Ye
s
Ye
s
Ye
s
No
No
Ye
s
No
No
No
Ye
s
No
Ye
s
[E23]
Check code
Check code name
Cause
Communication signal sending
trouble between outdoor units
1.
Inter-unit wire connection trouble between outdoor units
2.
Communication connector connection trouble
between outdoor units, I/F P
.C. board trouble
3.
End terminal resistance setup trouble between
outdoor units
Is connection
of CN02 connector on
outdoor I/F P
.C. board
normal?
Is main power of
outdoor unit turned
on?
Did power failure
occur?
Is there any noise
source?
Is the
terminator resistor between
outdoor units turned on?
(SW100 Bit 2)
Is
communication
line between outdoor
units connected
correctly?
Correct communication line.
Correct wiring or connector
.
T
urn on main power of
outdoor unit.
Turn the
terminator resistor
to ON.
Clear check code.
Eliminate noise
Replace outdoor I/F P
.C. board.
Do not set up outdoor addresses manually
.
[E25]
During setup of outdoor
Yes
Clear the trouble, and then start operation. (*1)
unit backup?
No
Is main power of
No
follower unit turned on?
Turn on the main power supply
.
Yes
Is
communication line between outdoor
No
Correct connection of
units connected
communication line.
normally?
Yes
(*1) How to clear the trouble
Check I/F P
.C. board.
Set SW01/SW02/SW03 on I/F P
.C. board of header unit to 2/16/1, and
push SW04 for 5 seconds or more. (7-segment display: [Er
.] [CL])
Check code
Check code name
Cause
Trouble has occurred on a follower outdoor unit.
[E28]
Follower outdoor unit trouble
Sub-code: Detected outdoor unit No.
A trouble occurred on a follower unit. See the check code on the 7-segment display on I/F P
.C. board of the follower
unit, and then check it according to diagnose procedure for the check code. (How to specify the follower outdoor unit in which trouble occurred) Push SW04 for 1 second or more under condition that [E28] is displayed on the 7-segment display of the header unit. The fan of the outdoor unit which stopped due to occurrence of trouble starts rotating. Push SW05 to stop the fan.
[E26]
Sub-code:
Address of the outdoor unit receiving signal abnormally
Check code
Check code name
Cause
Check code
Check code name
Cause
Duplicated follower outdoor
address setup
Addresses are duplicated by manual setup of outdoor
address
Decrease of connected outdoor
units
1.
Outdoor unit backup setup
2.
Outdoor power trouble
3.
Communication line connection trouble between
outdoor units
4.
Communication connector connection trouble
5. Outdoor
I/F
P
.C.
board
trouble
- 201 -