background image

No.

Part name

P

rocedure

s

Remarks

Vertical louver

assembly

Cross flow fan

Vertical louver

Screw

Screw

Bearing base

Heat exchanger

Cross flow fan

3.5 mm

Cross flow fan

Set screw

Fan motor

Body back

Cross flow fan

Heat exchanger

1)

Follow the procedure item 3 and 4

 

.

2)

Loosen the set screw of the cross flow fan.

3)

Remove 

4

 fixing screws from the bearing

base

 then remove 

it

 

from the main unit.

<To re-installation>

1)

To incorporate the fan motor 

and

 

the

motor into the position in the following

figure.

- Install the cross flow fan so that the right

end of the 1st joint from the right of the

Cross flow fan is keep

 

3.5mm

 

from

closed wall of the main unit.

- Holding the set screw, install the

cross flow fan so that flat area on shaft of

the fan motor comes to the mounting hole

of the set screw.

4) Lift up the heat exchanger follow the figure.

Pull out the left hand side until the cross flow

fan

 is

 released from the shaft of the fan

motor

 

and then pull out the lower side of

heat

 

exchanger follow the figure.

8

9

1)

Follow the procedure item 3 and 7

 

.

2)

Remove 2 fixing screws from the base vertical

    louver then remove the vertical louver

 

    

assembly from the body back.

FILE NO. SVM-16030

- 102 -

AMP Air Conditioning

www.ampair.co.uk | sales@ampair.co.uk

Summary of Contents for RAS-05BAVG-E

Page 1: ...r Unit RAS 05BKVG E RAS 07BKVG E RAS 10BKVG E RAS 13BKVG E RAS 16BKVG E SPLIT TYPE Outdoor Unit RAS 05BAVG E RAS 07BAVG E RAS 10BAVG E RAS 13BAVG E RAS 16BAVG E R32 FILE NO SVM 16030 2 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 2: ...ATIONS OF ELECTRICAL PARTS 23 7 REFRIGERANT CYCLE DIAGRAM 24 8 CONTROL BLOCK DIAGRAM 28 9 OPERATION DESCRIPTION 31 10 INSTALLATION PROCEDURE 55 11 HOW TO DIAGNOSE THE TROUBLE 70 12 HOW TO REPLACE THE MAIN PARTS 98 13 EXPLODED VIEWS AND PARTS LIST 119 FILE NO SVM 16030 2 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 3: ...t or refrigerating machine oil the sizes of connecting sections of charging port on main unit and installation tools are different from those used for the conventional refrigerant units Accordingly special tools are required for the new refrigerant R32 units For connecting pipes use new and clean piping materials with high pressure fittings made for R32 only so that water and or dust does not ente...

Page 4: ...ESSURE IN THE REFRIGERATION CIRCUIT WILL BECOME ABNORMALLY HIGH AND IT MAY RESULT IN THE PIPE BURSTING AND POSSIBLE PER SONNEL INJURIES IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE SERVICE WORK AND THE INSTALLATION WORK IMMEDIATELY LET FRESH AIR INTO THE ROOM IF THE REFRIGERANT GAS IS HEATED SUCH AS BY FIRE GENERATION OF POISONOUS GAS MAY RESULT WARNING Never modify this ...

Page 5: ...rge than Amin m2 How to get Amin m2 Amin M 2 5 x 0 22759 x h0 2 M is the refrigerant charge amount in appliance in kg h0 is the installation height of the appliance in m 0 6 m for floor standing 1 8m for wall mounted 1 0 m for window mounted 2 2 m for ceiling mounted Comply with national gas regulations CAUTION Exposure of unit to water or other moisture before installation may result in an electr...

Page 6: ...ight mm 530 530 Width mm 660 660 Depth mm 240 240 Net weight kg 21 21 Compressor Motor output W 500 500 Type Model NX66F0F 20D Fan motor output W 43 Air flow rate Cooling Heating m3 min 29 30 29 30 Piping Type Flare connection connection Indoor unit Liquid side mm 6 35 6 35 Gas side mm 9 52 9 52 Outdoor unit Liquid side mm 6 35 6 35 Gas side mm 9 52 9 52 Maximum length m 15 15 Maximum charge less ...

