Check code
Location
of
detection
Description
System status
Check code
detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
H07
H07
–
I/F
Low oil level
protection
All stop
Operating compressor
detects continuous state of
low oil level for about 2 hours.
<All outdoor units in
corresponding line to be
checked>
• Check balance pipe
service valve to confirm full
opening.
• Check connection and
installation of TK1,
TK2, TK4, and TK5
sensors.
• Check resistance
characteristics of TK1,
TK2, TK4, and TK5
sensors.
• Check for gas or oil leak in
same line.
• Check for refrigerant
problem inside
compressor casing.
• Check SV3A, SV3B,
SV3C, SV3D valves for
trouble
.
• Check oil return circuit of
oil separator for clogging.
• Check oil equalizing circuit
for clogging.
H08
H08
01: TK1 sensor trouble
0
2
: TK
2
sensor trouble
0
4
: TK
4
sensor trouble
05: TK5 sensor trouble
I/F
Trouble
in
temperature
sensor for oil
level detection
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK1
sensor connector.
• Check resistance
characteristics of TK1
sensor.
• Check for
trouble
in outdoor
P.
C. board (I/F).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK2
sensor connector.
• Check resistance
characteristics of TK2
sensor.
• Check for
trouble
in outdoor
P.
C. board (I/F).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK4
sensor connector.
• Check resistance
characteristics of TK4
sensor.
• Check for
trouble
in outdoor
P.
C. board (I/F).
All stop
Sensor resistance is infinity
or zero (open/short circuit).
• Check connection of TK5
sensor connector.
• Check resistance
characteristics of TK5
sensor.
• Check for
trouble
in outdoor
P.
C. board (I/F).
H15
H15
–
I/F
TD2 sensor
miswiring
(incomplete
insertion)
All stop
Discharge temperature of
(TD2) does not increase
despite compressor 2 being
in operation.
• Check installation of TD2
sensor.
• Check connection of TD2
sensor connector and
wiring.
• Check resistance
characteristics of TD2
sensor.
• Check for
trouble
in outdoor
P.
C. board (I/F).
−
16
9
−
Summary of Contents for MMY-MAP0806FT7(J)P
Page 32: ... 31 1 2 Single port FS Unit RBM Y1123FE FE2 RBM Y1803FE FE2 ...
Page 33: ... 32 RBM Y2803FE FE2 ...
Page 302: ...MMY MAP0806FT8 J P E MAP1006FT8 J P E MMY MAP0806FT8 J P TR MAP1006FT8 J P TR 301 ...
Page 307: ... 306 MMY MAP1206FT8 J P E MAP1406FT8 J P E MMY MAP1206FT8 J P TR MAP1406FT8 J P TR ...