(5) Set the DIP switch (SW800) setting of the service board to match the switch setting from the original PCB.
-Set the DIP switch (SW800) depending on the position of the IPDU within the electrical box, as shown in the
following diagram.
(6)
Apply the Silicone Thermal Grease to the semiconductors (DB01, DB02, DB03, Q201) on the service PC board,
and align the positions of the heat sink holes to mount the Compressor IPDU on the outdoor control unit. And fix
the Compressor IPDU to the outdoor control unit by the spacers
(
③
).
(7) Screw the Compressor IPDU to the heat sink by the eight screws that were removed in step (3). If the screws are
loose, the effect component will generate heat, and cause it to breakdown. Do not use an electric driver or an air
driver. As it can cause component damage. The torque of the screws for DB01, DB02, DB03 and Q201 is
“1.2Nm”.
(8) Re-connect the connectors and Faston and screw terminals(
①
).
Be sure that all the connectors and the screw terminals
are connected correctly and securely inserted.
Note:
①
When connecting the lead wire, don't touch PCB part of the T202
transformer.
②
When connecting the white lead wire which is connected to CN02,
be absolutely sure that it is passed through the T611 transformer
and then connected.
③
When connecting the black lead wire which is connected to CN03,
be absolutely sure that it is passed through the T612 transformer
and then connected.
④
When connecting the red lead wire which is connected to CN203,
be absolutely sure that it is passed through the T201 transformer
and then connected.
⑤
When connecting the white lead wire which is connected to CN202,
be absolutely sure that it is passed through the T202 transformer
and then connected.
(If it is not passed through the transformer, it will not be possible for
the input current level to be measured correctly, and a compressor
failure may result.)
(9) If the components on the PCB were bent during this procedure,
straighten them so they do not touch other parts.
(10) Install the cover, then turn on the supply. Check the operation.
Compressor IPDU
【
Left Side
】
For Compressor: 1
DIP switch (SW800) setting
:
Compressor IPDU
【
Right Side
】
For Compressor: 2
DIP switch (SW800) setting
:
ON
Ex. MMY-MAP2006FT8P
ON
OFF
OFF ON
1
2
1
2
ON
Uniformly apply the Silicone Thermal Grease to the heat dissipating surfaces of the IPM (Q201)
and rectifier (DB01, DB02, DB03).
Note: Do this work carefully since allowing any dirt, scratches, etc. to be left on the PC board
mounting areas of the semiconductors will impair the heat dissipation effect and may result
in a failure.
Silicone Thermal Grease use one of the following
・
Momentive Performance Materials ‘’TIG1000’’
・
Dow Corning Toray ‘’SC102’’
・
Mizutani Electric Ind ‘’HSC1000’’
・
Shin-Etsu Chemical ‘’G-746
’’ or ‘’G-747’’
T612
T611
DB03
Q201
DB02
DB01
T201
T202
PCB part of the T202
transformer
Summary of Contents for MMY-MAP0806FT7(J)P
Page 32: ... 31 1 2 Single port FS Unit RBM Y1123FE FE2 RBM Y1803FE FE2 ...
Page 33: ... 32 RBM Y2803FE FE2 ...
Page 302: ...MMY MAP0806FT8 J P E MAP1006FT8 J P E MMY MAP0806FT8 J P TR MAP1006FT8 J P TR 301 ...
Page 307: ... 306 MMY MAP1206FT8 J P E MAP1406FT8 J P E MMY MAP1206FT8 J P TR MAP1406FT8 J P TR ...