background image

Meets or Exceeds

Q9 Standard Specifications

Input Voltage

230 V

HP Rating

1

2

3

5

7.5

10

15

20

25

30

40

50

60

Current Rating

4.8

7.8

11

17.5

25.3

32.2

48.3

62.1

78.2

92

120

150

177

Input Voltage

460 V, 50/60 Hz, Three-Phase

HP Rating

1

2

3

5

7.5

10

15

20

25

30

40

50

60

Current Rating

2.1

3.4

4.8

7.6

11

14

21

27

34

40

52

65

77

HP Rating

75

100

125

150

200

250

300

350

400

Current Rating

96

124

156

180

240

302

361

414

477

Power Requirements

Input Voltage Range

200 to 240 V, 50/60 Hz, Three-Phase

380 to 480 V, 50/60 Hz, Three-Phase

Power Terminals

Input (L1/R, L2/S, L3/T), Output (T1/U, T2/V, T3/W), DCL (PO, PA), DC Bus (PA, PC)

Voltage Tolerance

±10%

Frequency Tolerance

±2%

Control Specifications

Output Method

Sine Wave Pulse-Width Modulated System

Output Frequency Range

0 to 299 Hz

V/Hz Pattern

Constant Torque, Variable Torque, Automatic Torque Boost, Sensor-Less Vector Control (Speed), V/f Five-Point Setting, 

Permanent Magnet Control, Auto Power-Saver

Overload Current Rating

100% Continuous; 110% for One Minute

Frequency Control

Rotary Encoder Integrated Into EOI, 0 to 10 VDC, ±10 VDC, 4 to 20 mA, Binary Input, Motor Operated Potentiometer

Frequency Accuracy

Analog Input: ±0.2% of Maximum Output Frequency; Digital Input: ±0.01% of ±0.022 Hz of Output Frequency

Frequency Resolution

Operation Panel: 0.01 Hz

Acceleration/Deceleration

0.1 to 6000 Seconds

Analog Inputs

Three: One Isolated Input Selectable Between 0 to 10 VDC/4 to 20 mA, One 0 to 10 VDC, and One ±10 VDC

Analog Outputs

Two Programmable to 57 Functions (One Switchable 0 to 10 VDC/0 to 20 mA, and One 0 to 1 mA)

Discrete Inputs

Eight Programmable to 41 Functions

Sink/Source Switching

Ability to Switch Between Sink Logic and Source Logic

Discrete Outputs

Three Programmable to 83 Functions (Two Form-A and One Form-C); Outputs Rated at 2 A/120 VAC, 2 A/30 VDC

PID (Set Point Control)

Adjustment of Proportional Gain, Integral Time, Differential Time, and Delay Filter

Braking Control

DC Braking, Over-Flux Braking

Communication Ports

Two-Wire/Four-Wire RS485

Communication Protocol

BACNet

®

, LonWorks

®

, Metasys N2

®

, Modbus RTU

®

, APOGEE FLN

®

Protection

Protective Functions

Overvoltage Stall, Overcurrent Stall, Critical (Skip) Frequencies, Ride-Through, Electronic Thermal Motor Protection

Interrupting Current Rating 100,000 AIC

Faults

Overcurrent, ASD Overheat, ASD Overload, Motor Overload, Overvoltage, Overtorque, Undercurrent, Ground Fault, 

Communication Time-Out, Analog-Input Terminal Overvoltage, Emergency Stop, Input/Output Phase Loss, RAM/ROM 

Error, Undervoltage

Retry

Ability to Reset Certain Faults Automatically; Programmable Up to 10 Retries

Restart

Ability to Detect Speed and Direction of Freewheeling Motor and Start into Motor Smoothly

Interface

EOI Display

Full-English Backlit LCD Display

Keys

LOCAL/REMOTE, ESC, RUN, MODE, STOP/RESET

Rotary Encoder

Encoder with Integrated Enter Key for Frequency and Parameter Adjustments

Monitoring

Monitors 19 Drive Conditions

Display Units

Programmed to Display Percentage or Volts/Amps

Ambient Conditions

Temperature

-10˚ to 40˚C

Relative Humidity

Maximum 93% (Non-Condensing)

