fan control Turns on outdoor unit fan Normal operation Cancels control Terminal Input signal Operation COOL SW1 Turns on all indoor units HEAT SW2 Turns off...

Page 114: ... to this capacity reduction Position of noise measuring device 1 m from the front face of the set and 1 5 m above ground anechoic sound Terminal Input signal Operation COOL SW1 Night time control Normal operation Outdoor unit base unit During low noise mode dB A Capacity Relative to maximum capacity Cooling Heating Model 0804 50 approx 85 approx 80 Model 1004 50 approx 70 approx 65 Model 1204 50 a...

Page 115: ...r units operating in a mode different from the selected operation mode prohibited mode indoor units become non priority units thermostat OFF Prohibited mode indoor units J01 cut The selected operation mode is imposed on all indoor units operating in a different mode SW1 Cooling mode specified input switch SW2 Heating mode specified input switch CN510 PJ17 TB1 SW1 SW2 COM HEAT COOL Locally procured...

Page 116: ... an AC power supply or a diode for preventing back electromotive force for a DC power supply on the bypass circuit The optional P C board should be connected to the header outdoor unit U1 Electrical Rating 220 240 VAC 10 mA or more 1A or less 24 VAC 10 mA or more 1 A or less non conductive load C1 Connector cable 1 CN511 Connector on Interface side green K1 K2 Relays L1 Error indication Lamp L2 Op...

Page 117: ...ass circuit Electrical Rating 220 240 VAC 10 mA or more 1A or less 24 VAC 10 mA or more 1 A or less non conductive load C2 Connection cable 2 CN514 Interface side connector green CTR1 Elapsed operation counter 1 CTR2 Elapsed operation counter 2 CTR3 Elapsed operation counter 3 K1 K2 K3 Relay L1 L2 L3 Operation indication lamp OUTPUT1 Compressor 1 in operation output terminal OUTPUT2 Compressor 2 i...

Page 118: ...omotive force for a DC power supply on the bypass circuit Function SW16 OUTPUT1 OUTPUT2 OUTPUT3 Operation factor FA System operation rate output Bit 1 ON Bit 2 OFF off off off FA 0 on off off 0 FA 20 off on off 20 FA 35 on on off 35 FA 50 off off on 50 FA 65 on off on 65 FA 80 off on on 80 FA 95 on on on 95 FA C2 Connection cable 2 CN514 Interface side connector green MONITOR Monitoring device OUT...

Page 119: ...ain power supply is turned on Check basic items mainly the installation work Be sure to enter the check results in checklist 1 and 2 This check is done after the power has been turned on Check that the refrigerant circuit system is turned on normally Set up the addresses Start the address setup in the outdoor indoor units Note Operation does not start simply by powering on Test operation END Carry...

Page 120: ...heck items Check 1 Are the indoor and outdoor communication lines of the header unit connected to the U1 U2 terminals 2 Is the relay connector between the U1 U2 terminal and the U3 U4 terminal removed Set up at shipment from the factory 3 Is the communication line between outdoor units connected to the U5 U6 terminal 4 Is the terminal resistance SW30 bit 2 on the interface PC board of the header u...

Page 121: ...Is the terminal resistance SW30 bit 2 on the interface PC board of the header unit turned on Set up at shipment from the factory After address setup and test operation check turn on the SW30 bit 2 of the header unit for the smallest line address and turn off SW30 bit 2 of the header unit for other refrigerant lines See page 125 7 4 3 Address Setup Procedure 6 Is the end terminal of the shield wire...

Page 122: ...ystem connection terminals U3 U4 Is the power of indoor units supplied collectively Is it grounded to earth Is the resistance sufficient 10 M or higher M or higher Is the main power voltage sufficient within 380 415 V 10 V Is the diameter of connecting pipe correct Is the branch kit correct Is the water drain of the indoor unit arranged so that it flows without accumulation Is the heat insulation ...

Page 123: ...ch liquid side kg Ø6 4 0 025 kg Ø9 5 0 055 kg Ø12 7 0 105 kg Ø15 9 0 160 kg Ø19 0 0 250 kg Ø22 2 0 350 kg Additional amount of refrigerant by pipe length A kg Combined HP HP Combined outdoor units HP C Corrective amount of refrigerant kg Standard type 8 8HP 1 5 10 10HP 2 5 12 12HP 3 5 14 14HP 8 5 16 16HP 10 5 18 10HP 8HP 0 0 20 10HP 10HP 3 0 22 12HP 10HP 5 0 24 12HP 12HP 7 5 26 16HP 10HP 8 5 28 16...

Page 124: ... controller in the case of a wired remote controller Check that a frame as shown in the following figure at left is displayed on the LC display section of the remote controller If no frame is displayed as shown in the above figure at right the remote controller does not have a normal supply of power check the following items Check the power supply of the indoor unit Check the cabling between the i...

Page 125: ... interface PC board of the header unit in the system where the address is to be set up 4 Address setup start Confirm the items in 7 4 3 Address Setup Procedure and then set up the address according to the operation procedure Be careful to note that the setup operation may differ in group control and central control systems Note The address cannot be set up if switches are not operated 5 Display ch...

Page 126: ...addresses of each line separately each line s header indoor unit is set separately In that case the CODE No L03 Indoor header unit overlap is indicated as running starts Change the group address to make one unit the header unit using wired remote controller No central control go to Address setting procedure 1 Central control of 2 or more refrigerant lines go to Address setting procedure 2 Example ...

Page 127: ... switch on switch off Example Controlling 2 or more refrigerant lines as a group System wiring diagram Outdoor Indoor Indoor Indoor Indoor Outdoor Remote controller Group control SW06 SW07 SW09 SW10 SW11 SW12 SW13 SW14 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 SW13 SW14 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 O O O O O O O O O O O O O O O O O O O O O O O O O 2 3 4 1 2 3 4 SW13 SW1...

Page 128: ...hing on the display When the flashing stops and remains lit on the display the setting is complete 7 Repeat steps 4 to 6 for other refrigerant lines 8 After completing address setting of all systems turn off dip switch 2 of SW30 on the interface P C boards of all the header outdoor units connected to the same central control except the unit that has the lowest address For unifying the termination ...

Page 129: ... the installation manuals of the central control devices SW15 SW04 1 2 SW13 SW14 SW01 SW02 SW03 D600 D601 D602 D603 D604 SW05 7 segment display Header unit interface P C board SW30 Header units are connected to the same central control except the header unit with the smallest line address number ...

Page 130: ...rminator of indoor outdoor communication line and central control line ON No setting required Set to OFF after setting addresses No setting required Set to OFF after setting addresses ON Relay connector Connect after setting addresses Open Connect after setting addresses Open Connect after setting addresses Open Line system address 1 1 2 2 3 Indoor unit address 1 2 1 2 1 Group address 0 0 1 2 0 A ...

Page 131: ...oller group control SET TIME TIMER SET TEST FILTER RESET TEMP CL FAN SAVE SWING FIX VENT MODE ON OFF UNIT LOUVER DN code CODE No Set data 5 8 11 14 6 9 12 15 16 4 7 10 13 3 1 Arrange one indoor unit and one remote controller set to 1 by 1 2 Turn on the power 3 Push the buttons simultaneously for 4 seconds or more LCD begins blinking Refrigerant line address 4 Using the buttons set the DN code to 1...

Page 132: ...frigerant line After that set up the central control address For central control address setup refer to the installation manual of the central control devices Confirming the indoor unit addresses and the position of an indoor unit using the remote controller Confirming the numbers and positions of indoor units To see the indoor unit address of an indoor unit which you know the position of When the...

Page 133: ...vers of the indicated indoor unit are activated 3 Push the button to finish the procedure All the indoor units in the group stop To check all the indoor unit addresses using an arbitrary wired remote controller When communication wirings of 2 or more refrigerant lines are interconnected for central control Execute it while the units are stopped You can check indoor unit addresses and positions of ...

Page 134: ... the button to finish the procedure Changing the indoor unit address using a remote controller To change an indoor unit address using a wired remote controller The method to change the address of an individual indoor unit the indoor unit is paired with a wired remote controller one to one or an indoor unit in a group The method is available when the addresses have already been set automatically Ex...

Page 135: ...hen communication wirings of 2 or more refrigerant lines are interconnected for central control NOTE You can change the addresses of indoor units in each refrigerant line using an arbitrary wired remote controller Enter the address check change mode and change the addresses If no number appears on UNIT No no outdoor unit exists on the line Push button and select another line following step 2 Execu...

Page 136: ...es so as to make each of them unique 7 Push the button All the segments on the LCD display light up 8 Push the button to finish the procedure Resetting the address Resetting to the factory default address undecided Method 1 Clearing each address separately using a wired remote controller Set the system address indoor unit address and group address to 0099 using a wired remote controller For the se...

Page 137: ... may still connected with other refrigerant lines Check the connection of the relay connectors between U1 U2 and U3 U4 NOTE Take care to carry out the procedure above correctly otherwise addresses in other refrigerate lines may also be cleared 5 Set the addresses again after finishing the clearance SW01 SW02 SW03 SW04 Clearable addresses 2 1 2 Confirm that the 7 segment display indicates A d buS a...

Page 138: ...llows 1 Remove the relay connector between U1 U2 and U3 U4 2 If it is off turn on SW30 bit 2 on the interface PC board at outdoor header unit side Turn off the power and then execute the operation 3 Turn on the indoor outdoor power for the refrigerant line for which an address is to be set up After approximately 1 minute check that U 1 is displayed on the 7 segment display 4 Execute the following ...

Page 139: ...of the header unit with the smallest line address number in the central control turned on Setup is unnecessary for follower units 4 Is the terminal resistance SW30 bit 2 of the header units except for the line with the smallest central control line address turned off Setup is unnecessary for follower units Line address 5 Are addresses in the line address SW13 SW14 not duplicated in each refrigeran...

Page 140: ... board failure Replace the interface PC board E06 After address setup communication from all the indoor units is interrupted under the condition that a normal operation can be performed Check and correct disconnection of the indoor outdoor communication line the communication line between the header unit and the leading indoor unit Check for the influence of communication noise E16 E16 XX Alternat...

Page 141: ...ndoor outdoor communication line between outdoor units Fig 3 Correct wiring Address setup is performed under the condition of connecting multiple refrigerant lines Fig 3 Correct wiring Indoorremote controller status Headerunit 7 segment display Cause Countermeasures No response None The communication line is not connected between indoor and outdoor the unit that does not respond to the indoor remo...

Page 142: ...ication of wiring set up the addresses again and check the number of connected indoor units The number of outdoor units connected to a group is too few in group operation from an indoor remote controller The indoor remote controller is not connected with wire Miswiring of the indoor remote controller Using the main indoor remote controller connected to a group start a test operation specify the un...

Page 143: ...2 U1 U2 U1 U2 U1 U2 Header unit Header unit U1 U2 Header unit U1 U2 U1 U2 U5 U6 U1 U2 U5 U6 Follower unit U1 U2 U1 U2 U1 U2 U1 U2 U1 U2 U1 U2 U1 U2 U5 U6 U1 U2 U1U2 U1 U2 Line 1 U1 U2 Header unit Follower unit Header unit Follower unit Header unit Follower unit Line 2 U1 U2 U1 U2 U1 U2 U3 U4 U1 U2 U1 U2 U1 U2 U3 U4 U1 U2 U1 U2 U1 U2 U5 U6 U5 U6 U3 U4 U1 U2 or or U3 U4 U1 U2 Header unit Follower un...

Page 144: ...urn Is air discharged from the discharge port of the indoor unit Is the sound normal When a check code has been displayed on the remote controller remove the cause of the error referring to Check code and check position displayed on remote controller and outdoor unit Check the indoor fan fan motor and fan circuit Check positions around the fan Check code appears Check code appears ...

Page 145: ...on The same display as in procedure 1 appears in the display section 5 Push the Test button to clear the test operating mode TEST disappears from the display section and the status returns to the normal stopped status 1 5 2 4 3 Procedure Operation content 1 Remove the nameplate of the receiver section by inserting a screwdriver or similar tool into the notch at the bottom of the plate and set the ...

Page 146: ...rn off the air conditioner s power Change Bit 1 of switch S003 on the sensor PC board from on to off Attach the adjustment corner cap with the sensors to the ceiling panel 1 ON 2 3 4 Sensor cover S003 Bit 1 OFF ON Adjustment corner cap Sensor PC board Procedure Operation content 1 Turn on the air conditioner s power 2 Push the button and change the operating mode to COOL or HEAT with the Mode butt...

Page 147: ...st operation using Start Stop Function of the Indoor Unit from Outdoor Unit in the Service Support Function section Check power voltage of the main power supply Check the cable size of the power supply Check the temperature load of the indoor outdoor units Check the pipe length and refrigerant amount Check the operating Hz of the compressor Check the operation of the outdoor fans Check for abnorma...

Page 148: ...ured with a clamp meter at the compressor lead line is two times the rotation count rps of the compressor Each compressor may have a different frequency as a measure against resonance The temperature of the indoor heat exchanger TC indicates TCJ sensor temperature when cooling and TC2 sensor temperature when heating respectively 2 Criteria for operating pressure Criteria after 15 minutes or more h...

Page 149: ...surely matches with the expected system capacity Check No of outdoor units Set the rotary switches SW01 SW02 SW03 on the interface P C board of the header unit to 1 3 3 Then No of outdoor units connected to the system is displayed on 7 segment display A Check that this display surely matches with the expected No of outdoor units Check No of indoor units No of units with cooling thermo ON Set the r...

