Ye
s
No
[P11]
Cause
Check code
Is correct
installation state
of outdoor unit?
Correct installation state
of outdoor unit.
Correct installed position of
sensors
Check code name
Outdoor heat exchanger freeze
trouble
1. Refrigerant shortage
2. TE1, TE2, TE3 sensor trouble
3. Pd, Ps sensor trouble
4. TS1 sensor trouble
5. 4-way valve trouble
6. PMV1 / PMV2 / PMV3 trouble
7. Outdoor I/F P.C. board trouble
8. Short circuit from outlet air to inlet air
Ye
s
No
Is outside air
temperature within the
operating range?
(A)
Operate within the operating
range.
Ye
s
No
Outdoor I/F P.C. board
TE1 sensor. CN381 White
TE2 sensor. CN381 White
TE3 sensor. CN384 Blue
TS1 sensor. CN378 White
Are
installed position
of TE1, TE2, TE3 and TS1
sensors correct?
Ye
s
No
Outdoor I/F P.C. board
PMV1, CN300 White
PMV2, CN301 White
PMV3, CN302 Blue
Outdoor I/F P.C. board
Pd sensor. CN501
Ps sensor. CN500
Are
connection of
PMV1, PMV2, and PMV3
connectors
correct?
Correct connection of connectors.
Ye
s
No
Are
connection of
TE1, TE2, TE3 and TS1
sensor connectors
correct?
Replace sensors.
Ye
s
No
Are
resistance
characteristics of TE1, TE2, TE3
and TS1 sensors
normal?
Replace 4 way valve.
Correct connection of connectors.
Ye
s
No
Does 4-way
valve normally
operate?
Replace PMVs.
Ye
s
No
Does PMV1,
PMV2, and PMV3
normally operate?
(A)
Correct connection of connectors.
Ye
s
No
Are
connection of
Pd sensor and Ps sensor
connectors
correct?
Replace PMVs.
Replaced outdoor I/F
P.C. board
Ye
s
No
Are
output voltage
characteristics of Pd sensor
and Ps sensor
normal?
- 219 -