P9 ASD Quick Start Guide
31
Volts per Hertz Setting
(F015)
This function establishes the relationship between the output frequency and the output voltage of the
ASD.
Settings:
Constant Torque
Voltage Decrease Curve
Automatic Torque Boost
Sensorless Vector Control (Speed)
Sensorless Vector Control (Speed/Torque Switching)
V/f 5-Point Curve (Go to
F190
to Configure the V/f 5-Point Settings)
PM Drive (Permanent Magnet)
PG Feedback Vector Control (Speed)
PG Feedback Vector Control (Speed/Torque Switching)
Motor Current Rating
(F406)
This parameter allows the user to input the full load amperage (FLA) of the motor. This value is found on
the name-plate of the motor and is used by the ASD to determine the
Thermal Overload
Protection
setting for the motor.
Motor RPM
(F407)
This parameter is used to input the (name-plated) rated speed of the motor.
Command Source
(F003)
This selection allows the user to establish the source of the
Run
commands. Run commands are
Run
,
Stop
,
Jog
, etc.
Settings:
Use Terminal Block
Use EOI Keypad
Use RS485
Use Communication Option Board