(1) Set the switches SW01/SW02/SW03 on the interface P.C. board of the outdoor unit to [2/1/4].
(2) When [F. d] is displayed in 7-segment display [A], keep pressing the switch SW04 for 2 seconds or more.
(3) When [ 63 ] is displayed in 7-segment display [B], the fan starts operation. (Max. mode operation)
(4) After that, by changing the setup number of the switches SW02 and SW03, 7-segment display [B] and the fan
mode are changed.
(Mode output pattern of the fan is as follows.)
[Clear]
This function is cleared by one of the following operations.
(1) When SW01 setting number was changed to other number.
(2) Press-switch SW05 was pressed for 2 seconds or more.
SW02 SW03
7-segment display [B]
Fan mode
1
4
[ 63 ]
63
2
[ 62 ]
62
3
[ 61 ]
61
4
[ 60 ]
60
5
[ 59 ]
59
6
[ 58 ]
58
7
[ 57 ]
57
8
[ 56 ]
56
9
[ 55 ]
55
10
[ 54 ]
54
11
[ 53 ]
53
12
[ 52 ]
52
13
[ 51 ]
51
14
[ 50 ]
50
15
[ 49 ]
49
16
[ 48 ]
48
1
5
[ 47 ]
47
2
[ 46 ]
46
3
[ 45 ]
45
4
[ 44 ]
44
5
[ 43 ]
43
6
[ 42 ]
42
7
[ 41 ]
41
8
[ 40 ]
40
9
[ 39 ]
39
10
[ 38 ]
38
11
[ 37 ]
37
12
[ 36 ]
36
13
[ 35 ]
35
14
[ 34 ]
34
15
[ 33 ]
33
16
[ 32 ]
32
SW02 SW03
7-segment display [B]
Fan mode
1
6
[ 31 ]
31
2
[ 30 ]
30
3
[ 29 ]
29
4
[ 28 ]
28
5
[ 27 ]
27
6
[ 26 ]
26
7
[ 25 ]
25
8
[ 24 ]
24
9
[ 23 ]
23
10
[ 22 ]
22
11
[ 21 ]
21
12
[ 20 ]
20
13
[ 19 ]
19
14
[ 18 ]
18
15
[ 17 ]
17
16
[ 16 ]
16
1
7
[ 15 ]
15
2
[ 14 ]
14
3
[ 13 ]
13
4
[ 12 ]
12
5
[ 11 ]
11
6
[ 10 ]
10
7
[ 9 ]
9
8
[ 8 ]
8
9
[ 7 ]
7
10
[ 6 ]
6
11
[ 5 ]
5
12
[ 4 ]
4
13
[ 3 ]
3
14
[ 2 ]
2
15
[ 1 ]
1
16
[ 0 ]
0
7-7-8. Fan Operation Check in Outdoor Unit
This function is provided to check the fan operation of the outdoor unit by using switches on the interface P.C. board
in the outdoor unit. The frequency of the fan speed can be controlled by setting of the switches. Use this function
to check the operation or abnormal sound in the fan system. And, use this function while the system is stopped.
NOTE)
Do not use this function during operation of the compressor. It may damage the compressor.
Two fans move synchronously in two fan model (MMY-MAP1606* to MAP2006*).
[Operation]
−
1
40
−
Summary of Contents for MMY-MAP0806FT7(J)P
Page 32: ... 31 1 2 Single port FS Unit RBM Y1123FE FE2 RBM Y1803FE FE2 ...
Page 33: ... 32 RBM Y2803FE FE2 ...
Page 302: ...MMY MAP0806FT8 J P E MAP1006FT8 J P E MMY MAP0806FT8 J P TR MAP1006FT8 J P TR 301 ...
Page 307: ... 306 MMY MAP1206FT8 J P E MAP1406FT8 J P E MMY MAP1206FT8 J P TR MAP1406FT8 J P TR ...