<RBC-AMT
*
>
1
Push the +
+
buttons simultaneously and hold for at
least 4 seconds. The display window will start flashing in a
little while.
Verify that the displayed CODE No. is 10.
• If the displayed CODE No. is not 10, press the
button to erase the
display and repeat the procedure from the beginning.
(Note that the system does not respond to remote controller operation
for about 1 minute after the
button is pushed.)
(In the case of group control, the indoor unit No. displayed first
indicates the header unit.)
VHW
WLP H
WLP HU#VHW
WHVW
I LOWHU
UHVHW
WHP S1
F O
I DQ
VDYH
VZ LQJ 2I L[
YHQW
P RGH
RQ#2#RI I
XQLW##ORXYHU
8
7
4
5
9
6
2
Each time the
UNIT LOUVER
button is pushed, one of the
indoor unit Nos. under group control is displayed in
turn. Select the indoor unit whose setting is to be
changed.
The fan and flap of the selected indoor unit then come on, so
that the position of this unit can be confirmed.
3
Use the
button to select the CODE No. 04.
4
Use the
button to select the SET DATA 0001.
Priority set 0001 No priority set 0000
Description
Check code
Duplicated indoor unit priority setting (The unit is set to 0001.)
Duplicated indoor unit priority setting (The unit is set to 0000.)
5
Push the
button.
The setup is finished when the display changes from flashing to steady.
6
Upon finishing the setup, push the
button. (This
finalizes the setting.)
When the
button is pushed, the display goes blank, and the
system returns to normal off state.
(Note that the system does not respond to remote controller
operation for about 1 minute after the
button is pushed.)
NOTE
Priority can be given to only one indoor unit. If more than one indoor unit is accidentally set to priority, an
check code
(L5 or L6: Duplicated indoor unit priority setting) will be displayed.
All units displaying L5 have been set to 0001 (priority). Keep the unit to which priority should be given as it
is, and change the value back to 0000 (no priority) for all the rest.