(3) Change the connection of wiring between Comp-IPDU and Fan-IPDU, as shown in the below.
Outdoor Unit (8, 10, 12, 14HP)
Model: MMY-MAP0806FT*, MAP1006FT*, MAP1206FT*, MAP1406FT*
1.When compressor No.1 (front left) is faulty
:
No change the connection of wiring
2.When compressor No.2 (front right) is faulty
:
Change the connection of wiring between Comp-IPDU and Fan-IPDU as shown in the below.
CN21
CN23
CN21
CN23
CN21
CN23
CN21
CN23
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU2
・
Change to CN21 of Comp-IPDU1 from CN21 of Comp-IPDU2
・
Change to CN23 of Comp-IPDU2 from CN23 of Comp-IPDU2
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU2
・
Change to CN21 of Comp-IPDU1 from CN21 of Comp-IPDU2
・
Change to CN23 of Comp-IPDU2 from CN23 of Comp-IPDU2
Ex. MMY-MAP0806FT*, MAP1006FT*
Ex. MMY- MAP1206FT*, MAP1406FT*