11-3. Check Procedure to Search Cause of Compressor Oil Shortage
Is the wiring
of the TK1 sensor and TK2
sensor of the unit with the replaced
compressor correct?
Are the
characteristics of the
TK1 and TK2 sensors of the unit
that has replaced compressor
correct?
(To next page)
No
No
Correct the miswiring or connection.
TK1: CN502 TK2: CN380
Yes
Yes
With the compressor(s) disconnected,
check the oil circuit in accordance
with the procedure described below.
Replace the troubled sensor.
- 267 -