B
4
Indoor BUS communication signal
receiving status
Upon receiving signal: [... ... 1], Other times: [... ... ...]
B
5
Indoor check code
No check code: [– – –]
B
6
Indoor HP capacity
0. 2, 0. 5, 0. 8, ... 1, 1. 2, 1. 7, ... 2, 2. 5,
...3, 3. 2, ...4, ...5, ...6, ...8, 1 0, 1 6, 2 0
8
Indoor PMV opening data
Displayed in decimal format
9
1~4
1~16
Indoor TA / TRA opening data
Displayed in decimal format
11~14 Indoor TSA opening data
Displayed in decimal format
10
Displayed in decimal format
1~4 Indoor TF / TFA opening data
11~14 Indoor TOA opening data
Displayed in decimal format
B
11
Indoor TCJ opening data
Displayed in decimal format
B
12
Displayed in decimal format
B
13
1~4 Indoor TC1 opening data
Indoor TC2 opening data
Displayed in decimal format
B
7
Indoor request command
(S code, operation mode)
[ #. ...
∗
]
# represents mode:
COOL: [C. ...
∗
], HEAT: [H. ...
∗
]
FAN: [F. ...
∗
], OFF: [S. ...
∗
]
∗
represents S code: [#. ... 0] to [#. ... F]
SW01
SW02
SW03
Display detail
SW02
1~16
SW03
1
11
2
12
3
13
Indoor address
SW02 setting number
SW02 setting 16
SW02 setting 32
7-segment display section A
[01]~[16]
[17]~[32]
[33]~[48]
(5) Display of Indoor Unit Information (Displayed on Header Unit Only)
Note:
Indoor address No. is selected by setting SW02 and SW03 and displayed on 7-segment display, section A.
(6) Display of Outdoor EEPROM Writing
Check
Code (Displayed on Header Unit Only)
* The latest code written in the EEPROM of each outdoor unit is displayed.
(This function is used to check the code after the resetting of the power supply.)
To display the code, push SW04 and hold for at least 5 seconds after setting SW01 to 03 as shown in the
table below.
• 7-Segment Display
SW01
SW02
SW03
Indoor address
7-segment display section A
1
E. 1.
∗∗∗
Latest
check
code of header unit (U1)
1
2
16
E. 2.
∗∗∗
Latest
check
code of follower unit No. 1 (U2)
3
E. 3.
∗∗∗
Latest
check
code of follower unit No. 2 (U3)
Section A
Section B
D600 D601
D602 D603 D604
Set SW01/SW02/SW03 to [1/1/16] and push SW04 and hold for at least 5 seconds. The latest code of the
header unit (U1) will be displayed.
If the setting of SW02 is changed, the latest code of a follow unit (U2-U3) will be displayed.
4
14
SW02 setting 48
[49]~[64]
−
21
6
−
B
B
B
B
B