Q9 ASD Quick Start Guide
19
terminal may be programmed to any of the functions listed in the
Q9 ASD Installation and Operation
Manual
(See F118).
RR
— The default function assigned to this terminal is the
Frequency Mode 1
setting. The
RR
terminal
accepts
a 0 – 10 VDC input signal that is used to control the function assigned to this terminal.
This input terminal may be programmed to control the speed or torque of the motor via an amplitude
setting or regulate by setting a limit. The gain and bias of this terminal may be adjusted for application-
specific suitability (See F210 – F215). See
Figure 20 on pg. 22
for an electrical depiction of the
RR
terminal. This terminal references
CCA
.
RX
— The
RX
terminal
accepts
a ±10 VDC analog input signal and controls the function assigned to
this terminal. This input terminal may be programmed to control the speed, torque, or direction of the
motor. It may also be used to regulate (limit) the speed or torque of the motor by setting a limit. The
gain and bias of this terminal may be adjusted for application-specific suitability (See F216 – F221).
See
Figure 20 on pg. 22
for an electrical depiction of the
RX
terminal.
V/I
— The V/I terminal has the dual function of being able to receive an input voltage or current. The
function as a voltage input to receive a 0 – 10 VDC input signal. The function as a current input is to
receive a 0 – 20 mA input signal. Using either input type, the function is to control the 0.0 – Maximum
Frequency output or the 0.0 to 250% torque output of the ASD. This is an isolated input terminal. This
terminal may be programmed to control the speed or torque of the motor and cannot process both input
types simultaneously. SW301 must be set to V or I to receive a voltage or current, respectively (See
Figure 9 on pg. 20
). Terminal scaling is accomplished via F201 – F206. The gain and bias of this
terminal may be adjusted for application-specific suitability (See F470 and F471).
SU+
— Externally su24 VDC ±10% at 1.1 A (minimum) backup control power. This terminal
references
CC
.
P24
— +24 VDC at 200 mA power supply for customer use. This terminal references
CCA
.
PP
— The function of output
PP
is to provide a 10 VDC/10 mADC output that may be divided using a
potentiometer. The tapped voltage is applied to the
RR
input to provide manual control of the
RR
programmed function. This terminal references
CCA
.
O1A/B
(OUT1A/B)
— The default function assigned to this terminal is
Damper Command
. This
output may be programmed to provide an indication (open or closed) that any one of the functions listed
in the
Q9 ASD Installation and Operation Manual
has occurred or is active. This function may be used
to signal external equipment (e.g., activate the brake) (See F130). The
OUT1
terminal is rated at 2 A/
120 VAC and 2 A/30 VDC.
O2A/B
(OUT2A/B) — The default function assigned to this terminal is
ACC/DEC Complete
. This
output may be programmed to provide an indication (open or closed) that any one of the functions listed
in the
Q9 ASD Installation and Operation Manual
has occurred or is active. This function may be used
to signal external equipment (e.g., activate the brake) (See F131). The
OUT2
terminal is rated at
2A/120 VAC and 2A/30 VDC.
FP
— The default function assigned to this open collector output terminal is
Output Frequency
. This
output terminal produces an output pulse train that has a frequency which is proportional to the
magnitude of the
Output Frequency
(or the function assigned to this terminal). This terminal may be
programmed to provide an output pulse rate that is proportional to the magnitude of the user-selected
item in the
Q9 ASD Installation and Operation Manual
(See F676).
AM
—
The default function assigned to this output terminal is
Output Current
. This output terminal
produces an output current that is proportional to the magnitude of the
Output Current
of the Q9 ASD
(or the function assigned to this terminal). The available assignments for this output terminal are listed
in the
Q9 ASD Installation and Operation Manual
(See F670).
FM
— This output terminal produces an output current or voltage that is proportional to the output
frequency of the ASD or of the magnitude of the function assigned to this terminal. The available
SU+
P24