ProtoNode Quick Install Guide – 66939-000
5
File Name
Protocols
Firmware pcc6029
BACnet MSTP, BACnet IP
Firmware pcc6030
Modbus RTU, Modbus TCP,
Metasys NS, SNMP
Firmware pcc6032
EtherNet/IP
Table 1
1.
Open and extract the ProtoNode firmware file (NLPN.BIN) and place it in the “Configuration
File Folder”, by going to Start|Programs|FieldServerUtilities|Configuration File Folder.
NOTE: Do not rename the “NLPN.BIN” file.
2.
In the main menu of the Remote User Interface screen, type “d” to go to “Download
configuration to FieldServer” menu (See Figure 4).
3.
Type “f”, for firmware, and the program will automatically fetch the firmware from the
“Configuration File Folder” (See Figure 5).
4.
Type “y”, for yes, to precede the installation of the new firmware.
5.
Wait until the download completes (Note: resetting or turning off while the ProtoNode is
installing the firmware can corrupt the ProtoNode.)
6.
Once download is complete hit “<esc>” key to go to the main menu. Type “!” or cycle power
to ProtoNode to put the new firmware into operation.
Figure 5
Note: to verify firmware version from the main menu type “b”, for “FieldServer
Information”. Then hit the <space bar> key and look at the “Kernel Version” (See Figure 6).