18
Q9 ASD Quick Start Guide
Terminal Descriptions
Note:
The programmable terminal assignments may be accessed and changed from their
default settings as mapped on
pg. 31
or via the Direct Access method: Program
Direct Access
Applicable Parameter Number. See the section titled
Program
Mode Menu Navigation on pg. 31
for the applicable Direct Access parameter
numbers.
For further information on terminal assignments and default setting changes, see the
sections titled
Default Setting Changes on pg. 47
and
Input Terminals on pg. 34
.
Note:
See the section titled
Cable/Terminal Specifications on pg. 58
for the Q9 ASD
conductor and terminal electrical specifications.
Note:
Programmable terminals will not retain their settings indefinitely in the event of a
power loss. Connect an ex24 VDC supply to the SU+ terminal to retain the
programmable settings in the event of Control Power loss (See
Figure 20 on pg. 22
).
ST
— The default setting for this terminal is the
Standby
mode controller. As the default setting, this
terminal must be activated for normal system operation. The
ST
terminal is activated by connecting
CC
to this terminal (Sink mode). When deactivated,
OFF
is displayed on the
Frequency
Command
screen. This input terminal may be programmed to any of the functions listed in the
Q9 ASD
Installation and Operation Manual
(See F113).
RES
— The default setting for this terminal is
Reset
. The
RES
terminal is activated by connecting
CC
to this terminal (Sink mode). A momentary connection to
CC
resets the ASD and any fault indications
from the display.
Reset
is effective when faulted only. This input terminal may be programmed to any
of the functions listed in the
Q9 ASD Installation and Operation Manual
(See F114).
F
— The default setting for this terminal is
Forward
run command. The
F
terminal is activated by
connecting
CC
to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the
Q9 ASD Installation and Operation Manual
(See F111).
R
— The default setting for this terminal is
Reverse
run command. The
R
terminal is activated by
connecting
CC
to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the
Q9 ASD Installation and Operation Manual
(See F112).
S1
— The default setting for this terminal is
Fire Speed
. The function of this input as
Fire Speed
is to
run the motor at the
Preset Speed #1
setting upon activation. This terminal may be activated by
connecting
CC
to this terminal (Sink mode) and may be initiated by a fire alarm signal or fire/smoke
sensing device. This input terminal may be programmed to any of the functions listed in the
Q9 ASD
Installation and Operation Manual
(See F115).
S2
— The default setting for this terminal is
Preset Speed 2
. The function of this input as
Preset Speed 2
is to run the motor at the
Preset Speed 2
setting upon activation. The terminal may be
activated by connecting
CC
to this terminal (Sink mode). This input terminal may be programmed to
any of the functions listed in the
Q9 ASD Installation and Operation Manual
(See F116).
S3
— The default setting for this terminal is
Damper Feedback
. The function of this input as Damper
Feedback is to complete the requirements for normal system operation as described in the
Q9 ASD
Installation and Operation Manual
. The S3 terminal is activated by connecting
CC
to this terminal
(Sink mode). This input terminal may be programmed to any of the functions listed in the
Q9 ASD
Installation and Operation Manual
(See F117).
S4
—
The default setting for this terminal is
Emergency Off
(Normally Closed). The
Emergency Off
terminal is activated by opening the connection to
CC
(Sink mode). The function of this input as
Emergency Off
is to remove power from the output of the ASD and may apply a supplemental braking
system using the method selected at the
Emg Off Mode
selection parameter (See F603). This input