Page 150: ...sults 2 Press the push switch SW05 on the interface P C board of the header unit for 2 seconds or more The indoor address in which error is being detected is displayed on 7 segment display B If there are multiple indoor address in which error is being detected they are successively exchanged and displayed When SW05 is turned on again the display returns to display of No of units After check return...

Page 151: ...2 SW03 to 1 Section A C H Section B 11 00 is displayed on Section B for 5 seconds Batch stop Stops all the connected indoor units collectively Setup Set SW01 SW02 SW03 to 2 7 1 and press SW05 for 2 seconds or more Release Return SW01 SW02 SW03 to 1 Section A C H Section B 00 00 is displayed on Section B for 5 seconds 4 Individual start Starts the specified indoor unit Notes The contents follow to ...

Page 152: ... power at the indoor side before power ON of outdoor unit Set SW01 SW02 SW03 on the interface P C board of the header unit to 2 5 1 C is displayed on 7 segment display A Test run is displayed on the remote controller of the indoor unit to be operated Check that C is displayed on 7 segment display B on the interface P C board of the header unit Press SW04 on the same board for 2 seconds or more Ret...

Page 153: ... same board for 2 seconds or more Test run is displayed on the remote controller of the indoor unit to be operated Check that H is displayed on 7 segment display B on the interface P C board of the header unit Set SW01 SW02 SW03 on the interface P C board of the header unit to 2 6 1 H is displayed on 7 segment display A Be sure to turn on power at the indoor side before power ON of outdoor unit Re...

Page 154: ...this case operation ready or operation mode controlled is displayed on the remote controller If the discharge temperature does not change though COOL or HEAT has been set up from the remote controller misconnection is considered Press SW04 on the same board for 2 seconds or more The indoor unit to be started operates Press the push switch SW05 on the interface P C board of the header unit for 2 se...

Page 155: ...sh switch SW04 on the same board for 2 seconds or more If pressed continuously for 10 seconds or more the operation changes to the individual test operation Match the rotary switches on the interface P C board of the header unit to the following table If an error is already displayed with SW01 SW02 SW03 being 1 1 1 return the status to normal one according to troubleshooting and then execute a tes...

Page 156: ...g buttons simultaneously for 4 seconds or more 2 Using buttons set CODE No to FF 3 The display in Section A in the following figure is counted with interval of 5 seconds as 0005 0004 0003 0002 0001 0000 When the count arrives 0000 the error is cleared However counting from 0005 is repeated on the display 4 When button is pushed the status returns to the normal status Error clearing in indoor unit ...

Page 157: ...ection is performed again Method 1 Be sure to reset power of both the outdoor and the indoor units 2 Turn on the power of the indoor unit prior to the power of the outdoor unit If the power is turned on in reverse order a check code E19 No of header unit error is output NOTE After power reset it requires usually 3 minutes to power on due to the initial communication of the system In some cases it ...

Page 158: ...o turn on the power of the indoor unit prior to the power of the outdoor unit Set the display select switches on the interface P C board of the header unit as follows Set SW01 SW02 SW03 to 2 4 1 Press the push switch SW04 on the same board for 2 seconds or more Checking display of the connected remote controller flashes Press the push switch SW05 on the interface P C board of the header unit for 2...

Page 159: ...ing automatically returns to the normal opening 7 7 6 Pulse Motor Valve PMV Forced Open Fully Close fully Function in Outdoor Unit This function is provided to forcedly open or close fully P M V PMV1 PMV2 PMV4 used in the outdoor unit for 2 minutes PMV1 PMV2 Open fully On the interface board of the outdoor unit set the dip switch SW12 bit1 to OFF SW12 bit2 to OFF and short circuit CN30 PMV1 PMV2 C...

Page 160: ...id valve output is exchanged when SW02 has been kept with the same number for 5 seconds or more NOTE 2 The mark O in the table indicates that the corresponding solenoid valve is forcedly turned on NOTE 3 The mark in the table indicates that ON OFF of the solenoid valve is controlled based upon the specifications of the air conditioner NOTE 4 The mark in the table indicates that the corresponding s...

Page 161: ...de operation 4 After that by changing the setup number of the switches SW02 and SW03 7 segment display B and the fan mode are changed Mode output pattern of the fan is as follows Clear This function is cleared by one of the following operations 1 When SW01 setting number was changed to other number 2 Press switch SW05 was pressed for 2 seconds or more SW02 SW03 7 segment display B Fan mode 1 4 63 ...

Page 162: ...nds or more 3 E 1 is displayed on 7 segment display A 4 The fan of the outdoor unit in which error occurred starts operation within approx 10 seconds after E 1 was displayed In case to operate the fans in all the normal outdoor units 1 Check that the switches SW01 SW02 SW03 on the interface P C board in the header unit are set to 1 1 1 2 Press the push switches SW04 and SW05 at the same time for 2...

Page 163: ...SW04 on the interface P C board for 1 second or more The mode changes to the TO sensor value fix manual mode 3 As shown in the following table TO sensor value can be fixed by setting the rotary switch SW02 on the interface P C board Clear Return SW01 SW02 SW03 on the interface P C board in the outdoor unit to 1 1 1 NOTE If operated with TO sensor fixed by this function the system control operation...

Page 164: ...ction 7 C H Indoor collective start stop ON OFF function 11 r d Outdoor refrigerant recovery operation function Pump down function 16 E r Error clear function 2 1 16 3 H r Solenoid valve forced open close function 2 4 7 F d Fan forced operation function 2 15 t o Outside temperature sensor manual adjustment function 16 1 16 1 0 1 1 6 Indoor No 1 to 16 unit Indoor individual start stop ON OFF functi...

Page 165: ...usly for 4 seconds or more to call up the service monitor mode The service monitor goes on and temperature of the CODE No 00 is firstly displayed 2 Push the temperature setup buttons to select the CODE No to be monitored For displayed codes refer to the table next page 3 Push button to determine the item to be monitored Then monitor the sensor temperature or operation status of indoor unit and the...

Page 166: ...mpressor 1 discharge temperature Td1 1 C 0024 24 C 13 23 33 43 Compressor 2 discharge temperature Td2 1 C 14 24 34 Compressor 3 discharge temperature Td3 1 C 15 25 35 45 Suction temperature TS 1 C 16 26 36 46 Outdoor coil temperature 1 TE1 1 C 17 27 37 Outdoor coil temperature 2 TE2 1 C 18 28 38 48 Temperature at liquid side TL 1 C 19 29 39 49 Outside ambient temperature TO 1 C 1A 2A 3A 4A PMV1 2 ...

Page 167: ...it just be the 3 minute delay period 3 minutes after compressor shutdown Could it just be the air conditioner having gone thermo OFF Could it just be the air conditioner operating in fan mode or put on the timer Could it just be the system going through initial communication 2 An indoor fan would not start Could it just be cold air discharge prevention control which is part of heating 3 An outdoor...

Page 168: ... between main controller and motor microcontroller is faulty E18 97 99 Error in periodic communication between indoor header and follower unit Periodic communication between indoor header and follower units cannot be maintained F01 OF ALT Indoor heat exchanger temperature sensor TCJ error Heat exchanger temperature sensor TCJ has been open short circuited F02 0d ALT Indoor heat exchanger temperatu...

Page 169: ...s have been set as master remote controller in two remote controller control alarm and shutdown for header unit and continued operation for follower unit Check code Display of receiving unit Typical fault site Description of error TCC LINK central control AI NETcentral control display with use of network adaptor Outdoor 7 segment display Indicator light block Sub code Flash C05 98 No indication wh...

Page 170: ...ant line E20 Connection to other refrigerant line found during automatic address setting Indoor unit from other refrigerant line is detected while indoor automatic address setting is in progress E23 E23 Outdoor outdoor communication transmission error Signal cannot be transmitted to other outdoor units E25 E25 Duplicated follower outdoor address There is duplication in outdoor addresses set manual...

Page 171: ...ge temperature sensor TD2 has been detected H16 01 TK1 oil circuit error 02 TK2 oil circuit error 03 TK3 oil circuit error 04 TK4 oil circuit error 05 TK5 oil circuit error H16 Oil level detection circuit error No temperature change is detected by temperature sensor for oil level detection TK1 5 despite compressor having been started H25 H25 Outdoor discharge temperature sensor TD3 wiring error Wi...

Page 172: ...it P13 P13 ALT Outdoor liquid backflow detection error State of refrigerant cycle circuit indicates liquid backflow operation P15 01 TS condition 02 TD condition P15 ALT Gas leak detection Outdoor suction temperature sensor TS1 detects sustained and repeated high temperatures that exceed standard value P17 P17 ALT Outdoor discharge TD2 temperature error Outdoor discharge temperature sensor TD2 det...

Page 173: ...ted H03 01 Compressor 1 02 Compressor 2 03 Compressor 3 H03 Current detection circuit error Abnormal current is detected while inverter compressor is turned off P04 01 Compressor 1 02 Compressor 2 03 Compressor 3 P04 ALT Activation of high pressure SW High pressure SW is activated P07 01 Compressor 1 02 Compressor 2 03 Compressor 3 P07 ALT Heat sink overheating error Temperature sensor built into ...

Page 174: ... mode by pressing the buttons simultaneously and holding for at least 4 seconds The letters SERVICE CHECK light up and the check code 01 is displayed indicating the error history This is accompanied by the indoor unit No to which the error history is related and a check code 2 To check other error history items press the button to select another check code Check code 01 latest Check code 04 oldest...

Page 175: ...ttons simultaneously and hold for at least 4 seconds 2 The letters SERVICE CHECK light up and the check code 01 is displayed 3 When a group No is selected blinking if there is an error history the UNIT No and the latest error history information are displayed alternately During this procedure the temperature setting feature is unavailable 4 To check other error history items push the button to sel...

Page 176: ...erloading E19 Error in number of outdoor header units E20 Detection of refrigerant piping communication error during automatic address setting E23 Faulty transmission in outdoor outdoor communication E25 Duplicated follower outdoor address E26 Faulty reception in outdoor outdoor communication dropping out of outdoor unit E28 Outdoor follower unit error E31 IPDU communication error P01 Indoor AC fa...

Page 177: ...discharge temperature sensor TD1 H06 Abnormal drop in low pressure sensor Ps reading Protective shutdown of outdoor unit H07 Abnormal drop in oil level H08 Error in temperature sensor for oil level detection circuit TK1 TK2 TK3 TK4 or TK5 H15 Wiring installation error or detachment of outdoor discharge temperature sensor TD2 H16 Oil level detection circuit error Error in outdoor unit TK1 TK2 TK3 T...

Page 178: ...est run in progress Setting incompatibility automatic cooling heating setting for model incapable of it and heating setting for cooling only model Light block Check code Cause of fault Operation Synchronized blinking Timer Ready Operation Timer Synchronized blinking Ready Alternate blinking Operation Timer Ready ...

Page 179: ...controller communication error detected at indoor end Stop of corresponding unit There is no communication from remote controller including wireless or network adaptor Check remote controller and network adaptor wiring E04 04 Indoor unit Indoor outdoor communication circuit error detected at indoor end Stop of corresponding unit Indoor unit is not receiving signal from outdoor unit Check order in ...

Page 180: ...ll stop Indoor automatic address setting is started while automatic address setting for equipment in other refrigerant line is in progress Outdoor automatic address setting is started while automatic address setting for indoor units is in progress Perform automatic address setting again after disconnecting communication cable to that refrigerant line E15 E15 42 I F Indoor unit not found during aut...

Page 181: ...gnal cannot be transmitted to other outdoor units for at least 30 seconds continuously Check power supply to outdoor units Is power turned on Check connection of tie cables between outdoor units for bad contact or broken wire Check communication connectors on outdoor P C boards Check for defect in outdoor P C board I F Check termination resistance setting for communication between outdoor units E2...

Page 182: ...C1 sensor error Stop of corresponding unit Sensor resistance is infinity or zero open short circuit Check connection of TC1 sensor connector and wiring Check resistance characteristics of TC1 sensor Check for defect in indoor P C board F04 F04 19 I F TD1 sensor error All stop Sensor resistance is infinity or zero open short circuit Check connection of TD1 sensor connector Check resistance characte...

Page 183: ...perature sensor wiring error TE1 TL All stop During compressor operation in HEAT mode TE1 continuously provides temperature reading higher than indicated by TL by at least specified margin for 3 minutes or more Check installation of TE1 and TL sensors Check resistance characteristics of TE1 and TL sensors Check for outdoor P C board I F error F16 F16 43 I F Outdoor pressure sensor wiring error Pd ...

Page 184: ...upply voltage AC200V 10 Check compressor system wiring particularly for open phase Check connection of connectors terminals on A3 IPDU P C board Check conductivity of case heater Check for refrigerant entrapment inside compressor Check for defect in outdoor P C board A3 IPDU Check outdoor MG CTT H03 H03 01 Compressor 1 side 02 Compressor 2 side 03 Compressor 3 side 17 IPDU Current detection circui...

Page 185: ...ero open short circuit Check connection of TK1 sensor connector Check resistance characteristics of TK1 sensor Check for defect in outdoor P C board I F All stop Sensor resistance is infinity or zero open short circuit Check connection of TK2 sensor connector Check resistance characteristics of TK2 sensor Check for defect in outdoor P C board I F All stop Sensor resistance is infinity or zero open...

Page 186: ...ng been started Check for disconnection of TK3 sensor Check resistance characteristics of TK3 sensor Check for connection error involving TK1 TK2 TK3 TK4 and TK5 sensors Check for faulty operation in SV3E or SV3F valve Check for clogging in oil equalizing circuit capillary and faulty operation in check valve Check for refrigerant entrapment inside compressor No temperature change is detected by TK...

Page 187: ... L07 99 Indoor unit Connection of group control cable to stand alone indoor unit Stop of corresponding unit There is at least one stand alone indoor unit to which group control cable is connected Check indoor addresses L08 L08 99 Indoor unit Indoor group addresses not set Stop of corresponding unit Address setting has not been performed for indoor units Check indoor addresses Note This code is dis...

Page 188: ...1 Check for defect in external device 2 Check for defect in indoor P C board When external device is not connected to CN80 connector 1 Check for defect in indoor P C board L31 I F Extended IC error Continued operation There is part failure in P C board I F Check outdoor P C board I F P01 11 Indoor unit Indoor fan motor error Stop of corresponding unit Check the lock of fan motor AC fan Check wirin...

Page 189: ...ction of open phase phase sequence All stop Open phase is detected when power is turned on Inverter DC voltage is too high overvoltage or too low undervoltage Check for defect in outdoor P C board I F 01 Compressor 1 side 02 Compressor 2 side 03 Compressor 3 side Inverter DC voltage Vdc error compressor MG CTT error P07 P07 01 Compressor 1 side 02 Compressor 2 side 03 Compressor 3 side 1C IPDU I F...

Page 190: ...tdoor service valves gas side liquid side to confirm full opening Check PMVs PMV1 2 for clogging Check resistance characteristics of TS1 sensor Check for defect in 4 way valve Check SV4 circuit for leakage 02 TD condition AE I F Gas leak detection TD condition All stop Protective shutdown due to sustained discharge temperature TD1 TD2 or TD3 at or above 108 C for at least 10 minutes is repeated fo...

Page 191: ...20 P20 22 I F Activation of high pressure protection All stop Pd sensor detects pressure equal to or greater than 3 6MPa Check for defect in Pd pressure sensor Check service valves gas side liquid side to confirm full opening Check for defect in outdoor fan Check for defect in outdoor fan motor Check outdoor PMVs PMV1 2 4 for clogging Check indoor outdoor heat exchangers for clogging Check for sho...

Page 192: ...ck fan motor Check connection of fan motor connector Check for defect in fan IPDU P C board All stop Sub code C Higher temperature than the specified value is detected during operation of the fan Check fan motor Check for defect in fan IPDU P C board All stop Sub code D The resistance value of the sensor is infinite or zero open or short circuit Check for defect in fan IPDU P C board All stop Sub ...

Page 193: ...trol device Check for defect in central control communication line Check termination resistance setting Check power supply for devices at other end of central control communication line Check defect in P C boards of devices at other end of central control communication line C12 General purpose device I F Blanket alarm for general purpose device control interface Continued operation Error signal is...

Page 194: ...ooked If there is any loose connector tighten it with a pair of pliers etc before connecting the lead How to Check Resistance of Compressor Winding 1 Turn off the power supply 2 Remove compressor leads from the compressors 3 With each compressor check the phase to phase winding resistances and winding to outdoor cabinet resistance using a multimeter Earth fault It is normal if the winding to outdo...

Page 195: ...tween the remote controller and indoor units is connected properly Is there no disconnection or connector contact error on harness out of terminal block of indoor unit Is a group control operation Is power of each indoor unit turned on Is power applied to remote controller AB terminals Approx DC18V Is setup of two remote controllers without header remote controller Correct inter unit cable of remo...

Page 196: ... unit wire normal Is connector connection from U1 U2 terminals of indoor outdoor inter unit wire normal Is the end terminal resistance setup of outdoor unit normal Is power applied to fuse F03 on indoor P C board Is address setup correct Is there no noise etc Is connection of CN40 connector on indoor P C board normal Is connection of CN01 connector on outdoor I F P C board normal Is power of indoo...

Page 197: ... outdoor unit correct Is inter unit wire U1 U2 between indoor and outdoor short circuited Is connection of inter unit wire between indoor and outdoor correct Is there no error on power wire to outdoor unit Is there noise source Is F400 fuse on I F P C board opened Correct setup of end terminal resistance Correct wire connection Correct communication line Set up indoor address again Correct communi...

Page 198: ...here no noise source Set up address again after resetting power supply Is there any trouble on power line Are U1 U2 U3 and U4 connectors connected Set up one controller as the header and the other follower Remote controller address connector Correct communication line Correct connection of connector Correct connection of connector Correct power wire Set up address again after resetting power suppl...

Page 199: ... Are powers of all indoor units turned on Check indoor address Is No of connected indoor units correct Is setup of indoor units HP correct Is total capacity of connected indoor units within 135 For a service P C board check outdoor HP setup Set up jumper 9 10 11 and 12 Indoor capacity over has been detected during the backup operation Perform setup of no detection for capacity over 1 Correct remot...

Page 200: ... not communication lines U1 U2 between indoor and outdoor connected to multiple outdoor units Is communication line between indoor and outdoor connected to one unit per 1 system Is connection of CN03 connector on outdoor I F P C board normal Is not main power of outdoor unit turned off Did power failure occur Is there no noise source etc Is the end terminal resistance between outdoor units turned ...

Page 201: ...F P C board Measurement with tester DC 0 to 5V 5 pins GND Is there voltage deflection between 3 and 5 pin of CN600 on I F P C board Measurement with tester DC0 to 5V 5 pins GND Is main power of follower unit turned on Is communication line between outdoor units connected normally Is communication connector CN03 between follower outdoor units connected Clear the error and then start operation 1 Cor...

Page 202: ...ensor Check indoor P C board Defect Replace Check indoor main P C board Defect Replace Check indoor P C board Defect Replace See Indoor unit temperature sensor characteristics on 8 9 Sensor Characteristics See Indoor unit temperature sensor characteristics on 8 9 Sensor Characteristics See Indoor unit temperature sensor characteristics on 8 9 Sensor Characteristics This error code means detection ...

Page 203: ...ion of connectors Check outdoor I F P C board Defect Replace TE1 sensor Outdoor heat exchanger temp sensor TL sensor Temp sensor between liquid tanks of outdoor PMV1 2 See Outdoor unit temperature sensor characteristics on 8 9 Sensor Characteristics This error code means detection of Open Short of TL sensor Check disconnection of circuit for connection of connector TL sensor CN523 White and charac...

Page 204: ... Replace Sensor error Replace Check compressor Replace SV4 valve Check 4 way valve Check compressor Check outdoor I F P C board Defect Replace 1 Pressure Check joint by pressure gauge 2 Pressure display on 7 segment display 3 Output voltage of I F P C board If 1 and 2 3 are different an error of pressure sensor itself is considered If 2 and 3 are different check interface P C board 1 Pressure Chec...

Page 205: ... other compressor starts Is winding resistance between phases of corresponding compressor normal Note 1 Is not it an abnormal overload Is connection of wiring or connection of connector on A3 IPDU P C board normal Check power voltage and line Correct power line Check external noise etc Check I F P C board Correct power line Correct connector connection or wiring Compressor error Motor burning etc ...

Page 206: ...es voltage drop occur when other compressor starts Is wiring or connector connection on A3 IPDU P C board normal Is MG CTT normal 2 Is there no refrigerant stagnation in compressor shell Is compressor normal 3 Is case heater output normal Correct power line Correct connector connection or wiring Check IPDU P C board Correct connector connection or wiring Exchange MG CTT No Yes Abnormal overload Co...

Page 207: ...Open service valves fully Exchange low pressure sensor Correct SV2 and SV4 circuits Correct wiring Repair faulty parts Check indoor P C board Failure Replace Refrigerant shortage or clogging or pipe deformed Repair faulty parts Repair faulty parts Refrigerant shortage clogging pipe deformed Replace PMV body Check outdoor I F P C board Failure Replace In cooling season go to A In heating season go ...

Page 208: ...the power supply take off connector of SV3A valve and then start a test operation after power ON Check the temperature change at secondary side of SV3A valve during operation 1 in the figure If temperature is raised leakage occurs in the SV3A valve Replace SV3A valve b Leakage check for SV3C valve Turn off the power supply take off connector of SV3C valve and then start a test operation after powe...

Page 209: ... 2 seconds or more Set up SW02 6 and turn on SV3A valve 7 segment display Hr 3 A If temperature is low at secondary side of the valve or it does not change clogging of valve or check valve is considered 1 in the figure b Leakage check for SV3C valve While outdoor unit is operating set up SW01 02 03 2 1 3 7 segment display Hr and push SW04 for 2 seconds or more Set up SW02 8 and turn on SV3C valve ...

Page 210: ...are normal replace the outdoor I F P C board 1 Coming off of TK1 sensor miswiring characteristics error of resistance value 2 Oil equalization circuit error Check valve capillary clogging strainer clogging 3 Refrigerant stagnation in the compressor shell Is not TK1 sensor detached Is there no miswiring or misinstallation on TK1 TK2 TK3 TK4 TK5 sensors Are characteristics of TK1 sensor resistance v...

Page 211: ...play TK2 sensor temperature on 7 segment display with SW01 02 03 1 13 2 Check TK2 sensor temp approx 10 minutes after compressor 1 has operated If low temperature continues approximately outside temp or temperature has little change a clogging of strainer of oil equalization circuit clogging of capillary tube or malfunction of check valve is considered Compressor 2 Note 1 Refer to the article of t...

Page 212: ...nstallation of sensor Sensor error replace Replace clogging part capillary Replace SV3E valve Check I F P C board Sensor error Replace clogging part Replace SV3E valve Check I F P C board Correct miswiring misinstallation TK1 CN531 black TK2 CN532 green TK3 CN533 pink TK4 CN534 yellow TK5 CN535 red Correct miswiring misinstallation TK1 CN531 black TK2 CN532 green TK3 CN533 pink TK4 CN534 yellow TK...

Page 213: ...sensor resistance value normal Check the clogging of SV3E valve Note 1 Correct miswiring misinstallation TK1 CN531 black TK2 CN532 green TK3 CN533 pink TK4 CN534 yellow TK5 CN535 red Note 1 Refer to the article of the check code H07 H25 B2 AI NET Yes Yes No No Check code Cause Check code name Outdoor discharge temperature sensor TD3 misconnection 1 Coming off of TD3 sensor 2 Misinstallation of TD1...

Page 214: ...use Check code name 1 Check whether the connection on remote controllers group and or individual has been changed since the group configuration and address checking on the remote controllers finished 2 If the group configuration and address are normal when power has been turned on the mode automatically shifts to address setup mode For setting up addresses again refer to Address setup Duplicated i...

Page 215: ...2 Connection error of communication line between outdoor units 3 Outdoor I F P C board error L08 99 AI NET Yes No No Yes L09 46 AI NET L10 88 AI NET Check code Cause Check code name Check code Cause Check code name Check code Cause Check code name I F P C board A ssy service for the outdoor unit is common to this series A setup for model selection different from that for P C board with trouble is ...

Page 216: ...Yes No Sub code 01 02 03 04 05 06 07 08 09 1 2 A3 IPDU 3 0A 0B 0C 0D 0E 0F 1 2 A3 IPDU O O O O O O O O 3 O O O O O O O O O O O O O O O O O O O O O O O O Check code Cause Check code name Is jumper setup of outdoor I F P C board correct Check jumpers 8 9 10 11 and 12 Is communication connector between IPDU and I F P C board connected Is there no disconnection of communication line between IPDU and I...

Page 217: ...place B Cooling operation Cooling To B Heating To C Reset power supply and start a test operation corresponded to the season Is outdoor PMV normal 1 Connector connection 2 Cabling 3 Coil 4 Valve body 5 Outdoor I F P C board Yes No Yes Yes No Yes No No No Yes Yes No P03 1E AI NET Check code Cause Check code name Discharge temp TD1 error Are service valve of gas and liquid sides fully opened Open se...

Page 218: ...compressor or connector connection Check fan and fan motor Tighten screws Clear clogging Check A3 IPDU P C board Yes Yes Yes No No Yes No Yes No No No No No Yes No Yes Yes Yes Yes Yes Yes No No C A Is SV2 circuit normal Is SV4 circuit normal Does heating indoor fan normally operate Are connector connection condenser fan motor and fan normal Is connector connection and coil normal Is there clogging...

Page 219: ...35 to 50Ω 2 way Cassette type AP007 to AP015 Approx 70 to 100Ω AP018 to AP030 Approx 30 to 70Ω AP036 to AP056 Approx 20 to 50Ω 1 way Cassette type Approx 30 to 70Ω Ceiling type AP015 to AP027 Approx 30 to 70Ω AP036 to AP056 Approx 20 to 50Ω Wall and concealed duct types Approx 15 to 35Ω Is not grounded between cabinet and 1 3 5 Should be 10MΩ or more 2 Check resistance value of fan motor position ...

Page 220: ... No Yes Yes No Yes No Yes Yes P13 47 AI NET Check code Cause Check code name Outdoor liquid back detection error 1 PMV1 PMV2 error 2 Pd sensor Ps sensor error 3 Clogging of SV2 circuit 4 Clogging of SV3B circuit and or balance pipe 5 Leakage at a check valve on a main discharge pipe 6 Outdoor I F P C board error Are connections of outdoor PMV1 PMV2 PMV4 connectors correct Are operations of outdoor...

Page 221: ... coils installed correctly 2 Is SV42 circuit sealed correctly no leakage Yes Yes No No Yes No Yes No No Yes P15 AE AI NET Check code Cause Check code name Gas leak detection TD condition Sub code 02 1 Outdoor unit service valve closed 2 Outdoor PMV error 3 TD sensor error 4 SV4 circuit error 5 Refrigerant shortage clogging refrigerant circuit Are service valves of gas and liquid sides fully opened...