Page 7: ...30 530 Width mm 660 660 Depth mm 240 240 Net weight kg 21 22 Compressor Motor output W 750 750 Type Model NX89F0F 20D Fan motor output W 43 Air flow rate Cooling Heating m3 min 31 0 31 0 33 33 Piping Type Flare connection connection Indoor unit Liquid side mm 6 35 6 35 Gas side mm 9 52 9 52 Outdoor unit Liquid side mm 6 35 6 35 Gas side mm 9 52 9 52 Maximum length m 15 15 Maximum charge less lengt...

Page 8: ...pressor Motor output W 750 Type Model KSN108D22UFZ Fan motor output W 43 Air flow rate Cooling Heating m3 min 34 36 Piping Type Flare connection connection Indoor unit Liquid side mm 6 35 Gas side mm 12 7 Outdoor unit Liquid side mm 6 35 Gas side mm 12 7 Maximum length m 20 Maximum charge less length m 15 Maximum height difference m 12 Refrigerant Name of refrigerant R32 Weight kg 0 80 Wiring Powe...

Page 9: ... 10 Heating Capacity ratio Outside Temperature ºC RAS 16BKVG E 50 0 55 0 60 0 65 0 70 0 75 0 80 0 85 0 90 0 95 0 100 0 105 0 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 Cooling Capacity ratio Outside Temperature oC Conditions Indoor DB 27oC WB 19oC Outdoor DB 35oC WB 24oC Indoor Air Flow High Pipe Length 5m Voltage 230V Capacity ratio 100 1 50kW RAS 05BKVG E 2 00kW RAS 07BKVG E 2 50kW RAS 10BKVG ...

Page 10: ...rs or similar work on air conditioning equipment is performed 3 If a refrigeration gas leakage occurs during installation servicing be sure to ventilate fully If the refrigerant gas comes into contact with fire a poisonous gas may occur 4 When installing or removing an air conditioner do not allow air moisture dust or oil to remain in the refrigeration cycle Otherwise pressure in the refrigeration...

Page 11: ...4 3 8 1 2 5 8 Reference outer diameter of copper pipe jointed mm 6 35 9 52 12 70 15 88 Minimum joint thickness mm 0 50 0 60 0 70 0 80 3 2 2 Processing of Piping Materials When performing the refrigerant piping installation care should be taken to ensure that water or dust does not enter the pipe interior that no other oil than lubricating oils used in the installed air water heat pump is used and ...

Page 12: ...5 Conventional flare tool Clutch type Wing nut type 1 0 to 1 5 1 5 to 2 0 1 0 to 1 5 1 5 to 2 0 1 0 to 1 5 2 0 to 2 5 1 0 to 1 5 2 0 to 2 5 Table 3 2 4 Dimensions related to flare processing for R22 Nominal diameter 1 4 3 8 1 2 5 8 Outer diameter mm 6 35 9 52 12 70 15 88 Thickness mm 0 8 0 8 0 8 1 0 A mm Flare tool for R22 clutch type 0 to 0 5 0 to 0 5 0 to 0 5 0 to 0 5 Conventional flare tool Clu...

Page 13: ...t for conventional R22 Incidentally when the torque is weak the gas leakage may occur When it is strong the flare nut may crack and may be made non removable When choosing the tighten ing torque comply with values designated by manufacturers Table 3 2 7 shows reference values NOTE When applying oil to the flare surface be sure to use oil designated by the manufacturer If any other oil is used the ...

Page 14: ... Electronic balance for refrigerant charging Leakage detector Usage Pipe flaring Flaring by conventional flare tool Connection of flare nut Evacuating refrigerant charge run check etc Vacuum evacuating Refrigerant charge Gas leakage check R32 R410A air water heat pump installation Existence of new equipment for R32 Yes Yes Yes Yes Yes Yes Yes Whether conven tional equipment can be used Note 1 Note...

Page 15: ...ctronic balance and charge liquid refrigerant Indoor unit Outdoor unit Opened Opened Refrigerant cylinder with siphon Check valve Open close valve for charging Electronic balance for refrigerant charging Opened Closed Service port 3 4 Recharging of Refrigerant When it is necessary to recharge refrigerant charge the specified amount of new refrigerant according to the following steps 1 Never charge...

Page 16: ...generally used to join copper or copper alloy 3 Low temperature brazing filler Low temperature brazing filler is generally called solder and is an alloy of tin and lead Since it is weak in adhesive strength do not use it for refrigerant pipes 1 Phosphor bronze brazing filler tends to react with sulfur and produce a fragile compound water solution which may cause a gas leakage Therefore use any oth...

