38
P9 ASD Quick Start Guide
Feedback (Inst)
— Provides a status of the
Real-Time Feedback
in Hz.
Feedback (1 Second)
— Provides a status of the
1-Second Averaging
feedback in Hz.
Torque
—
Displays the
Output Torque
as a percentage of the rated capacity of the P9 ASD.
Torque Reference
—
Displays the
Torque Reference
as a percentage of the maximum torque
available.
Torque Current
—
Displays the torque-producing current value.
Excitation Current
—
Displays the current value required to produce the excitation field.
PID Feedback
— Provides a status of the
PID
Real-Time Feedback
in Hz.
Input Power
— Displays the
Input Power
in Kilowatts (kW).
Output Power
— Displays the
Output Power
in Kilowatts (kW).
Pattern Group Number
—
Displays the active
Pattern Run Group Number
.
Pattern Group Cycle
—
Displays the cycle number of the active
Pattern Run Group
.
Pattern Group Preset
—
Displays the active
Preset Speed
being run of the active
Pattern Run
Group
.
Pattern Time
—
Displays the remaining time for the active
Pattern Run Group
.
RR
— Displays the
RR
input value as a percentage of the full range of the
RR
value (potentiometer
input).
V/I
— Displays the
V/I
input setting as a percentage of the full range of the
V/I
value.
Note:
The isolated
V/I
input terminal may receive
Current
or
Voltage
to control the
output speed or the output torque. The input signal type must be selected at
SW301
on the
Terminal Board
.
The
V
input setting of
SW301
is used for the 0 – 10 VDC analog input signal and
the
I
input setting of
SW301
is used for the 0 – 20 mA analog input signal. Either
may be used as a frequency or torque command source. See parameter
F201
for
more information on the setup of this terminal.
RX
— Displays the
RX
input setting as a percentage of the full range of the
RX
value (-10 to +10
VDC input).
RX2 Option (AI1)
— Displays the
RX2
input setting as a percentage of the full range of the
RX2
value.
Note:
The RX2 function is available on the
Expansion IO Card Option 1
option board
(P/N ETB003Z) only.
Trip Code
—
Displays
None
if there are no errors, or displays one of the associated
Fault Codes
listed in the
P9 ASD Installation and Operation Manual
if there is an active
Fault
(e.g.,
E
=
Emergency Off
).
Past Trip 1
—
This function records and displays the last trip incurred. Subsequent trips will replace
Past Trip 1
. As trip records are replaced they are shifted to the next level of the
Past Trip
locations
until being deleted (i.e.,
Past Trip 1
is moved to
Past Trip 2
and then to
Past Trip 3
until being
shifted out of
Past Trip 4
). Once shifted out of
Past Trip 4
the record is deleted. If no trips have
occurred since the last reset,
No Error
is displayed for each trip record.
Past Trip 2
—
Past trip information or
None
.
ast Trip 1