4
P9 ASD Quick Start Guide
Installation Precautions
Location and Ambient Requirements
•
The TIC ASD is intended for permanent installations only.
•
Installation should conform to the
National Electrical Code — Article 110
(NEC) (
Requirements
For Electrical Installations
), all regulations of the
Occupational Safety and Health
Administration
, and any other applicable national, regional, or industry codes and standards.
Note:
For ALL references to the National Electrical Code (NEC), see the latest release of
the National Electrical Code.
•
Select a mounting location that is easily accessible, has adequate personnel working space, and
adequate illumination for adjustment, inspection, and maintenance of the equipment (refer to the
NEC Article 110-13).
•
DO NOT
mount the ASD in a location that would produce catastrophic results if it were to become
dislodged from its mounting location (equipment damage or injury).
•
DO NOT
mount the ASD in a location that would allow it to be exposed to flammable chemicals or
gases, water, solvents, or other fluids.
•
Avoid installation in areas where vibration, heat, humidity, dust, fibers, metal particles, explosive/
corrosive mists or gases, or sources of electrical noise are present.
•
The installation location shall not be exposed to direct sunlight.
•
Allow proper clearance spaces for installation. Do not obstruct the ventilation openings. Refer to
the section titled
Installation and Connections on pg. 10
for further information on ventilation
requirements.
•
The ambient operating temperature range of the P9 ASD is 14° to 104° F (-10° to 40° C).
Mounting Requirements
•
Only
Qualified Personnel
should install this equipment.
•
Install the unit in a secure and upright position in a well-ventilated area.
•
As a minimum, the installation of the equipment should conform to the
NEC — Article 110
(NEC), OSHA, as well as any other applicable national, regional, or industry codes and standards.
•
Installation practices should conform to the latest revision of NFPA 70E Electrical Safety
Requirements for Employee Workplaces.
•
It is the responsibility of the ASD installer/maintenance personnel to ensure that the unit is installed
into an enclosure that will protect personnel against electric shock.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www .ctiautomation.net - Email: info@ctiautomation.net