Page 222: ...1 sensor Normal if TS is 50 C or less in the seasons except summer Outside temp 20 C or lower Yes No Yes Yes No Yes No No No Yes Yes No P18 E2 AI NET Check code Cause Check code name Discharge temp TD3 error 1 Outdoor unit service valve closed 2 Outdoor PMV error 3 TD sensor error 4 Refrigerant shortage clogging of refrigerant circuit 5 4 way valve error 6 SV4 circuit leakage misinstallation Are s...

Page 223: ...faulty parts Repair check valve Replace Eliminate the interference Replace PMV body Repair SV5 circuit Check and correct wiring Replace TC2 or TCJ sensor Refrigerant overcharge clogging pipe breakage abnormal overload Check indoor P C board Faulty Replace Coil error choke disconnection of cables etc Check it using the miswiring check function of the outdoor unit Repair faulty parts Repair faulty p...

Page 224: ...or Ignore the indication 0 F on digit Is wire connector connection on fan IPDU P C board normal Is power voltage of outdoor unit normal Is wire connector connection on INV P C board normal Is there no fusing of AC30A fuse Is compressor normal Is smoothing condenser normal 1500µF 400V Is not outdoor fan motor locked Is the resistance of the motor s winding wire normal Is sub code of outdoor I F P C...

Page 225: ...02 Compressor 2 03 Compressor 3 Are connector connection and wiring normal Is the unit grounded Is not winding shorted Is winding resistance 0 1 to 0 4Ω Is not winding opened Check and correct circuit and cables such as wiring to compressor etc Compressor error Replace Compressor error Replace Compressor error Replace Check A3 IPDU P C board Failure Replace When the header unit of the group detect...

Page 226: ...t hand section of the 7 segment display B U1 OOO OOO Check code To check the check code set the rotary switches SW01 SW02 SW03 to 1 1 1 If there is a sub code the display alternates between the check code OOO 3 seconds and the sub code OOO 1 second 2 Check the check code and follow the applicable diagnostic procedure 3 If the 7 segment display shows U1 E28 there is an error in a follower unit Pres...

Page 227: ...nt oil recovery operation A Oil recovery in cooling C1 Normal C B Refrigerant recovery in heating H1 Normal H 11 Automatic addressing A Ad B During automatic addressing FF Normal 12 Power pick cut A dU B Normal During 50 90 capacity operation _50 _90 While control is based on BUS line input E50 E90 13 Optional control P C board input Displays optional control status A B Operation mode selection Du...

Page 228: ...ode A FP B Mode 0 to 63 0 to 63 7 Compressor backup A C b B Displays compressor backup setting status Normal Compressor No 1 backup 1 Compressor No 2 backup 1 Compressor No 3 backup 1 8 A B 9 Control valve output data Displays control output status of solenoid valve A B 4 way valve ON 4 way valve 2 OFF H 1 4 way valve OFF 4 way valve 2 ON H 0 10 SV2 ON SV5 OFF SV6 OFF 2 1 0 0 SV2 OFF SV5 ON SV6 ON...

Page 229: ...ter symbol and data are displayed alternately for 1 second and display for 3 seconds respectively Data with negative value is displayed as Letter symbol t d 1 Data 5 TD2 sensor data Letter symbol t d 2 Data 6 TD3 sensor data Letter symbol t d 3 Data 7 TS sensor data Letter symbol t S Data 8 TE1 sensor data Letter symbol t E Data 9 TE2 sensor data Letter symbol t E 2 Data 10 TL sensor data Letter s...

Page 230: ...ssor No 1 is ON 1 0 0 When compressor No 2 is ON 0 1 0 When compressor No 3 is ON 0 0 1 5 Fan operation mode A U SW03 setting No 1 Outdoor unit No U2 to U4 B At rest F 0 In mode 63 F 6 3 6 Release signal A U SW03 setting No 1 Outdoor unit No U2 to U4 B Normal r Upon receiving release signal r 1 7 Oil level judgment A U SW03 setting No 1 Outdoor unit No U2 to U4 B Normal Low level L 8 Compressor 1 ...

Page 231: ...4 will be displayed SW01 SW02 SW03 Display detail 4 1 16 1 4 Indoor BUS communication signal receiving status B Upon receiving signal 1 Other times 5 Indoor check code B No check code 6 Indoor HP capacity B 0 2 0 5 0 8 1 1 2 1 7 2 2 5 3 3 2 4 5 6 8 1 0 1 6 2 0 7 Indoor request command S code operation mode B represents mode COOL C HEAT H FAN F OFF S represents S code 0 to F 8 Indoor PMV opening da...

Page 232: ...g is completed revert the SW01 SW02 SW03 setting to 1 1 1 2 Oil Level Judgment Results Display example Displayed digit Judgment result Description O Normal The amount of oil in the compressor is sufficient 1 2 Low level The amount of oil in the compressor is insufficient Both 1 and 2 stand for insufficiency If this result persists the system will turn itself off in a protective shutdown 1 Start op...

Page 233: ... circuit capillary Strainer H Corresponding unit Oil level low detection and protection H07 Oil level low SV3E valve I Corresponding unit Oil level detection circuit error Oil level low detection and protection H16 05 H07 Oil circuit error Oil level low Oil level low Oil return distributor J Corresponding unit Oil level low detection and protection H07 Oil level low SV3C bypass capillary K Corresp...

Page 234: ...eck valve Check valve SV3A TD1 TK4 SV3E TK5 SV41 SV42 A3 Oil header Oil separator Fan SV3C Reducer TO SV SV SV SV SV SV SV SV SV Heat exchanger Left side Heat exchanger Fan motor FP Low pressure sensor Fusible plug High pressure SW High pressure SW Compressor 1 inverter Compressor 2 inverter Liquid side packed valve Gas side service valve Balance pipe packed valve A C D E J F K G H I B ...

Page 235: ... and protection H07 Oil level low SV3E valve I Corresponding unit Oil level detection circuit error Oil level low detection and protection H16 05 H07 Oil circuit error Oil level low Oil level low SV3F valve J Corresponding unit Oil level low detection and protection H07 Oil level low Oil return distributor K Corresponding unit Oil level low detection and protection H07 Oil level low SV3C bypass ca...

Page 236: ... TO SV3F SV3C SV SV SV SV SV SV SV SV SV SV SV Right side Main heat exchanger Left side Main heat exchanger Right side sub heat exchanger Fan motor Liquid side service valve Gas side service valve Balance pipe packed valve Low pressure sensor Accumulator Oil separator Liquid tank Fusible plug High pressure SW High pressure SW High pressure SW Compressor 1 inverter Compressor 2 inverter Compressor ...

Page 237: ... 95 100 105 110 115 120 181 5 138 5 107 2 83 6 65 7 52 0 41 5 33 4 27 1 22 1 18 1 14 9 12 4 10 4 8 7 7 3 6 2 5 3 4 5 3 9 3 3 2 9 2 5 2 2 1 9 Outdoor TS1 TE1 TE2 TL and TO sensors Outdoor TD1 TD2 TD3 TK1 TK2 TK3 TK4 and TK5 sensors Resistance kΩ 10 C or below Resistance kΩ 10 C or above Resistance kΩ 10 C or below Resistance kΩ 10 C or above 10 15 25 5 20 0 10 20 30 40 50 60 70 10 0 Temperature C 8...

Page 238: ...te 2 OUTPUT White 3 GND Black GND Black 4 5V Red 5V Red High pressure side Pd Low pressure side Ps 0 5 4 3V 0 3 73MPa 0 5 3 5V 0 0 98MPa 0 4 41 5 1 0 5 4 3 5 0 0 98 1 47 5 1 0 5 3 5 5 3 73 High pressure side output voltage V Low pressure side output voltage V Pressure MPa Pressure MPa 0 5 10 15 20 25 30 35 40 45 50 55 60 33 9 26 1 20 3 15 9 12 6 10 0 8 0 6 4 5 2 4 2 3 5 2 8 2 4 Temperature C Resis...

Page 239: ... 46 6 35 2 26 9 20 7 16 1 12 6 10 0 8 0 6 4 5 2 4 2 3 5 2 8 2 4 2 0 1 6 1 4 1 2 Temperature C Resistance kΩ Temperature C Resistance kΩ 10 15 5 20 0 10 20 30 40 50 60 70 10 0 80 90 100 20 30 100 150 50 200 0 10 15 5 20 0 10 20 30 40 50 60 70 10 0 80 90 100 20 30 100 150 50 200 0 Resistance kΩ 10 C or below Resistance kΩ 10 C or above Temperature C Resistance kΩ 10 C or below Resistance kΩ 10 C or ...

Page 240: ... 2 73 2 75 2 77 2 79 2 81 2 83 2 85 2 87 2 89 2 91 2 93 2 95 2 97 1 46 1 48 1 50 1 52 1 54 1 56 1 58 1 60 1 62 1 64 1 66 1 67 1 69 1 71 1 73 1 75 1 77 1 79 1 81 1 83 1 85 1 87 1 89 1 90 1 92 1 94 1 96 1 98 2 00 2 02 2 04 2 06 2 08 2 10 2 12 2 13 2 15 2 17 2 19 2 21 2 23 2 25 2 27 2 29 2 31 2 33 2 35 2 36 2 38 2 40 2 42 14 9 15 1 15 3 15 5 15 7 15 9 16 1 16 3 16 5 16 7 16 9 17 1 17 3 17 5 17 7 17 9...

Page 241: ...5 2 87 2 89 2 91 2 93 2 95 2 97 0 49 0 49 0 50 0 51 0 51 0 52 0 53 0 53 0 54 0 55 0 55 0 56 0 56 0 57 0 58 0 58 0 59 0 60 0 60 0 61 0 62 0 62 0 63 0 64 0 64 0 65 0 65 0 66 0 67 0 67 0 68 0 69 0 69 0 70 0 71 0 71 0 72 0 72 0 73 0 74 0 74 0 75 0 76 0 76 0 77 0 78 0 78 0 79 0 79 0 80 0 81 5 0 5 0 5 1 5 2 5 2 5 3 5 4 5 4 5 5 5 6 5 6 5 7 5 8 5 8 5 9 6 0 6 0 6 1 6 1 6 2 6 3 6 3 6 4 6 5 6 5 6 6 6 7 6 7 6...

Page 242: ...p outdoor units under outdoor unit backup operation to one in the system single refrigerant line Note 4 It is prohibited to combine compressor backup operation and outdoor unit backup operation Note 5 With a two outdoor unit system containing an MMY MAP1604 or MAP1404 and an MMY MAP1204 or MMY MAP0804 or MAP1004 do not preform outdoor unit backup operation to back up the MMY MAP1604 or MAP1404 It ...

Page 243: ... to all the units connected to the system This is the end of compressor backup operation setting Three compressor model SW06 Bit 1 Bit 2 Bit 3 Bit 4 Factory default setting OFF OFF OFF OFF When compressor No 1 front left is faulty ON OFF OFF OFF When compressor No 2 front center is faulty OFF ON OFF OFF When compressor No 3 front right is faulty OFF OFF ON OFF Two compressor model SW06 Bit 1 Bit 2...

Page 244: ...y open to prevent refrigerant stagnation in the unit However if there is a leakage from an outdoor PMV unable to close fully close the liquid pipe service valve 4 In case of fault in compressor electrical part I F P C board or IPDU P C board From this point on keep the power supply to the failed unit off In case of fault in refrigerating circuit or related part pressure sensor temperature sensor r...

Page 245: ...settings needed to gain permission for backup operation from the header unit error clearance 1 Set SW01 02 03 on the interface P C board to 1 1 1 and confirm that U1 E26 dropping out of an outdoor unit is displayed on the 7 segment display 2 Set SW01 02 03 on the interface P C board to 2 16 1 Upon confirming that Er is displayed on the 7 segment display press SW04 and hold for 5 seconds or more 3 ...

Page 246: ...part Disconnect the connector CN03 for outdoor outdoor communication BUS2 provided on the interface P C board Selection of new header unit 5 Select a new header unit from the follower units on the basis of the following criteria If only one follower unit is connected select it as the header unit If two or more follower units are connected select the follower unit that is nearest to the failed head...

Page 247: ...Turn on the power supply to protect the compressor by turning on the case heater When the power supply to the unit is turned on E19 error in the number of outdoor header units will be displayed on the 7 segment display However this will not cause any problems This is the end of header outdoor unit backup operation setting Check the operation 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 ...

Page 248: ... electric circuit this function is not available In that case follow the procedure specified in the Outdoor Unit Backup Operation Setting section Work procedure 1 Turn off the power supply to all the units connected to the system Setup of failed outdoor unit Regardless of whether the failed outdoor unit is the header unit or a follower unit there is no difference in the setup procedure 2 Turn on B...

Page 249: ...the heat exchangers or sub heat exchangers cannot be recovered In that case recover any residual gas in the heat exchangers or sub heat exchangers using a tube piercing valve or some other tool After a pump down operation do not perform any welding until the residual gas in the heat exchangers is recovered 10 1 2 Refrigerant recovery procedure A Case of no outdoor unit backup operation setting Wor...

Page 250: ...or pressure adjustment to 1 2 2 11 As the low pressure sensor output is displayed on the 7 segment display adjust the pressure to around 0 12 MPa by slowly closing the gas pipe service valve with checking pressure data 12 Compare the low pressure sensor outputs of the failed unit with that of the unit for pressure adjustment and wait until the two pressure readings become almost the same After let...

Page 251: ...ose gas pipe service valve 8 Select outdoor unit with lowest unit No as outdoor unit for pressure adjustment Fully close balance pipes of all outdoor units other than unit for pressure adjustment and failed unit While monitoring low pressure sensor output adjust pressure to around 0 12 MPa by slowly closing gas pipe service valve When low pressure sensor output of failed outdoor unit falls below 0...

