P9 ASD Quick Start Guide
15
Figure 4. The
Grounding Capacitor
Switch
is used on typeforms
230-volt
0.75 HP to 10 HP and the 25 and 30
HP/
460-volt
1.0 HP to 25 HP.
The value may be set to
Maximum
(default setting) or to
Zero
by pushing or
pulling the switch actuator, respectively.
Figure 5. The
Grounding Capacitor
Switch
is used on typeforms
230-volt
15 HP and 20 HP and the 40 HP to 60
HP/
460-volt
30 HP to 100 HP.
The value may be set to
Large
(default setting) or
Small
by pushing
or pulling the switch actuator,
respectively.
Figure 6. The
Grounding Capacitor Bar
is
used on typeforms
230-volt
75 HP to 125 HP/
460-volt
125 HP and the 150 HP.
The value may be set to
Large
or
Small
(default setting) by connecting or
disconnecting the switching bar, respectively.
Figure 7. The
Grounding Capacitor Screw
is
used on typeforms
460-volt
200 HP and
above.
The value may be set to
Large
or
Small
(default setting) by placing the screw in the
A
position or by placing the screw in the
B
position, respectively.