Page 17: ...orine 3 When adding water to the flux use water which does not contain chlorine e g distilled water or ion exchange water 4 Remove the flux after brazing 3 5 3 Brazing As brazing work requires sophisticated techniques experiences based upon a theoretical knowledge it must be performed by a person qualified In order to prevent the oxide film from occurring in the pipe interior during brazing it is ...

Page 18: ...0 131 120 24 Installation plate hanger Drain hose 0 4m Installation plate hanger Connecting pipe 0 35m Flare 9 52mm Connecting pipe 0 40m Flare 6 35mm 510 40 298 94 94 135 170 170 135 40 144 144 170 170 192 192 Installation plate outline Center line Hanger Hanger Hanger Outline of indoor unit 65 65 64 5 73 5 110 58 17 5 Wireless remote controller 25 Remote controller holder FILE NO SVM 16030 18 AM...

Page 19: ...4 2 Outdoor Unit RAS 05 07 10 13BAVG E C L C L 280 400 Unit mm FILE NO SVM 16030 19 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 20: ... PV Liquid side Flare 6 35 Ø Flare 12 7 Gas side Service port Installation dimension Air outlel 100 or more 100 or more 600 or more 600 or more Air intlel Ø Ø Ø Ø6 hole 86 Ø6 hole Ø11x14 hole R15 28 A 320 R5 5 36 108 125 50 137 92 5 4 600 320 90 600 90 275 290 550 Ø 436 Z R15 50 36 2 320 342 69 Unit mm FILE NO SVM 16030 20 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 21: ...5 WIRING DIAGRAM RAS 05BKVG E RAS 05BAVG E RAS 07BKVG E RAS 07BAVG E RAS 10BKVG E RAS 10BAVG E RAS 13BKVG E RAS 13BAVG E FILE NO SVM 16030 21 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 22: ...RAS 16BKVG E RAS 16BAVG E FILE NO SVM 16030 2 22 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 23: ...89F0F 20D 3 Phases 6 Poles 790W RAS 16 KSN108D22UFZ 3 Phases 6 Poles 840W 2 Fan Motor WDF 340 A43 1 DC 140 340V 43W 3 Pulse Modulating Valve PMV coil PQ M10012 000313 DC 12V 4 4 Way valve coil DXQ 939 AC 220 240V 5 Reactor RAS 16 CH 69 Z T L 19mH 10A 6 Suction temp sensor TS sensor Inverter attached 10kΩ at 25 C 7 Discharge temp sensor TD sensor Inverter attached 62kΩ at 20 C 8 Outside air temp se...

Page 24: ...of heat insulator Allowable height difference 12m Allowable pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting port Pulse Modulating valve at liquid side TD 4 way valve Compressor NX66F0F 20D TS T2 Outdoor heat exchanger Temp measurement Propeller fan OUTDOOR UNIT Muffler Muffler Min 2m Chargeless 15m Strainer Max 15m Split capillary TE RAS 05BKVG E RAS 05BAVG E RAS 07B...

Page 25: ...wable height difference 12m Allowable pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting port Pulse Modulating valve at liquid side TD 4 way valve Compressor NX89F0F 20D TS T2 Outdoor heat exchanger Temp measurement Propeller fan OUTDOOR UNIT Muffler Muffler TE TC TA Min 2m Chargeless 15m TO Strainer RAS 10BKVG E RAS 10BAVG E RAS 13BKVG E RAS 13BAVG E Strainer 10k and 1...

Page 26: ...pipe length P Pressure measurement Gauge attaching port Vacuum pump connecting port Deoxidized copper pipe Outer dia 12 7mm Thickness 0 8mm Pulse Modulating valve at liquid side TD 4 way valve Compressor KSN108D22UFZ TS T2 Outdoor heat exchanger Temp measurement Propeller fan OUTDOOR UNIT Muffler Muffler TE TC TA Min 2m Chargeless 15m TO Strainer RAS 16BKVG E RAS 16BAVG E Strainer Refrigerant amou...

Page 27: ...1 High High 52 condition C Tempeature Heat exchanger pipe temp Model name Standard Indoor Outdoor Compressor RAS pressure fan mode fan mode revolution Indoor Outdoor P MPa T1 C T2 C rps 20 7 6 2 1 to 2 2 34 to 36 1 to 2 High High 51 2 1 to 2 4 35 to 40 0 to 1 High High 65 2 4 to 2 6 40 to 42 0 to 1 High High 68 condition C Tempeature Heat exchanger pipe temp 05BKVG E 07BKVG E 10BKVG E 13BKVG E 1 0...

Page 28: ...essing Timer LED brightness dim Serial Signal Communication Functions M C U Indoor Unit Control Panel Power Supply Remote Control Heat Exchanger Sensor Temperature Sensor Infrared Rays Signal Receiver Infrared Rays Initiallizing Circuit Clock Frequency Oscillator Circuit Louver Motor 36 7KHz Power Supply Circuit Noise Filter Indoor Fan Motor Timer Display Operation Display Louver Driver Louver ON ...

Page 29: ... detect control Outdoor fan control High power factor correction control Inverter output frequency control A D converter function P M V control Discharge temp control 4 way valve control Signal communication to indoor unit P M V Pulse Motor Valve M C U Micro Control Unit M C U For INDOOR UNIT 4 way valve P M V Inverter DC AC Inverter DC AC Outdoor Fan motor Compressor WP 032 P C B OUTDOOR UNIT Cur...

Page 30: ...rent detect control Outdoor fan control High power factor correction control Inverter output frequency control A D converter function P M V control Discharge temp control 4 way valve control Signal communication to indoor unit P M V Pulse Motor Valve M C U Micro Control Unit M C U For INDOOR UNIT 4 way valve P M V Inverter DC AC Inverter DC AC Outdoor Fan motor Compressor WP 030 P C B OUTDOOR UNIT...

Page 31: ...gnal from outdoor unit controller to indoor unit controller The following signals are sent from the outdoor unit controller The current operation mode The current compressor revolution Outdoor temperature Existence of protective circuit operation For transferring of these signals the indoor unit controller monitors the contents of signals and judges existence of trouble occurrence Contents of judg...

Page 32: ...eration 43 10 Temporary operation 44 11 12 Discharge temperature control 44 13 Pulse Modulating valve P M V control 45 Self Cleaning function 46 14 Remote A or B selection 48 9 3 Auto Restart Function 9 3 1 How to Set the Auto Restart Function 50 9 3 2 How to Cancel the Auto Restart Function 51 9 3 3 Power Failure During Timer Operation 51 9 4 Remote Controller and Its Fuctions 9 4 1 Parts Name of...

Page 33: ...tioner Air purifier Operation select COOL HEAT AUTO DRY Temperature setup Air direction Swing Air volume select AUTO LOW LOW MED MED HIGH ECO ON timer setup OFF timer setup Hi POWER Indoor unit control Command signal generating function of indoor unit operation Calculation function temperature calculation Activation compensation function of indoor fan Cold draft preventive function Timer function ...

Page 34: ...s controlled by the previous operation mode 4 DRY operation DRY operation is performed according to the difference between room temperature and the setup temperature as shown below In DRY operation fan speed is controlled in order to prevent lowering of the room temperature and to avoid air flow from blowing directly to persons 1 Detects the room temperature Ta when the DRY operation started 2 Sta...

Page 35: ...r flow rate 2 5 Ta C 2 0 1 5 1 0 0 5 Tsc a b c d e M WC 3 4 5 L W7 Air volume AUTO L L M M H W7 L M 2 WA M H 2 WD Indication Fan speed Fan speed setup COOL ON AUTO MANUAL 3 Fan speed M L x 3 4 L 4 Fan speed M L x 2 4 L 5 Fan speed M L x 1 4 L Linear approximation from M and L Fan speed level Cooling Heating Cooling Heating Cool Heat Dry Fan speed Air flow rate Fan speed Air flow rate rpm m3 s Fan ...

Page 36: ... Air flow rate rpm m3 s Fan speed Air flow rate rpm m3 s Fan speed Air flow rate rpm m3 s rpm m3 s WF UH 1110 524 1110 663 1200 582 1200 730 WE UH H 1110 524 1110 663 1200 582 1200 730 WD H M UH 1060 491 1060 626 1170 563 1080 640 WC M H 960 425 960 551 1120 530 1020 596 WB M M 870 367 870 484 1010 458 960 551 WA M M 870 367 870 484 900 386 960 551 W9 L 750 288 750 395 900 386 840 462 W8 L L L 640...

Page 37: ...5 L W9 M WD 1 2 3 H WE H WE Line approximate H and SUL with Tc SUL W2 Stop 46 46 Tc 34 45 45 33 33 33 21 32 32 20 A 4 A 4 A 4 A 4 A 4 A 4 Fan speed MANUAL in starting Fan speed AUTO in stability Fan speed AUTO in starting L L M M H W8 L M 2 WA M H 2 WE Indication Fan speed Fan speed setup HEAT ON AUTO YES NO MANUAL TC 42 C Min air flow rate control Tc 52 51 42 41 Limited to Min WD tap Fan speed TC...

Page 38: ...r ON 3 Fan lock OFF status of fan motor continues 4 Motor operates as shown in the table below 1 Outdoor unit operation command Outdoor fan control Air conditioner OFF Alarm display Outdoor fan speed rpm 31 7 Compressor speed rps To 10 C To To 10 C To 5 C To 3 C When To is abnormal Hz 16 8 16 8 Hz 48 6 48 6 Hz MAX f 7 f 8 f 9 f 9 f B f E f E f E f E f E f E f E f F f F f F In Heating operation 32 ...

Page 39: ... specified value 5 Current release control Set temp Ts Room temp Ta Correction of Hz signal Outdoor temp To Setup of current release point Capacity control continues Detection of electromotive force of compressor motor winding Detection of motor speed and rotor position Inverter output change Commutation timing change Change of compressor speed Remote controller Indoor unit Ts Ta Current decrease ...

Page 40: ... temperature of the indoor heat exchanger drops in the range from 48 C to under 55 C the compressor speed is kept Q zone 2 When temperature of the indoor heat exchanger rises to 55 C or higher the compressor speed is reduced P zone 3 When temperature of the indoor heat exchanger does not rise to 52 C or when it drops below to 48 C the capacity control operation returns to the usual control in heat...

Page 41: ...umulated heating operation time condition TE 2 C Table 1 In normal To In abnormal To TE0 TE 2 C SH SH0 2 TE0 TE TO0 TO 2 C SH SH0 2 Returning from defrost operation 1 Stop operation of the compressor for approx 40 seconds 2 Invert ON 4 way valve approx 30 seconds after stop of the compressor 3 The outdoor fan starts rotating at the same time when the compressor starts Defrost operation Defrost ope...

Page 42: ...is indicated as the louver closes fully is 0 1 Louver position in cooling operation mode COOL HEAT and the louver returns to the stored position when the next operation is performed Cooling Heating memory position The louver position can be arbitrarily set up by pressing FIX button Swing operation is perfor in range 35 with the Fixed position as the center If the swing range exceeded either upper ...

Page 43: ...C zone cHz 0 0 5 1 0 1 5 2 0 2 5 3 0 4 0 5 0 6 0 7 0 8 0 9 0 10 0 11 0 Room temp Set temp 3 5 3 0 2 5 1 5 1 0 TSC 1 0 2 0 5 5 1H 2H 11 10 7 6 5 4 3 2 1 OFF Dry Max 12 11 9 8 10 TA 6 0 6 5 3H 4H 5 0 4 5 4 0 2 0 0 5 0 5 12 9 8 Time Zone Frequency FAN Min Hz Fan speed depend on presetting and can change every speed 1 The control target temperature increase 0 5ºC per hour up to 2ºC starting from the s...

Page 44: ...ss RESET button for 10 seconds or more Switch to AUTO RESTART control YES NO NO YES Temporary AUTO operation Temporary COOL Operation 11 Discharge temperature control 1 Purpose This function detects error on the refrigerating cycle or error on the com pressor and performs protective control 2 Operation Control of the compressor speed The speed control is performed as described in the left table ba...

Page 45: ... Discharge temp control 4 When defrost operation is performed the open degree of valve is adjusted accord ing to each setup conditions during preparation for defrost and during defrost operation 4 way valve is inversed 5 To turn off the compressor while the air conditioner stops by control of the thermostat or by remote controller adjust the open degree of valve to the setup value before stop of t...

Page 46: ... reception of the stop code 3 After the Self Cleaning operation has been performed for the specified period the unit stops operating Unit now performing cooling or dry operation Press STOP button Only timer indicator lights and Self Cleaning operation starts Time set now elapses Operation stops function During Self Cleaning operations The louver opens slightly The indoor fan operates continuously ...

Page 47: ...1 Hz OFF flash 1 Hz not flash ON OFF ON OFF Setting diagnosis code 06 on remote controlle See detail of setting diagnosis code in 11 4 1 Turn on air conditioner again by remote controller to confirm setting Turn on the power supply to air conditioner after that press RESET button on air conditioner 1 time to turn on the air conditioner The LED display will show in operation LED Fig 11 1 1 Take the...

