Miswiring example
Remote
Header unit
Figure controller
7-segment
Miswiring example
status
display
Header unit
Header unit
Header unit
Header unit
Line 1
Line 2
Uv
Uc
Uv
Uc
Uv
Uv
U1 U2 U5 U6
U1 U2 U5 U6
U1 U2
U1 U2
Fig 1 No response
E19, 02
U1 U2
U1 U2
U1 U2
U1 U2
Uv
Uv
Uv
Uv
Header unit
Header unit
Uh
Uv
U3 U4
U1 U2
Fig 2
E11
L08
Wiring forgotten
U1 U2
A B
U1 U2
U1 U2
Uv
Uv
Uv
Figure
Status
Miswiring example
The number of connected
outdoor units is few.
Header unit
Follower unit
Header unit
Follower unit
Uv
Uc
Uh
Uv
Uh
Uc
U1 U2 U5 U6
U3 U4
U1 U2 U3 U4
U5 U6
Fig 3
U1 U2
U1 U2
U1 U2
U1 U2
Uv
Uv
Uv
Uv
The number of connected
indoor units is few.
Header unit
Header unit
Uv
Uv
U1 U2
U1 U2
Fig 4
Wiring forgotten
U1 U2
A B
U1 U2
U1 U2
Uv
Uv
Uv
• Follower unit is incorrectly set to
header unit.
• Indoor/outdoor communication line is
miswired to header unit of other system.
• Indoor/outdoor communication line is
miswired to Uh (U3/U4).
• Indoor/outdoor communication line is
not connected.
• Outdoor communication line is miswired to Uh (U3/U4).
• Indoor/outdoor communication line is
miswired to remote controller terminal (A/B).
• There is an indoor unit not connected to
the indoor/outdoor communication line.
- 139 -