No.
Part
Work procedure
Remarks
Reactor
assembly
(
1
4A
-24HP
)
WARNING
Wear a pair of gloves.
Otherwise, you will risk an injury involving a replacement
part or some other object.
1. Detachment
1) Stop the air conditioner operation, and turn off the
circuit breaker.
2) Following to works 1) to 5) in 1 of No.1 Cabinet,
remove the cabinets.
3) Remove the screws for the fixed plate of reactor box.
(M5 × 10, 4 pcs)
4) Remove the screws for the reactor box, and draw the
reactor box toward you.
(M5 × 10, 2 pcs, Rear side is hooked)
5) Remove the reactor cover.
(M4 × 8, 6 pcs)
6) Remove the reactor.
(M4 × 8, 4 pcs)
5
2. Attachment
Carry out installation by following reverse procedure in the
detachment 1) to 6).
Hook the hooks on each cabinet securely into the square
holes in the supports.
[When attaching two reactors for 22, 24 HP]
Be sure to wire the round type terminal leads to the
specified reactors.
Reactor 1: Wire the round type terminal lead without the
black tape to the reactor 1.
Reactor 2: Wire the round type terminal lead with the black
tape to the reactor 2.
5) Screws for
reactor cover
6) Screw for reactor box
4) Screw for reactor box
3) Fixed plate of reactor box
- 279 -