Page 252: ... 1 Connect the liquid pipe check joint and the low pressure side check joint using a gauge manifold and purge the manifold of air to recover refrigerant from the liquid tank and heat exchangers 2 Fully close the liquid pipe packed valve of the failed outdoor unit Leave the service valve of the gas pipe and the packed valve of the balance pipe fully open Setup of unit selected as header unit hereaf...

Page 253: ...covery device Be sure to measure the amount of recovered refrigerant This is necessary to determine how much additional refrigerant will be needed after the completion of the repair This is the end of the refrigerant recovery operation Set SW01 02 03 of the header unit back to 1 1 1 8 6 7 9 10 12 11 Approx 10 minutes after system startup fully close gas pipe service valve Select header unit as uni...

Page 254: ... a 10HP outdoor unit is under repair in a 30HP system Amount of refrigerant required by system as it was initially 30HP in capacity 34 5kg Amount of refrigerant required by system with available outdoor units only 20HP in capacity 26 0kg Amount of refrigerant to be removed from system 34 5 26 0 8 5kg 3 Set up the outdoor unit from which refrigerant has been recovered in the manner described in 9 3...

Page 255: ... suction pipe SW12 CN30 PMV operation Bit 1 Bit 2 Bit 3 Bit 4 OFF OFF OFF OFF Short circuit PMV1 and 2 fully open for 2 minutes OFF ON OFF OFF Short circuit PMV4 fully opens for 2 minutes TL PMV1 4 way valve Check valve High pressure sensor TD2 Accumulator TS1 SV2 Low pressure sensor TE1 M SV3D PMV2 TK2 SV3B TK1 SV3A TD1 TK4 SV3E TK5 SV41 SV42 Oil pipe PMV4 Fan Liquid tank TE2 Left side sub heat e...

Page 256: ...ituations such as indoor unit relocation and repairs it is not possible to recover all the refrigerant held by the system in the outdoor units It could cause a serious accident such as blow out or injury Be sure to perform refrigerant recovery using a refrigerant recovery device WARNING When detaching a pipe by heating with a burner a welded joint take care as any oil left in the piping may burn i...

Page 257: ...d A cc by following the steps below 1 Amount of oil in faulty compressor A cc 0 A 1000 1 Adjust the amount of oil in the new compressor to 1000cc Lay the new compressor down and draw 900 cc of oil via the oil equalization pipe Notes Do not draw more than 900 cc of oil as it may cause damage to the compressor If the faulty compressor contained 500cc or less there may have been a problem with the oi...

Page 258: ...al compressor contained B cc by following the steps below 1 Combined amount of oil in faulty and normal compressors A B cc 0 A B 2000 1 Adjust the amount of oil in the two new compressors to 1000cc each total 2000cc Lay the compressors down and draw 900 cc of oil from each of them via their oil equalization pipes Notes Do not draw more than 900 cc of oil from a compressor as it may cause damage If...

Page 259: ... following the steps below 1 Combined amount of oil in faulty compressor and two normal compressors A B C cc 0 A B C 3000 1 Adjust the amount of oil in the three new compressors to 1000cc each total 3000cc Lay the compressors down and draw 900 cc of oil from each of them via their oil equalization pipes Notes Do not draw more than 900 cc of oil from a compressor as it may cause damage If the fault...

Page 260: ...f the outdoor unit cannot be vacuum pumped Connect a vacuum pump consecutively to the check joints placed in the liquid and discharge pipes and on the high pressure side of the suction pipe and turn it on Operate the vacuum drying until the vacuum gauge indicates 1 mmHg Method to fully open PMV manually 1 Turn on the power switch of the outdoor unit 2 With the Bits 1 and 2 of SW12 set to off short...

Page 261: ...ted to the same refrigerant line fully open Are the characteristics of the TK1 TK2 TK3 TK4 or TK5 sensors of the unit that has replaced compressor correct To next page No No No Yes TK1 CN531 TK2 CN532 TK3 CN533 TK4 CN534 TK5 CN535 Yes Yes With the compressor s disconnected check the oil circuit in accordance with the procedure described below Open the balance pipe valves fully Correct the miswirin...

Page 262: ...e pipe with nitrogen manually open the SV3B valve If gas escapes from the suction pipe section of the disconnected compressor there is a leak from the SV3A valve Replace the part Leakage of SV3B valve H 6 Then manually open the SV3A valve If gas escapes from the suction pipe section of the disconnected compressor there is a leak from the SV3B valve Replace the part Clogging of SV3E valve Clogging ...

Page 263: ...y open the SV3B valve If gas escapes from the suction pipe section of the disconnected compressor there is a leak from the SV3A valve Replace the part Leakage of SV3B valve H 6 Then manually open the SV3A valve If gas escapes from the suction pipe section of the disconnected compressor there is a leak from the SV3B valve Replace the part Clogging of SV3E valve Clogging of oil return distributor I ...

Page 264: ... 5 Remove the screws for the suction cabinet Front and rear M5 10 4 pcs each 6 Remove the screws for the discharge cabinet side cabinet Left and right M5 10 6 pcs each 2 Attachment Carry out installation by following the detachment procedure in reverse 6 1 Be careful of the hooks provided on the suction cabinet service panel and lower cabinet With a 14 16HP unit the discharge cabinet side covers n...

Page 265: ... the fan motor and propeller fan To loosen the nut turn it clockwise 5 Remove the square washer 6 Remove the propeller fan CAUTION Lift it straight up Do not forcibly pull it or it may get stuck 7 Disconnect the faston connectors for the fan motor leads 3 pieces from the Fan IPDU and pull the leads up and out 8 Remove the fan motor M6 20 4 pcs No Part to be replaced Work procedure Remarks Discharg...

Page 266: ...ue to friction heat 2 Be sure to put the square washer in place Otherwise unusual noises and vibrations may result 3 Tighten the flange nut at a torque of 15N m 153kgf cm To tighten the flange nut turn it counterclockwise 4 Remove the clamp filter from the fan motor with trouble then attach the clamp filter to the substitution in the same way as before replacement Wind the fan motor lead once arou...

Page 267: ...rews for the waterproof board M4 10 2 pcs 6 Remove the brazed joints of the piping connected 2 locations 7 Remove the screws for the heat exchanger end plate and pull the heat exchanger out M5 10 2 pcs No Part to be replaced Work procedure Remarks With a 14 16HP unit remove the discharge cabinet anchor plates Left and right M5 2 2 pcs 2 sets With a 14 16HP unit also remove the brazed joints of the...

Page 268: ...following the dismantling procedure in reverse 7 1 Before pushing the lower part in pull the reactor leads out Take care so that the wiring does not get caught in the way Reconnect all the wiring No Part to be replaced Work procedure Remarks 4 Steps only applicable to a 14 16HP unit Remove the reactor lead cover M4 10 1 pc Remove the screws securing the box M4 10 1 pc Detach the reactor leads 6 te...

Page 269: ... 5 Remove and replace the reactor M4 6 1 pc 14 16HP case 8 10 12HP case No Part to be replaced Work procedure Remarks 3 With a 14 16HP unit remove the separately mounted reactor box To remove the reactor box remove the screws at the top and bottom M5 10 and unlock the box by sliding the stopper to the right Before pulling the reactor box tilt it back to free the bottom With a 14 16HP unit remove t...

Page 270: ...s SV3B SV3D SV42 PD sensor PS sensor SV41 Accumulator Rear Front Inverter assembly Liquid tank Oil separator Compressor 1 SV2 SV5 SV3A SV3C SV3E Compressor 2 SV3B SV3D SV42 SV43 PD sensor PS sensor SV41 Accumulator Rear Front Inverter assembly Liquid tank Oil separator Compressor 1 SV2 SV6 SV3A SV3C SV3E SV3F Compressor 2 Compressor 3 ...

Page 271: ...oduct Rear View No Part to be replaced Work procedure Remarks TD1 sensor yellow TD2 sensor red Accumulator Compressor 1 Compressor 2 TS1 sensor gray TK4 sensor white TK5 sensor green Accumulator Liquid tank Oil separator TK1 sensor black One closer to you TK2 sensor blue One farther from you TL sensor white ...

Page 272: ... to be replaced Work procedure Remarks Accumulator Compressor 1 Compressor 2 Compressor 3 TD1 sensor yellow TD2 sensor red TD3 sensor black Accumulator Liquid tank Oil separator TK4 sensor white TS1 sensor gray TK3 sensor yellow TK1 sensor black One closer to you TK5 sensor green TL sensor white TK2 sensor blue One farther from you ...

Page 273: ...locations No Part to be replaced Work procedure Remarks SV41 valve Suction pipe Ø8 0 Ø19 05 SV42 valve Suction pipe Ø8 0 Ø19 05 SV2 valve Discharge pipe Ø6 35 Ø15 88 Oil header Liquid pipe Ø25 4 Ø12 7 Suction pipe Distributor Ø19 05 Ø22 22 SV41 valve Suction pipe Ø8 0 Ø19 1 SV42 valve Suction pipe Ø8 0 Ø19 1 SV43 valve Suction pipe Ø8 0 Ø19 1 SV2 valve Discharge pipe Ø6 35 Ø19 1 Liquid pipe Balanc...

Page 274: ... band can be placed the other way around but only at the expense of work efficiency 3 Place the SUS band tightly around the pipe fixing rubber so that there is no gap between them Take utmost care not to create a gap over the curved section of the rubber where the hairpin side of the band is located 4 While holding the rubber press down the base of the hook lightly against the rubber and engage th...

Page 275: ... valve 7 Remove the end sections of the pipes above the 4 way valve which were cut in step 5 8 Install a new 4 way valve Provide adequate cover for the 4 way valve to protect it from overheating During the installation insert pipes firmly into the 4 way valve or a blockage or leakage involving brazing filler metal may result 9 Reinstall the PMV assembly which was removed in step 4 Provide adequate...

Page 276: ... way valve 7 Remove the end sections of the pipes above the 4 way valve which were cut in step 5 8 Install a new 4 way valve Provide adequate cover for the 4 way valve to protect it from overheating During the installation insert pipes firmly into the 4 way valve or a blockage or leakage involving brazing filler metal may result 9 Reinstall the PMV assembly which was removed in step 4 Provide adeq...

Page 277: ...ader follower designation and confirm the integrity of the refrigerating cycle by conducting a test operation etc Replacement procedure Method 1 If it is possible to turn on the indoor unit and read the setting data from the P C board to be replaced via a wired remote controller Reading EEPROM data Procedure 1 Replacing P C board and turning on power Procedure 2 Writing EEPROM data in new EEPROM P...

Page 278: ...d the method to replace it see the EEPROM Location Diagram section The old EEPROM supplied with the P C board to be replaced and now mounted on the service P C board needs to be replaced with the new EEPROM supplied with the service P C board Replacing P C board and turning on power Procedure 2 Writing EEPROM data in new EEPROM Procedure 3 Resetting power supply applicable to all indoor units conn...

Page 279: ...rom 10 to 01 To set filter sign lighting time Jot down the setting data displayed 5 Change the CODE No DN code using the button Again jot down the setting data displayed 6 Repeat step 5 until all the setting data has been jotted down See the CODE No list CODE No DN code go from 01 to FF with a few gaps along the way 7 When finished push the button to bring the system back to normal off state 6 It ...

Page 280: ... units in the same group b Turn on the indoor unit and proceed to Procedure 3 Be sure to restore the temporarily removed group control wiring and CN41 connectors to their initial states after Procedure 3 has been completed CN34 red SW501 J01 J02 MCC 1403 MCC 1402 MCC 1570 CN030 CN41 CN34 CN041 Connector for drain pump CN504 AP009 AP030 AP036 AP056 Cut Present factory default J02 If a short circuit...

Page 281: ...ayed 10 Push the button to bring the system back to normal off state 6 4 Next write any setting changes made on site after installation such as address settings in the EEPROM Perform the tasks specified in step 1 again 5 Use the button to set the CODE No DN code to 01 To set filter sign lighting time 6 Check the value displayed with the value jotted down in Procedure 1 and information proved by th...

Page 282: ...alling it adjust its orientation as shown in the diagram below During EEPROM removal installation take care not to bend IC leads IC503 P C board MCC 1402 P C board MCC 1570 P C board MCC 1403 EEPROM IC10 EEPROM IC10 IC socket Notch Notch EEPROM EEPROM IC503 When installing the EEPROM align its notch with that of the IC socket ...

Page 283: ...remote controller 0000 Available F0 Swing mode 0001 Standard F1 Louver fixing position Flap No 1 0000 Not fixed 4 way type only F2 Louver fixing position Flap No 2 0000 Not fixed 4 way type only F3 Louver fixing position Flap No 3 0000 Not fixed 4 way type only F4 Louver fixing position Flap No 4 0000 Not fixed 4 way type only Type Code No 10 Setup data Type Model abb name 0000 1 way Air Discharge...

Page 284: ... 1608 A B ASM PCB N F MMY MAP1204 MMY MAP1004 MMY MAP0804 MMY MAP1404 MMY MAP1604 Inverter P C board for fan Fan IPDU MCC 1610 Inverter P C Board for Compressor 1 A3 IPDU MCC 1596 Inverter P C Board for Compressor 2 A3 IPDU MCC 1596 Interface P C board Outdoor control P C board MCC 1606 Power supply terminal block Communication terminal block Magnet switch Inverter P C board for fan Fan IPDU MCC 1...

Page 285: ...e PCB being replaced 6 Install the service board to the outdoor control unit Confirm that it is securely fixed to the PCB Mounts 7 Connect the connectors and fast on terminals Confirm that they are correctly and securely inserted 8 If a component on the board is bent during board replacement adjust it manually ensuring that it is not short or contact other parts 9 Install the cover then turn on th...

