P9 ASD Quick Start Guide
19
terminal may be used to regulate the speed or torque of a motor by setting a limit. The gain and bias of
this terminal may be adjusted for application-specific suitability (See F216 – F221).
V/I
— The V/I terminal has the dual function of being able to receive an input voltage or current. The
function as a voltage input is to receive a 0 – 10 VDC input signal. The function as a current input is to
receive a 0 – 20 mA input signal. Using either input type, the function is to control the 0.0 – Maximum
Frequency output or the 0.0 to 250% torque output of the ASD. This is an isolated input terminal. This
terminal may be programmed to control the speed or torque of the motor and cannot process both input
types simultaneously.
must be set to V or I to receive a voltage or current, respectively (See
). Terminal scaling is accomplished via F201 – F206. The gain and bias of this
terminal may be adjusted for application-specific suitability (See F470 – F471).
SU+
—
Control Power Supply Backup
input terminal. This terminal accepts the user-supplied
24 VDC backup power to the control circuits (only). Backup power is used in the event of an open
MCCB or during a momentary loss of the 3-phase input power and cannot be supplied by the 3-phase
input power. Parameter settings, real-time clock information, and trip history information are retained
with the use of the
SU+
backup power.
The P9 ASD is also equipped with a separate battery for this function. The battery backup has the added
feature of allowing for the transfer of the EOI to another ASD while retaining the programming. See the
section titled
for more information on the battery backup features.
P24
— +24 VDC at 200 mA power supply for customer use.
PP
— The function of output
PP
is to provide a 10 VDC/10 mADC (max.) output that may be divided
using a potentiometer. The tapped voltage is applied to the
RR
input to provide manual control of the
RR
programmed function.
O1A/B
(OUT1A/B)
— The default function assigned to this terminal is
External Device 1
. The
function as
External Device 1
is to activate or deactivate an auxiliary motor once the VLP level has
remained within the V
LP Maximum Zone
or the
VLP Minimum Zone
, respectively, for the time
setting of
F480
. The
OUT1
terminal is rated at 2 A/120 VAC and 2 A/30 VDC. This terminal may be
set to any of the functions listed in the
P9 ASD Installation and Operation Manual
(See F130).
O2A/B
(OUT2A/B)
— The default function assigned to this terminal is
External Device 2
. The
function as
External Device 2
, in conjunction with External Device 1, is to activate or deactivate an
auxiliary motor once the VLP level has remained within the V
LP Maximum Zone
or the
VLP
Minimum Zone
, respectively, for the time setting of
F480
. The
OUT2
terminal is rated at 2 A/120
VAC and 2 A/30 VDC. This terminal may be set to any of the functions listed in the
P9 ASD
Installation and Operation Manual
(See F131).
FP
— The default function of this output terminal is to output a series of pulses at a rate that is a
function of the ASD output frequency (50 mA max. at 1.0 kHz to 43.3 kHz). As the output frequency of
the ASD goes up so does the
FP
output pulse rate. This terminal may be programmed to provide an
output pulse rate that is proportional to the magnitude of the user-selected item from the
P9 ASD
Installation and Operation Manual
. For further information on this terminal, see parameter
F676
.
AM
—
This output terminal produces an output current that is proportional to the output frequency of
the ASD or of the magnitude of the function assigned to this terminal. The available assignments for
this output terminal are listed in the
P9 ASD Installation and Operation Manual
. For further
information on this terminal, see
F670
.
FM
— This output terminal produces an output current or voltage that is proportional to the output
frequency of the ASD or of the magnitude of the function assigned to this terminal. The available
assignments for this output terminal are listed in the
P9 ASD Installation and Operation Manual
. For
further information on this terminal, see
F005
. The Voltage/Current output selection is performed at
F681
.
FLA
— One of two normally open contacts that, under user-defined conditions, connect to
FLC
.
FLB
— One of two normally closed contacts that, under user-defined conditions, connect to
FLC
.
V/I
U+
4
P
1A/B
xternal Device
2A/B
xternal Device
P
M
M
LA
LB
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www .ctiautomation.net - Email: info@ctiautomation.net