P9 ASD Quick Start Guide
67
Figure 31. Complete the VLP Setup.
Figure 32. Run the Motor/Pump in the Direct Mode.
VLP Setup Wizard
Back
Press [STOP]
Virtual Linear Pump Setup
Is Now Complete
Next
Exit
16. Press the
Stop
key to complete
the
VLP
setup.
17. Click
Exit
to save settings
(Exit available at zero Hz).
18. From the
Frequency
Command
screen press
ESC
,
scroll to the
VLP Control
field,
and select
Direct Mode
if using
no feedback (if using feedback
go to
19. While in the
Hand
mode, and
from the
Frequency Command
screen, press
Run
.
20. During operation, adjust
parameters
F500
and
F501
to
stabilize
VLP
operation if
unstable.
Press
ESC