Page 286: ...U from the four spacers 3 by pinching the top of the spacers by round nose pliers 5 Confirm that no dirt or damage is on the insulation sheet flesh color on the heat sink As it can reduce the heat transfer efficiency and can cause a breakdown If the insulation sheet comes off the heat sink re apply the insulation sheet as shown in the following figure Compressor IPDU MCC 1596 e g MMY MAP1004HT8 Co...

Page 287: ...screws for DB01 is 0 55Nm and it for Q201 is 1 2Nm 9 Re connect the connectors and fast on terminals 1 Be sure that all the connectors and the fast on terminals are connected correctly and securely inserted 10 If the components on the PCB were bent during this procedure straighten them so they do not touch other parts 11 Install the cover then turn on the supply Check the operation ON 3 4 2 1 ON 3...

Page 288: ...tdoor control unit by clipping the PCB into the PCB mounts 3 7 Screw the FAN IPDU to the heat sink by the five screws that were removed in step 3 If the screws are loose the effected component will generate heat and cause in to breakdown Do not use an electric driver or an air driver as it can cause component damage The torque of 5 screws IC701 DB509 DB510 and Q590 is 0 55Nm 8 Re connect the conne...

Page 289: ... the screws on the power supply terminal block 4 and the screws 3 securing the terminal block sub assembly 1 The screws will be reused during the installation of the service P C board so keep them in a safe place 7 Card edge spacer 8 8 3 Example MMY MAP1004HT8 Z ZG Noise filter P C board 431 6V 440 Noise filter P C board MCC 1608 9 Line filter Noise filter P C board A MMC 1608 Noise filter P C boa...

Page 290: ...lter 9 and its leads both connected to the screw on terminals 8 of the just removed noise filter P C board A and reinstall them on the service P C board A by firmly connecting them to the screw on terminals 8 in the same manner as before Line Filter installation Screw the line filter and the connecting wires together to the terminals as below The torque of 6 screws of the line filter is 2 5Nm Plea...

Page 291: ...ect the wiring using the connectors and fastons removed in step 3 Make sure that the connectors and fastons are connected correctly and securely 10 If any component on the P C board becomes crooked during replacement straighten it without touching any other component 11 Mount the terminal block sub assembly 1 and firmly secure it using the screws 3 12 Securely connect the red white and black leads...

Page 292: ...14EXPLODED DIAGRAM PARTS PRICE LIST SMMS i OUTDOOR UNIT MMY MAP0804HT8 Z ZG E MMY MAP1004HT8 Z ZG E MMY MAP1204HT8 Z ZG E 035 002 064 065 001 037 053 036 058 003 060 055 052 004 061 007 009 077 068 059 011 ...

Page 293: ...A 016 018 018 016 SV3C 030 SV3E 018 016 SV2 016 018 041 028 023 022 017 057 026 027 SV5 056 043 015 014 069 025 019 043 013 070 008 027 026 007 009 042 033 010 040 066 066 067 072 045 046 078 066 078 050 046 SV4 047 051 078 044 048 078 ...

Page 294: ...43 056 018 033 026 008 007 018 083 075 075 083 007 026 018 083 074 043 023 057 018 021 041 042 013 018 084 081 086 015 014 040 028 083 074 083 073 008 043 LIQUID LINE VALVE PACKED GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT CHECK STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE CHECKED LOW PRESSURE SENSOR PLUG FUSIBLE SEPARATOR OIL HIGH PRESSURE SWITCH Symbol ...

Page 295: ...294 SMMS i OUTDOOR UNIT MMY MAP1404HT8 Z ZG E MMY MAP1604HT8 Z ZG E 035 002 001 064 065 011 054 039 053 038 058 005 052 055 062 059 063 006 007 009 068 077 ...

Page 296: ...019 3 013 012 015 017 023 022 024 040 016 018 016 018 029 047 049 078 078 046 051 016 018 016 020 016 018 042 016 018 016 021 066 2 078 047 049 041 047 044 078 072 016 020 049 046 031 051 047 078 046 050 078 050 046 078 050 046 078 079 078 032 010 066 066 SV3A SV3C SV3B SV3E SV3D SV3F SV2 SV6 SV41 SV42 SV43 056 057 ...

Page 297: ... 040 008 040 018 008 083 040 083 043 056 032 083 FAN MOTOR FAN VALVE 4WAY LIQUID LINE VALVE SERVICE GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE Symbol OIL HEADER HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH ACCUMULATOR LOW PRESSURE SENSOR HIGH PRESSURE SWITCH SEPARATOR OIL TANK LIQUID PLUG FUSIBLE CONDENSER RIGHT S...

Page 298: ...12TF 6 2 2 2 3 3 020 43146712 VALVE 2WAY VPV 303DQ1 2 2 021 43146730 VALVE 2WAY VPV 603DQ2 1 1 1 1 1 022 4314N042 VALVE 4WAY STF 0740G 1 1 1 1 1 023 43146734 VALVE CHECK ZGV S55B A 1 1 1 1 1 024 43146742 VALVE CHECK ZGV S66B A 1 1 025 4314N043 VALVE PMV HAM BD28TF 1 2 2 2 3 3 026 4314N044 VALVE 2WAY FDF3A06 3 3 3 3 3 027 4314N047 COIL VALVE 2WAY FQ G593 3 3 3 3 3 028 43148241 SEPARATOR 5L 1 1 1 02...

Page 299: ...4 4 5 5 067 43149323 RUBBER SUPPORTER PIPE 9 52 12 7 2 2 2 068 43149324 RUBBER CUSHION 6 6 6 9 9 069 43147195 BONNET 1 2 IN 1 1 1 070 43047401 BONNET 3 8 IN 1 1 1 1 1 071 43194029 BONNET 5 8 IN 1 1 072 43148220 PLUG FUSIBLE 1 1 1 1 1 073 44246235 TUBE CAPILLARY BYPASS ID 0 8 1 1 1 1 1 074 44246236 TUBE CAPILLARY BYPASS ID 1 0 1 1 1 1 1 075 44246239 TUBE CAPILLARY ID 1 2 1 1 1 1 1 076 43019904 HOLD...

Page 300: ... 2 3 4 1 SW06 L1 R CN32 L2 S CN31 CN33 L3 T WHI RED BLK 1 600V 75A 22m m 2 L 1 L 2 C Q C J X O 6 0 0 4 L 3 N O LD E R 4 0mm 2 BLU WHI BLU WHI WHI JXO B2F 600V WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 RED N CN34 L3 T CN32 CN33 WHI BLK 706 707 707 703 711 712 713 718 719 717 709 721 TD1...

Page 301: ...L3 T COMP2 COMP1 JXO 6B COMP3 1 600V 75A 22m m 2 L1 L2 C Q C JX O 6 0 0 4 L3 N O LD ER 4 0mm 2 WHI WHI WHI BLU WHI BLU BLU WHI BLU 600V JXO B2F WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 L3 T CN32 CN33 RED N CN34 WHI BLK 706 707 707 707 703 712 711 713 717 718 719 709 721 TD1 TD2 TD3 TK...

Page 302: ...60621 TERMINAL 6P 1 1 709 43152519 CONTACTOR MAGNETIC 1 1 1 1 1 710 43160583 TERMINAL 6P 1 1 1 1 1 711 43069524 SUPPORT SPACER 3 3 3 3 3 712 43182011 SPACER EDGE 10 10 10 10 10 713 4316V440 PC BOARD ASSY NOISE FILTER MCC 1608 1 1 1 1 1 714 4316V420 PC BOARD ASSY INTERFACE MCC 1606 1 1 1 1 1 715 4316V422 PC BOARD ASSY FAN IPDU MCC 1610 1 1 1 1 1 716 4316V441 PC BOARD ASSY COMP IPDU MCC 1596 2 2 2 3...

Page 303: ...302 SMMS i OUTDOOR UNIT MMY MAP0804T8 Z ZG E MMY MAP1004T8 Z ZG E MMY MAP1204T8 Z ZG E 035 002 064 065 001 037 053 036 058 003 060 055 052 004 061 007 009 077 068 059 011 ...

Page 304: ... SV3A 016 018 018 016 SV3C 030 SV3E 018 016 SV2 016 018 041 028 023 057 026 027 SV5 056 043 015 014 069 025 019 043 013 070 008 027 026 007 009 042 033 010 040 066 066 067 072 045 046 078 066 078 050 046 SV4 047 051 078 044 048 078 ...

Page 305: ...018 033 026 008 007 018 083 075 075 083 007 026 018 083 074 043 023 057 018 021 041 042 013 018 084 081 086 015 014 040 028 083 074 083 073 008 043 LIQUID LINE VALVE PACKED GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT CHECK STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE CHECKED LOW PRESSURE SENSOR PLUG FUSIBLE SEPARATOR OIL HIGH PRESSURE SWITCH Symbol CONDENS...

Page 306: ...305 SMMS i OUTDOOR UNIT MMY MAP1404T8 Z ZG E MMY MAP1604T8 Z ZG E 035 002 001 064 065 011 054 039 053 038 058 005 052 055 062 059 063 006 007 009 068 077 ...

Page 307: ...019 3 013 012 015 023 024 040 016 018 016 018 029 047 049 078 078 046 051 016 018 016 020 016 018 042 016 018 016 021 066 2 078 047 049 041 047 044 078 072 016 020 049 046 031 051 047 078 046 050 078 050 046 078 050 046 078 079 078 032 010 066 066 SV3A SV3C SV3B SV3E SV3D SV3F SV2 SV6 SV41 SV42 SV43 056 057 043 ...

Page 308: ...040 008 040 018 008 083 040 083 043 056 032 083 FAN MOTOR FAN LIQUID LINE VALVE SERVICE GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE Symbol OIL HEADER HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH ACCUMULATOR LOW PRESSURE SENSOR HIGH PRESSURE SWITCH SEPARATOR OIL TANK LIQUID PLUG FUSIBLE CONDENSER RIGHT SIDE CONDENSE...

Page 309: ... 2 2 2 3 3 020 43146712 VALVE 2WAY VPV 303DQ1 2 2 021 43146730 VALVE 2WAY VPV 603DQ2 1 1 1 1 1 023 43146734 VALVE CHECK ZGV S55B A 1 1 1 1 1 024 43146742 VALVE CHECK ZGV S66B A 1 1 025 4314N043 VALVE PMV HAM BD28TF 1 2 2 2 3 3 026 4314N044 VALVE 2WAY FDF3A06 3 3 3 3 3 027 4314N047 COIL VALVE 2WAY FQ G593 3 3 3 3 3 028 43148241 SEPARATOR 5L 1 1 1 029 43148249 SEPARATOR 6L 1 1 030 43148247 TANK LIQU...

Page 310: ... 4 4 4 5 5 067 43149323 RUBBER SUPPORTER PIPE 9 52 12 7 2 2 2 068 43149324 RUBBER CUSHION 6 6 6 9 9 069 43147195 BONNET 1 2 IN 1 1 1 070 43047401 BONNET 3 8 IN 1 1 1 1 1 071 43194029 BONNET 5 8 IN 1 1 072 43148220 PLUG FUSIBLE 1 1 1 1 1 073 44246235 TUBE CAPILLARY BYPASS ID 0 8 1 1 1 1 1 074 44246236 TUBE CAPILLARY BYPASS ID 1 0 1 1 1 1 1 075 44246239 TUBE CAPILLARY ID 1 2 1 1 1 1 1 076 43019904 H...

Page 311: ... 3 4 1 SW06 L1 R CN32 L2 S CN31 CN33 L3 T WHI RED BLK 1 600V 75A 22m m 2 L 1 L 2 C Q C J X O 6 0 0 4 L 3 N O LD E R 4 0mm 2 BLU WHI BLU WHI WHI JXO B2F 600V WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 RED N CN34 L3 T CN32 CN33 WHI BLK 706 707 707 703 711 712 713 718 719 717 709 721 TD1 T...

Page 312: ...3 T COMP2 COMP1 JXO 6B COMP3 1 600V 75A 22m m 2 L1 L2 C Q C JX O 6 0 0 4 L3 N O LD ER 4 0mm 2 WHI WHI WHI BLU WHI BLU BLU WHI BLU 600V JXO B2F WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 L3 T CN32 CN33 RED N CN34 WHI BLK 706 707 707 707 703 712 711 713 717 718 719 709 721 TD1 TD2 TD3 TK1...

Page 313: ...21 TERMINAL 6P 1 1 709 43152519 CONTACTOR MAGNETIC 1 1 1 1 1 710 43160583 TERMINAL 6P 1 1 1 1 1 711 43069524 SUPPORT SPACER 3 3 3 3 3 712 43182011 SPACER EDGE 10 10 10 10 10 713 4316V440 PC BOARD ASSY NOISE FILTER MCC 1608 1 1 1 1 1 714 4316V420 PC BOARD ASSY INTERFACE MCC 1606 1 1 1 1 1 715 4316V422 PC BOARD ASSY FAN IPDU MCC 1610 1 1 1 1 1 716 4316V441 PC BOARD ASSY COMP IPDU MCC 1596 2 2 2 3 3 ...

Page 314: ...313 SMMS i OUTDOOR UNIT MMY MAP0804HT8 Z ZG MMY MAP1004HT8 Z ZG MMY MAP1204HT8 Z ZG 035 002 064 065 001 037 053 036 058 003 060 055 052 004 061 007 009 077 068 059 011 ...

Page 315: ...A 016 018 018 016 SV3C 030 SV3E 018 016 SV2 016 018 041 028 023 022 017 057 026 027 SV5 056 043 015 014 069 025 019 043 013 070 008 027 026 007 009 042 033 010 040 066 066 067 072 045 046 078 066 078 050 046 SV4 047 051 078 044 048 078 ...

