58
Q9 ASD Quick Start Guide
Cable/Terminal Specifications
Installation should conform to the 2008 National Electrical Code Article 110 (NEC
) (Requirements for Electrical
Installations), all regulations of the Occupational Safety and Health Administration, and any other
applicable national, regional, or industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the Q9 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the Q9 ASD.
Note:
Cable/Terminal specifications are based on the rated current of the Q9 ASD and Do
Not include the 10% Service Factor.
Note:
Use only 75° C copper wire/cable for motor and power connections.
Table 7. 230-Volt Q9 ASD Cable/Terminal/Torque Specifications.
Model
Number
VT130Q9U
Wire/Cable Size
Lug Size Range
Terminal
Board Wire
Size
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-Capacity for
Input/Output Power
In-Lbs./N·m
Recommended
Maximum
3Ø-Input
3Ø-Output
TB1 – 4
Terminals
3Ø-Input 3Ø-Output
2010
14
10
14 to 10
20
(3-core shield)
Torque to 5.3/0.6
12.4/1.4
2015
14
10
2025
14
10
2035
14
10
2055
10
10
2080
8
8
12 to 8
26.6/3
2110
8
8
10 to 4
2160
6
3
8 to 2
47.8/5.4
2220
4
3
2270
3
3
4 to 1/0
212/24
2330
2
2
2400
1/0
4/0
2 to 300
360/41
2500
2/0
4/0
2600
4/0
4/0