(2) Indoor unit setup method for priority indoor unit mode
The setting can be changed only when the system is at rest. (Be sure to turn
off the system prior to this operation.)
1
Push the
+
+
buttons simultaneously and hold for at
least 4 seconds. The display window will start flashing in a little
while.
Verify that the displayed CODE No. is 10.
ë If the displayed CODE No. is not 10, press the
button to erase the
display and repeat the procedure from the beginning.
(Note that the system does not respond to remote controller operation
for about 1 minute after the
button is pushed.)
(In the case of group control, the indoor unit No. displayed first indicates
the header unit.)
2
Each time the
button is pushed, one of the indoor
unit Nos. under group control is displayed in turn. Select
the indoor unit whose setting is to be changed.
The fan and flap of the selected indoor unit then come on, so
that the position of this unit can be confirmed.
3
Use the
button to select the CODE No. 04.
4
Use the
button to select the SET DATA 0001.
Priority set 0001
No priority set 0000
5
Push the
button.
The setup is finished when the display changes from flashing to steady.
6
Upon finishing the setup, push the
button. (This
finalizes the setting.)
When the
button is pushed, the display goes blank, and the
system returns to normal off state.
(Note that the system does not respond to remote controller
operation for about 1 minute after the
button is pushed.)
NOTE
Priority can be given to only one indoor unit. If more than one indoor unit is accidentally set to priority, a check code
(L5 or L6: Duplicated indoor unit priority setting) will be displayed.
All units displaying L5 have been set to 0001 (priority). Keep the unit to which priority should be given as it is, and
change the value back to 0000 (no priority) for all the rest.
n
o
it
p
ir
c
s
e
D
Check code
Duplicated indoor unit priority setting (The unit is set to 0001.)
Duplicated indoor unit priority setting (The unit is set to 0000.)
SET
TIME
TIMER SET
TEST
FILTER
RESET
TEMP.
CL
FAN
SAVE
SWING/FIX
VENT
MODE
ON / OFF
UNIT LOUVER
5
4
1
2
6
3
UNIT LOUVER
−
8
4
−
Summary of Contents for MMY-MAP0806FT7(J)P
Page 32: ... 31 1 2 Single port FS Unit RBM Y1123FE FE2 RBM Y1803FE FE2 ...
Page 33: ... 32 RBM Y2803FE FE2 ...
Page 302: ...MMY MAP0806FT8 J P E MAP1006FT8 J P E MMY MAP0806FT8 J P TR MAP1006FT8 J P TR 301 ...
Page 307: ... 306 MMY MAP1206FT8 J P E MAP1406FT8 J P E MMY MAP1206FT8 J P TR MAP1406FT8 J P TR ...