Page 316: ...43 056 018 033 026 008 007 018 083 075 075 083 007 026 018 083 074 043 023 057 018 021 041 042 013 018 084 081 086 015 014 040 028 083 074 083 073 008 043 LIQUID LINE VALVE PACKED GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT CHECK STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE CHECKED LOW PRESSURE SENSOR PLUG FUSIBLE SEPARATOR OIL HIGH PRESSURE SWITCH Symbol ...

Page 317: ...316 SMMS i OUTDOOR UNIT MMY MAP1404HT8 Z ZG MMY MAP1604HT8 Z ZG 035 002 001 064 065 011 054 039 053 038 058 005 052 055 062 059 063 006 007 009 068 077 ...

Page 318: ...019 3 013 012 015 017 023 022 024 040 016 018 016 018 029 047 049 078 078 046 051 016 018 016 020 016 018 042 016 018 016 021 066 2 078 047 049 041 047 044 078 072 016 020 049 046 031 051 047 078 046 050 078 050 046 078 050 046 078 079 078 032 010 066 066 SV3A SV3C SV3B SV3E SV3D SV3F SV2 SV6 SV41 SV42 SV43 056 057 ...

Page 319: ... 040 008 040 018 008 083 040 083 043 056 032 083 FAN MOTOR FAN VALVE 4WAY LIQUID LINE VALVE SERVICE GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE Symbol OIL HEADER HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH ACCUMULATOR LOW PRESSURE SENSOR HIGH PRESSURE SWITCH SEPARATOR OIL TANK LIQUID PLUG FUSIBLE CONDENSER RIGHT S...

Page 320: ...2 2 2 3 3 020 43146712 VALVE 2WAY VPV 303DQ1 2 2 021 43146730 VALVE 2WAY VPV 603DQ2 1 1 1 1 1 022 4314N042 VALVE 4WAY STF 0740G 1 1 1 1 1 023 43146734 VALVE CHECK ZGV S55B A 1 1 1 1 1 024 43146742 VALVE CHECK ZGV S66B A 1 1 025 4314N043 VALVE PMV HAM BD28TF 1 2 2 2 3 3 026 4314N044 VALVE 2WAY FDF3A06 3 3 3 3 3 027 4314N047 COIL VALVE 2WAY FQ G593 3 3 3 3 3 028 43148241 SEPARATOR 5L 1 1 1 029 43148...

Page 321: ...ND 4 4 4 5 5 067 43149323 RUBBER SUPPORTER PIPE 9 52 12 7 2 2 2 068 43149324 RUBBER CUSHION 6 6 6 9 9 069 43147195 BONNET 1 2 IN 1 1 1 070 43047401 BONNET 3 8 IN 1 1 1 1 1 071 43194029 BONNET 5 8 IN 1 1 072 43148220 PLUG FUSIBLE 1 1 1 1 1 073 44246235 TUBE CAPILLARY BYPASS ID 0 8 1 1 1 1 1 074 44246236 TUBE CAPILLARY BYPASS ID 1 0 1 1 1 1 1 075 44246239 TUBE CAPILLARY ID 1 2 1 1 1 1 1 076 43019904...

Page 322: ...3 4 1 SW06 L1 R CN32 L2 S CN31 CN33 L3 T WHI RED BLK 1 600V 75A 22m m 2 L 1 L 2 C Q C J X O 6 0 0 4 L 3 N O LD E R 4 0mm 2 BLU WHI BLU WHI WHI JXO B2F 600V WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 RED N CN34 L3 T CN32 CN33 WHI BLK 706 707 707 703 711 712 713 718 719 717 709 721 TD1 TD...

Page 323: ... T COMP2 COMP1 JXO 6B COMP3 1 600V 75A 22m m 2 L1 L2 C Q C JX O 6 0 0 4 L3 N O LD ER 4 0mm 2 WHI WHI WHI BLU WHI BLU BLU WHI BLU 600V JXO B2F WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 L3 T CN32 CN33 RED N CN34 WHI BLK 706 707 707 707 703 712 711 713 717 718 719 709 721 TD1 TD2 TD3 TK1 ...

Page 324: ... TERMINAL 6P 1 1 709 43152519 CONTACTOR MAGNETIC 1 1 1 1 1 710 43160583 TERMINAL 6P 1 1 1 1 1 711 43069524 SUPPORT SPACER 3 3 3 3 3 712 43182011 SPACER EDGE 10 10 10 10 10 713 4316V440 PC BOARD ASSY NOISE FILTER MCC 1608 1 1 1 1 1 714 4316V420 PC BOARD ASSY INTERFACE MCC 1606 1 1 1 1 1 715 4316V422 PC BOARD ASSY FAN IPDU MCC 1610 1 1 1 1 1 716 4316V441 PC BOARD ASSY COMP IPDU MCC 1596 2 2 2 3 3 71...

Page 325: ...324 SMMS i OUTDOOR UNIT MMY MAP0804T8 Z ZG MMY MAP1004T8 Z ZG MMY MAP1204T8 Z ZG 035 002 064 065 001 037 053 036 058 003 060 055 052 004 061 007 009 077 068 059 011 ...

Page 326: ... SV3A 016 018 018 016 SV3C 030 SV3E 018 016 SV2 016 018 041 028 023 057 026 027 SV5 056 043 015 014 069 025 019 043 013 070 008 027 026 007 009 042 033 010 040 066 066 067 072 045 046 078 066 078 050 046 SV4 047 051 078 044 048 078 ...

Page 327: ...018 033 026 008 007 018 083 075 075 083 007 026 018 083 074 043 023 057 018 021 041 042 013 018 084 081 086 015 014 040 028 083 074 083 073 008 043 LIQUID LINE VALVE PACKED GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT CHECK STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE CHECKED LOW PRESSURE SENSOR PLUG FUSIBLE SEPARATOR OIL HIGH PRESSURE SWITCH Symbol CONDENS...

Page 328: ...327 SMMS i OUTDOOR UNIT MMY MAP1404T8 Z ZG MMY MAP1604T8 Z ZG 035 002 001 064 065 011 054 039 053 038 058 005 052 055 062 059 063 006 007 009 068 077 ...

Page 329: ...019 3 013 012 015 023 024 040 016 018 016 018 029 047 049 078 078 046 051 016 018 016 020 016 018 042 016 018 016 021 066 2 078 047 049 041 047 044 078 072 016 020 049 046 031 051 047 078 046 050 078 050 046 078 050 046 078 079 078 032 010 066 066 SV3A SV3C SV3B SV3E SV3D SV3F SV2 SV6 SV41 SV42 SV43 056 057 043 ...

Page 330: ...040 008 040 018 008 083 040 083 043 056 032 083 FAN MOTOR FAN LIQUID LINE VALVE SERVICE GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE Symbol OIL HEADER HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH ACCUMULATOR LOW PRESSURE SENSOR HIGH PRESSURE SWITCH SEPARATOR OIL TANK LIQUID PLUG FUSIBLE CONDENSER RIGHT SIDE CONDENSE...

Page 331: ...2 3 3 020 43146712 VALVE 2WAY VPV 303DQ1 2 2 021 43146730 VALVE 2WAY VPV 603DQ2 1 1 1 1 1 023 43146734 VALVE CHECK ZGV S55B A 1 1 1 1 1 024 43146742 VALVE CHECK ZGV S66B A 1 1 025 4314N043 VALVE PMV HAM BD28TF 1 2 2 2 3 3 026 4314N044 VALVE 2WAY FDF3A06 3 3 3 3 3 027 4314N047 COIL VALVE 2WAY FQ G593 3 3 3 3 3 028 43148241 SEPARATOR 5L 1 1 1 029 43148249 SEPARATOR 6L 1 1 030 43148247 TANK LIQUID 11...

Page 332: ... BAND 4 4 4 5 5 067 43149323 RUBBER SUPPORTER PIPE 9 52 12 7 2 2 2 068 43149324 RUBBER CUSHION 6 6 6 9 9 069 43147195 BONNET 1 2 IN 1 1 1 070 43047401 BONNET 3 8 IN 1 1 1 1 1 071 43194029 BONNET 5 8 IN 1 1 072 43148220 PLUG FUSIBLE 1 1 1 1 1 073 44246235 TUBE CAPILLARY BYPASS ID 0 8 1 1 1 1 1 074 44246236 TUBE CAPILLARY BYPASS ID 1 0 1 1 1 1 1 075 44246239 TUBE CAPILLARY ID 1 2 1 1 1 1 1 076 43019...

Page 333: ...4 1 SW06 L1 R CN32 L2 S CN31 CN33 L3 T WHI RED BLK 1 600V 75A 22m m 2 L 1 L 2 C Q C J X O 6 0 0 4 L 3 N O LD E R 4 0mm 2 BLU WHI BLU WHI WHI JXO B2F 600V WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 RED N CN34 L3 T CN32 CN33 WHI BLK 706 707 707 703 711 712 713 718 719 717 709 721 TD1 TD2 ...

Page 334: ...T COMP2 COMP1 JXO 6B COMP3 1 600V 75A 22m m 2 L1 L2 C Q C JX O 6 0 0 4 L3 N O LD ER 4 0mm 2 WHI WHI WHI BLU WHI BLU BLU WHI BLU 600V JXO B2F WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 L3 T CN32 CN33 RED N CN34 WHI BLK 706 707 707 707 703 712 711 713 717 718 719 709 721 TD1 TD2 TD3 TK1 T...

Page 335: ...RMINAL 6P 1 1 709 43152519 CONTACTOR MAGNETIC 1 1 1 1 1 710 43160583 TERMINAL 6P 1 1 1 1 1 711 43069524 SUPPORT SPACER 3 3 3 3 3 712 43182011 SPACER EDGE 10 10 10 10 10 713 4316V440 PC BOARD ASSY NOISE FILTER MCC 1608 1 1 1 1 1 714 4316V420 PC BOARD ASSY INTERFACE MCC 1606 1 1 1 1 1 715 4316V422 PC BOARD ASSY FAN IPDU MCC 1610 1 1 1 1 1 716 4316V441 PC BOARD ASSY COMP IPDU MCC 1596 2 2 2 3 3 717 4...

Page 336: ...335 SMMS i OUTDOOR UNIT MMY MAP0804HT8 Z ZG TR MMY MAP1004HT8 Z ZG TR MMY MAP1204HT8 Z ZG TR 035 002 064 065 001 037 053 036 058 003 060 055 052 004 061 007 009 077 068 059 011 ...

Page 337: ...A 016 018 018 016 SV3C 030 SV3E 018 016 SV2 016 018 041 028 023 022 017 057 026 027 SV5 056 043 015 014 069 025 019 043 013 070 008 027 026 007 009 042 033 010 040 066 066 067 072 045 046 078 066 078 050 046 SV4 047 051 078 044 048 078 ...

Page 338: ...43 056 018 033 026 008 007 018 083 075 075 083 007 026 018 083 074 043 023 057 018 021 041 042 013 018 084 081 086 015 014 040 028 083 074 083 073 008 043 LIQUID LINE VALVE PACKED GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT CHECK STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE CHECKED LOW PRESSURE SENSOR PLUG FUSIBLE SEPARATOR OIL HIGH PRESSURE SWITCH Symbol ...

Page 339: ...338 SMMS i OUTDOOR UNIT MMY MAP1404HT8 Z ZG TR MMY MAP1604HT8 Z ZG TR 035 002 001 064 065 011 054 039 053 038 058 005 052 055 062 059 063 006 007 009 068 077 ...

Page 340: ...019 3 013 012 015 017 023 022 024 040 016 018 016 018 029 047 049 078 078 046 051 016 018 016 020 016 018 042 016 018 016 021 066 2 078 047 049 041 047 044 078 072 016 020 049 046 031 051 047 078 046 050 078 050 046 078 050 046 078 079 078 032 010 066 066 SV3A SV3C SV3B SV3E SV3D SV3F SV2 SV6 SV41 SV42 SV43 056 057 ...

Page 341: ... 040 008 040 018 008 083 040 083 043 056 032 083 FAN MOTOR FAN VALVE 4WAY LIQUID LINE VALVE SERVICE GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE Symbol OIL HEADER HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH ACCUMULATOR LOW PRESSURE SENSOR HIGH PRESSURE SWITCH SEPARATOR OIL TANK LIQUID PLUG FUSIBLE CONDENSER RIGHT S...

Page 342: ...146712 VALVE 2WAY VPV 303DQ1 2 2 021 43146730 VALVE 2WAY VPV 603DQ2 1 1 1 1 1 022 4314N042 VALVE 4WAY STF 0740G 1 1 1 1 1 023 43146734 VALVE CHECK ZGV S55B A 1 1 1 1 1 024 43146742 VALVE CHECK ZGV S66B A 1 1 025 4314N043 VALVE PMV HAM BD28TF 1 2 2 2 3 3 026 4314N044 VALVE 2WAY FDF3A06 3 3 3 3 3 027 4314N047 COIL VALVE 2WAY FQ G593 3 3 3 3 3 028 43148241 SEPARATOR 5L 1 1 1 029 43148249 SEPARATOR 6L...

Page 343: ...ER SUPPORTER PIPE 9 52 12 7 2 2 2 068 43149324 RUBBER CUSHION 6 6 6 9 9 069 43147195 BONNET 1 2 IN 1 1 1 070 43047401 BONNET 3 8 IN 1 1 1 1 1 071 43194029 BONNET 5 8 IN 1 1 072 43148220 PLUG FUSIBLE 1 1 1 1 1 073 44246235 TUBE CAPILLARY BYPASS ID 0 8 1 1 1 1 1 074 44246236 TUBE CAPILLARY BYPASS ID 1 0 1 1 1 1 1 075 44246239 TUBE CAPILLARY ID 1 2 1 1 1 1 1 076 43019904 HOLDER SENSOR 9 9 9 12 12 077...