Altitude

1000 Meters or Less

Q9 Dimensions

230 V

1 to 2 HP

3 to

5 HP

7.5 HP

10 HP

15 to

20 HP

25 to

30 HP

-

40 to 

60 HP

-

100 HP

125 HP

-

-

-

460 V

1 to 3 HP

5 to

7.5 HP

10 HP

15 to

20 HP

25 to

30 HP

40 HP

50 to

60 HP

-

75 to 

125 HP

150 HP

200 HP 250 HP

300 to  

350 HP

400 HP

Frame

2

3

4

5A

5B

6

7A

7B

8

9B

10B

11B

12B

13A

Height (in.)

10.0

11.1

12.6

12.6

15.7

16.5

21.7

21.7

24.8

36.2

40.2

46.9

46.9

46.9

Width (in.)

5.1

6.1

6.9

8.3

9.1

9.4

9.4

12.6

12.6

12.2

13.8

13.0

16.9

23.0

Depth (in.)

6.0

6.5

6.5

7.5

7.5

8.3

8.3

9.5

11.4

14.6

14.6

14.6

14.6

14.6

 Your Specifications

Summary of Contents for Q9 Series

Page 1: ...Q9 Series ADJUSTABLE SPEED DRIVES ...

Page 2: ...upting capacity The drive is also designed to operate in environments from 10 to 40 C at elevations upto 3 300 feet Configurable The Q9 is not only a monster in durability and dependability but also simple to use The electronic operator interface EOI with its LCD display and simple keypad layout allows for quick and easy menu and parameter navigation Toshiba even provides optional Windows based so...

Page 3: ...ve runs at the lower limit frequency for a specified time This option helps reduce energy costs PID Control A built in proportional integral derivative PID controller used to regulate a process without the need for external control devices comes standard with the Q9 In addition the wire break function trips the drive if the feedback signal drops below specified levels This prevents the drive from ...

Page 4: ...oothly without tripping This drive feature proves especially useful when trying to start a motor after a momentary power outage or in the case of a free wheeling fan Adjustable acceleration deceleration times and stall capabilities allow for minimal stress on fans pumps belts and pulleys The Q9 is capable of programming up to three different skip frequencies User selected frequencies may be skippe...

Page 5: ...P 75 to 100 HP Height in 35 5 36 3 36 3 40 5 41 3 Width in 16 0 16 0 16 0 16 0 16 0 Depth in 12 5 12 5 12 5 12 5 12 5 Integrated Enclosure Dimensions Without Reactor 230 V 3 to 7 5 HP 10 to 25 HP 460 V 3 to 15 HP 20 to 40 HP Height in 28 5 45 5 Width in 16 1 16 1 Depth in 10 6 13 9 Integrated Enclosure Build your own drive uses a standard NEMA 1 enclosure that is available with the following optio...

Page 6: ...While Running and Green While Stopped LOCAL REMOTE Key Toggles System to and from Local Remote Modes LOCAL REMOTE Key Light Illuminates Green While in Local Mode Option Card Status LEDs Shows Stackable Option Card Status LEDs When Options are Installed Panel Locking Screw Allows for Simple Front Panel Locking and Unlocking Panel Door Allows Easy Access to Control Terminal Strip STOP RESET Key Issu...

Page 7: ...ee Programmable to 83 Functions Two Form A and One Form C Outputs Rated at 2 A 120 VAC 2 A 30 VDC PID Set Point Control Adjustment of Proportional Gain Integral Time Differential Time and Delay Filter Braking Control DC Braking Over Flux Braking Communication Ports Two Wire Four Wire RS485 Communication Protocol BACNet LonWorks Metasys N2 Modbus RTU APOGEE FLN Protection Protective Functions Overv...

Page 8: ...are technologically innovative and our products are manufactured from start to end using only the highest quality domestic and foreign parts Product Warranty Toshiba offers a comprehensive warranty program on its full line of industrial products Consult your salesperson or the factory for specific information Need to Know More Be sure to visit our website located at www toshiba com ind for the lat...

Reviews: