24
3
−
(11)Turn on the power supply to all the units connected to the system other than the failed unit.
Determine what to do with the
power
supply to the failed unit in the following manner.
<In
case
of fault in compressor,
electrical
part, I/F P.C.
board,
or
IPDU P.C. board>
Leave the power supply
off.
<In case of fault in refrigerating circuit or related part (pressure sensor, temperature sensor, refrigerating cycle
part,
or fan system part)>
Turn on the power supply to protect
the
compressor (by
turning on
the
case
heater).
(When
the power supply to the
unit is turned on, [E19]
(
trouble
in the number of outdoor header units) will be
displayed
on the 7-segment display. However, this will not cause any problems.)
This is the end of header outdoor unit backup operation setting. Check the operation.