Page 344: ...N 2 3 4 1 SW06 L1 R CN32 L2 S CN31 CN33 L3 T WHI RED BLK 1 600V 75A 22m m 2 L 1 L 2 C Q C J X O 6 0 0 4 L 3 N O LD E R 4 0mm 2 BLU WHI BLU WHI WHI JXO B2F 600V WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 RED N CN34 L3 T CN32 CN33 WHI BLK 706 707 707 703 711 712 713 718 719 717 709 721 TD...

Page 345: ... L3 T COMP2 COMP1 JXO 6B COMP3 1 600V 75A 22m m 2 L1 L2 C Q C JX O 6 0 0 4 L3 N O LD ER 4 0mm 2 WHI WHI WHI BLU WHI BLU BLU WHI BLU 600V JXO B2F WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 L3 T CN32 CN33 RED N CN34 WHI BLK 706 707 707 707 703 712 711 713 717 718 719 709 721 TD1 TD2 TD3 T...

Page 346: ...3160621 TERMINAL 6P 1 1 709 43152519 CONTACTOR MAGNETIC 1 1 1 1 1 710 43160583 TERMINAL 6P 1 1 1 1 1 711 43069524 SUPPORT SPACER 3 3 3 3 3 712 43182011 SPACER EDGE 10 10 10 10 10 713 4316V440 PC BOARD ASSY NOISE FILTER MCC 1608 1 1 1 1 1 714 4316V420 PC BOARD ASSY INTERFACE MCC 1606 1 1 1 1 1 715 4316V422 PC BOARD ASSY FAN IPDU MCC 1610 1 1 1 1 1 716 4316V441 PC BOARD ASSY COMP IPDU MCC 1596 2 2 2...

Page 347: ...346 SMMS i OUTDOOR UNIT MMY MAP0804HT7 Z ZG MMY MAP1004HT7 Z ZG MMY MAP1204HT7 Z ZG 035 002 064 065 001 037 053 036 058 003 060 055 052 004 061 007 009 077 068 059 011 ...

Page 348: ...A 016 018 018 016 SV3C 030 SV3E 018 016 SV2 016 018 041 028 023 022 017 057 026 027 SV5 056 043 015 014 069 025 019 043 013 070 008 027 026 007 009 042 033 010 040 066 066 067 072 045 046 078 066 078 050 046 SV4 047 051 078 044 048 078 ...

Page 349: ...43 056 018 033 026 008 007 018 083 075 075 083 007 026 018 083 074 043 023 057 018 021 041 042 013 018 084 081 086 015 014 040 028 083 074 083 073 008 043 LIQUID LINE VALVE PACKED GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT CHECK STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE CHECKED LOW PRESSURE SENSOR PLUG FUSIBLE SEPARATOR OIL HIGH PRESSURE SWITCH Symbol ...

Page 350: ...349 SMMS i OUTDOOR UNIT MMY MAP1404HT7 Z ZG MMY MAP1604HT7 Z ZG 035 002 001 064 065 011 054 039 053 038 058 005 052 055 062 059 063 006 007 009 068 077 ...

Page 351: ...019 3 013 012 015 017 023 022 024 040 016 018 016 018 029 047 049 078 078 046 051 016 018 016 020 016 018 042 016 018 016 021 066 2 078 047 049 041 047 044 078 072 016 020 049 046 031 051 047 078 046 050 078 050 046 078 050 046 078 079 078 032 010 066 066 SV3A SV3C SV3B SV3E SV3D SV3F SV2 SV6 SV41 SV42 SV43 056 057 ...

Page 352: ... 040 008 040 018 008 083 040 083 043 056 032 083 FAN MOTOR FAN VALVE 4WAY LIQUID LINE VALVE SERVICE GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE Symbol OIL HEADER HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH ACCUMULATOR LOW PRESSURE SENSOR HIGH PRESSURE SWITCH SEPARATOR OIL TANK LIQUID PLUG FUSIBLE CONDENSER RIGHT S...

Page 353: ... 2 3 3 020 43146712 VALVE 2WAY VPV 303DQ1 2 2 021 43146730 VALVE 2WAY VPV 603DQ2 1 1 1 1 1 022 4314N042 VALVE 4WAY STF 0740G 1 1 1 1 1 023 43146734 VALVE CHECK ZGV S55B A 1 1 1 1 1 024 43146742 VALVE CHECK ZGV S66B A 1 1 025 4314N043 VALVE PMV HAM BD28TF 1 2 2 2 3 3 026 4314N044 VALVE 2WAY FDF3A06 3 3 3 3 3 027 4314N048 COIL SOLENOID FQ D640 60HZ 3 3 3 3 3 028 43148241 SEPARATOR 5L 1 1 1 029 43148...

Page 354: ...ND 4 4 4 5 5 067 43149323 RUBBER SUPPORTER PIPE 9 52 12 7 2 2 2 068 43149324 RUBBER CUSHION 6 6 6 9 9 069 43147195 BONNET 1 2 IN 1 1 1 070 43047401 BONNET 3 8 IN 1 1 1 1 1 071 43194029 BONNET 5 8 IN 1 1 072 43148220 PLUG FUSIBLE 1 1 1 1 1 073 44246235 TUBE CAPILLARY BYPASS ID 0 8 1 1 1 1 1 074 44246236 TUBE CAPILLARY BYPASS ID 1 0 1 1 1 1 1 075 44246239 TUBE CAPILLARY ID 1 2 1 1 1 1 1 076 43019904...

Page 355: ...3 4 1 SW06 L1 R CN32 L2 S CN31 CN33 L3 T WHI RED BLK 1 600V 75A 22m m 2 L 1 L 2 C Q C J X O 6 0 0 4 L 3 N O LD E R 4 0mm 2 BLU WHI BLU WHI WHI JXO B2F 600V WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 RED N CN34 L3 T CN32 CN33 WHI BLK 706 707 707 703 711 712 713 718 719 717 709 721 TD1 TD...

Page 356: ... T COMP2 COMP1 JXO 6B COMP3 1 600V 75A 22m m 2 L1 L2 C Q C JX O 6 0 0 4 L3 N O LD ER 4 0mm 2 WHI WHI WHI BLU WHI BLU BLU WHI BLU 600V JXO B2F WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 L3 T CN32 CN33 RED N CN34 WHI BLK 706 707 707 707 703 712 711 713 717 718 719 709 721 TD1 TD2 TD3 TK1 ...

Page 357: ... TERMINAL 6P 1 1 709 43152395 CONTACTOR MAGNETIC 1 1 1 1 1 710 43160583 TERMINAL 6P 1 1 1 1 1 711 43069524 SUPPORT SPACER 3 3 3 3 3 712 43182011 SPACER EDGE 10 10 10 10 10 713 4316V440 PC BOARD ASSY NOISE FILTER MCC 1608 1 1 1 1 1 714 4316V420 PC BOARD ASSY INTERFACE MCC 1606 1 1 1 1 1 715 4316V422 PC BOARD ASSY FAN IPDU MCC 1610 1 1 1 1 1 716 4316V441 PC BOARD ASSY COMP IPDU MCC 1596 2 2 2 3 3 71...

Page 358: ...357 SMMS i OUTDOOR UNIT MMY MAP0804T8 SG MMY MAP1004T8 SG MMY MAP1204T8 SG 035 002 064 065 001 037 053 036 058 003 060 055 052 004 061 007 009 077 068 059 011 ...

Page 359: ... SV3A 016 018 018 016 SV3C 030 SV3E 018 016 SV2 016 018 041 028 023 057 026 027 SV5 056 043 015 014 069 025 019 043 013 070 008 027 026 007 009 042 033 010 040 066 066 067 072 045 046 078 066 078 050 046 SV4 047 051 078 044 048 078 ...

Page 360: ...018 033 026 008 007 018 083 075 075 083 007 026 018 083 074 043 023 057 018 021 041 042 013 018 084 081 086 015 014 040 028 083 074 083 073 008 043 LIQUID LINE VALVE PACKED GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT CHECK STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE CHECKED LOW PRESSURE SENSOR PLUG FUSIBLE SEPARATOR OIL HIGH PRESSURE SWITCH Symbol CONDENS...

Page 361: ...360 SMMS i OUTDOOR UNIT MMY MAP1404T8 SG MMY MAP1604T8 SG 035 002 001 064 065 011 054 039 053 038 058 005 052 055 062 059 063 006 007 009 068 077 ...

Page 362: ...019 3 013 012 015 023 024 040 016 018 016 018 029 047 049 078 078 046 051 016 018 016 020 016 018 042 016 018 016 021 066 2 078 047 049 041 047 044 078 072 016 020 049 046 031 051 047 078 046 050 078 050 046 078 050 046 078 079 078 032 010 066 066 SV3A SV3C SV3B SV3E SV3D SV3F SV2 SV6 SV41 SV42 SV43 056 057 043 ...

Page 363: ...040 008 040 018 008 083 040 083 043 056 032 083 FAN MOTOR FAN LIQUID LINE VALVE SERVICE GAS LINE VALVE SERVICE OIL BALANCE LINE VALVE PACKED VALVE 2WAY CAPILLARY TUBE JOINT STRAINER SENSOR TEMPERATURE DISTRIBUTOR VALVE Symbol OIL HEADER HIGH PRESSURE SWITCH HIGH PRESSURE SWITCH ACCUMULATOR LOW PRESSURE SENSOR HIGH PRESSURE SWITCH SEPARATOR OIL TANK LIQUID PLUG FUSIBLE CONDENSER RIGHT SIDE CONDENSE...

Page 364: ...20 43146712 VALVE 2WAY VPV 303DQ1 2 2 021 43146730 VALVE 2WAY VPV 603DQ2 1 1 1 1 1 022 023 43146734 VALVE CHECK ZGV S55B A 1 1 1 1 1 024 43146742 VALVE CHECK ZGV S66B A 1 1 025 4314N043 VALVE PMV HAM BD28TF 1 2 2 2 3 3 026 4314N044 VALVE 2WAY FDF3A06 3 3 3 3 3 027 4314N047 COIL VALVE 2WAY FQ G593 3 3 3 3 3 028 43148241 SEPARATOR 5L 1 1 1 029 43148249 SEPARATOR 6L 1 1 030 43148247 TANK LIQUID 11L 1...

Page 365: ...49683 BAND 4 4 4 5 5 067 43149323 RUBBER SUPPORTER PIPE 9 52 12 7 2 2 2 068 43149324 RUBBER CUSHION 6 6 6 9 9 069 43147195 BONNET 1 2 IN 1 1 1 070 43047401 BONNET 3 8 IN 1 1 1 1 1 071 43194029 BONNET 5 8 IN 1 1 072 43148220 PLUG FUSIBLE 1 1 1 1 1 073 44246235 TUBE CAPILLARY BYPASS ID 0 8 1 1 1 1 1 074 44246236 TUBE CAPILLARY BYPASS ID 1 0 1 1 1 1 1 075 44246239 TUBE CAPILLARY ID 1 2 1 1 1 1 1 076 ...

Page 366: ... SW06 L1 R CN32 L2 S CN31 CN33 L3 T WHI RED BLK 1 600V 75A 22m m 2 L 1 L 2 C Q C J X O 6 0 0 4 L 3 N O LD E R 4 0mm 2 BLU WHI BLU WHI WHI JXO B2F 600V WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 RED N CN34 L3 T CN32 CN33 WHI BLK 706 707 707 703 711 712 713 718 719 717 709 721 TD1 TD2 TK1...

Page 367: ... COMP2 COMP1 JXO 6B COMP3 1 600V 75A 22m m 2 L1 L2 C Q C JX O 6 0 0 4 L3 N O LD ER 4 0mm 2 WHI WHI WHI BLU WHI BLU BLU WHI BLU 600V JXO B2F WHI WHI WHI CN12 WHI P15 L2 S L1 R CN11 RED L3 T CN13 BLK P17 GRY CN24 CN22 CN23 RED CN50 CN14 GRY L1 R L2 S CN41 RED L3 T CN42 WHI CN43 BLK L2 S L1 R CN31 L3 T CN32 CN33 RED N CN34 WHI BLK 706 707 707 707 703 712 711 713 717 718 719 709 721 TD1 TD2 TD3 TK1 TK...

Page 368: ...L 6P 1 1 709 43152519 CONTACTOR MAGNETIC 1 1 1 1 1 710 43160583 TERMINAL 6P 1 1 1 1 1 711 43069524 SUPPORT SPACER 3 3 3 3 3 712 43182011 SPACER EDGE 10 10 10 10 10 713 4316V440 PC BOARD ASSY NOISE FILTER MCC 1608 1 1 1 1 1 714 4316V420 PC BOARD ASSY INTERFACE MCC 1606 1 1 1 1 1 715 4316V422 PC BOARD ASSY FAN IPDU MCC 1610 1 1 1 1 1 716 4316V441 PC BOARD ASSY COMP IPDU MCC 1596 2 2 2 3 3 717 431530...

Page 369: ...air conditioners is 0 3kg m3 NOTE 1 If there are 2 or more refrigerating systems in a single refrigerating device the amounts of refrigerant should be as charged in each independent device For the amount of charge in this example The possible amount of leaked refrigerant gas in rooms A B and C is 10kg The possible amount of leaked refrigerant gas in rooms D E and F is 15kg NOTE 2 The standards for...

Page 370: ......

Reviews: