<Outline>
This product allows outdoor unit backup operation setting to be performed either at the header unit or a follower
unit. If any of the fault modes specified below occurs to one of the outdoor units in a multi-outdoor unit system,
proceed with outdoor unit backup operation.
• A compressor failure (e.g. a layer short-circuit or a compressor failure in which no compressor is available to
back up the faulty compressor)
•
A failure of a pressure sensor (PD or PS) or a temperature sensor (TD1, TD2, TS1, TS2, TE1, TE2,
TK1, TK2, TK4, TK5 or TL1)
Note:
Keep the number of backed-up outdoor units to one in the system (single refrigerant line).
<Work procedure>
(1) Turn off the power supply to all the indoor and outdoor units connected to the system.
[Setup of failed follower outdoor unit]
(2) Fully close the gas pipe service valve of the failed outdoor unit.
(3) Leave the service valves of the liquid and balance pipe fully open (to prevent refrigerant stagnation in the unit).
However, if there is a leakage from an outdoor PMV (unable to close), fully close the liquid pipe service valve.
(4) <In case of fault in compressor, electrical part, I/F P.C. board, or IPDU P.C. board>
From this point on, keep the power supply to the failed unit off.
<In case of fault in refrigerating circuit or related part (pressure sensor, temperature sensor, refrigerating cycle
part, or fan system part)>
Disconnect the connector [CN03] for outdoor-outdoor communication (BUS2) provided on the interface P.C.
board.
9-3. Outdoor Unit Backup Operation Setting
9-3-1. Follower outdoor unit backup operation setting
(failure of follower outdoor unit)
−
23
9
−
Setup of failed follower outdoor unit
(2)
Fully close discharge
gas
pipe and suction gas pipe
(3)
Leave service valves of liquid and balance pipes fully open.
(If there is leakage from outdoor PMV, fully close liquid pipe.)
(4)
In case of fault in refrigerating circuit
or related part, disconnect BUS2
communication connector [CN03] on
interface P.C. board.