[E09]
Ye
s
Ye
s
No
No
Ye
s
No
No
No
Ye
s
No
Ye
s
Ye
s
[E15]
No
Ye
s
[E10]
[E12]
Sub-code: 01: Communication between indoor and outdoor 02: Communication between outdoor units
Ye
s
No
es
ua
C
ed
oc
kc
eh
C
Check code name
es
ua
C
ed
oc
kc
eh
C
Check code name
es
ua
C
ed
oc
kc
eh
C
Check code name
es
ua
C
ed
oc
kc
eh
C
Check code name
Duplicated header remote controller
No corresponding indoor unit during automatic address
Setup of header remote controller is duplicated.
Communication
trouble
between
indoor MCUs.
Automatic address start
trouble
Indoor P
.C. board
trouble
.
Are two remote
controllers set up as two
header remote
controllers?
Is communication line between indoor
and outdoor
normal?
Is connection of
CN40 connector on indoor P
.C. board
correct?
Is
connection of CN01
connector on I/F P
.C. board
of header outdoor unit
correct?
Is there any connection
trouble
of power wire?
Did a power failure
occur?
Is there no noise source?
Set up address again after resetting power supply
.
Is there any trouble on
power line?
Are U1, U2, U3, and
U4 connectors connected?
Set up one controller as the header and the other follower
.
(Remote controller address connector)
Correct communication line.
Correct connection of connector
.
Correct connection of connector
.
Correct power wire.
Set up address again after resetting power supply
.
Eliminate noise.
Check remote controller P
.C. board.
Failure
Replace
Check power voltage. Improve the line condition. Eliminate noise, etc.
Check indoor control P
.C. board.
Failure
Replace
Disconnect connector connection of U1, U2, U3, and U4.
Turn on power of outdoor unit again.
1.
Starting automatic addressing of indoor units during automatic addressing in another refrigerant line. (Sub-code: 01)
2.
Starting automatic addressing of outdoor units during automatic addressing of indoor units (Sub-code: 02)
1.
Communication line connection
trouble
between
indoor and outdoor
2.
Indoor power system
trouble
3.
Noise from surrounding devices
4.
Power failure
5.
Indoor P
.C. board
trouble
Set
up
addr
ess
agai
n.
(R
efer
to
“7
-4-
3.
Addr
ess
Set
up
Pr
ocedur
e”.
)
−
18
2
−
Summary of Contents for MMY-MAP0806FT7(J)P
Page 32: ... 31 1 2 Single port FS Unit RBM Y1123FE FE2 RBM Y1803FE FE2 ...
Page 33: ... 32 RBM Y2803FE FE2 ...
Page 302: ...MMY MAP0806FT8 J P E MAP1006FT8 J P E MMY MAP0806FT8 J P TR MAP1006FT8 J P TR 301 ...
Page 307: ... 306 MMY MAP1206FT8 J P E MAP1406FT8 J P E MMY MAP1206FT8 J P TR MAP1406FT8 J P TR ...