Page 48: ...pencil 00 will be shown the air conditioner ON shown on the display Picture 4 Press MODE during pushing CHECK B will show on the display and 00 will disappear and the air conditioner will turn OFF The Remote Control B is memorized Picture Note 1 Repeat above step to reset Remote Control to be A 2 Remote Control A has not A display 3 Default setting of Remote Control from factory is A 1 2 1 2 15 Hi...

Page 49: ...d off 50 All lamps are turned off All turned off In the examples of and the lamp illuminates for 5 seconds before going off FAN 17 Operation mode select table 2 1 Purpose Choosing the operating system as appropriate in real condition Operation Factory default setting prefer Heat pump system Through it is able to cooling only system heating only system or return to factory default Operating system ...

Page 50: ... an automatic restarting function which allows the unit to restart operating with the set operating conditions in the event of a power supply being accidentally shut down The operation will resume without warning three minutes after power is restored This function is not set to work when shipped from the factory Therefore it is necessary to set it to work 9 3 1 How to Set the Auto Restart Function...

Page 51: ...tton once more or use the remote controller to turn it on 9 3 2 How to Cancel the Auto Restart Function To cancel auto restart function proceed as follows Repeat the setting procedure the unit receives the signal and beeps three times The unit will be required to be turned on with the remote controller after the main power supply is turned off When the system is on stand by not operating When the ...

Page 52: ...o automatically select cooling or fan only operation 1 Press Select Cool Heat or Fan only 2 Press Set the desired temperature Cooling Heating Min 17 C Max 30 C Fan Only No temperature indication 3 Press Select AUTO LOW LOW MED MED or HIGH MODE MODE FAN 2 Press Set the desired temperature 3 DRY OPERATION COOLING ONLY For dehumidification a moderate cooling performance is controlled automatically 1 ...

Page 53: ...T button on the indoor unit for 3 seconds to set the operation 3 beep sound and OPERATION lamp blink 5 time sec for 5 secpmds Do not operate ON timer and OFF timer 2 Press and hold the RESET button on the indoor unit for 3 seconds to cancel the operation 3 beep sound but OPERATION lamp does not blink 2 Press to rise or decrease the brightness in 4 levels 8 DISPLAY LAMP BRIGHTNESS ADJUSTMENT To dec...

Page 54: ...ither AUTO or Dry 5 OFF TIMER indicator Indicates when the OFF timer is setting press the OFF timer button and select off time by TEMP botton after that back to press OFF timer again to timer setting and push CLEAR button to stop the operation 6 Hi POWER indicator Indicates when the Hi POWER operation starts Press the Hi POWER button to start and press it again to stop the operation 7 ECO indicato...

Page 55: ... Vinyl tape Apply after carrying out a drainage test Wireless remote control Saddle Extension drain hose Not available provided by installer Shield pipe Attach to the front panel Air lter Hook Installation plate Hook 65 mm or more 300 mm or more 300 mm or more C mm or more F mm or more E mm or more D mm or more C mm or more Remark Detail of accessory and installation parts can see in the accessory...

Page 56: ...llation Fixing bolt arrangement of outdoor unit Part code Parts name Q ty A One each B Pipe insulating material polyethylene foam 6 mm thick 1 C Putty PVC tapes One each Air inlet Air outlet 108 mm 28 mm 600 mm 320 mm 125 mm 86 mm 102 mm 90 mm Ø 2 5 m m Air inlet Air outlet 280 mm 500 mm 53 mm 97 mm Ø25 mm Drain outlet RAS 05 07 10 13BAVG E Drain outlet RAS 16BAVG E Refrigerant piping Liquid side ...

Page 57: ...s Name Owner s manual Installation manual Part name Q ty 10 2 2 Accessory and installation parts The part marked with asterisk is packaged with the outdoor unit Mounting screw 4 x 25 s x 6 Flat head wood screw 3 1 x 16 s x 2 Drain nipple x 1 Cap waterproof x 2 For RAS 16BAVG E only 8 FILE NO SVM 16030 2 57 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 58: ...0 threads per inch When purchasing a charge hose be sure to confirm the port size As pressure is high and gasification speed is fast it is difficult to read the indicated value by means of charging cylinder as air bubbles occur The size of opposite sides of flare nuts have been increased Incidentally a common wrench is used for nominal diameters 1 4 and 3 8 By increasing the clamp bar s receiving ...

Page 59: ... Cutting a hole When installing the refrigerant pipes from the rear 1 After determining the pipe hole position on the mounting plate A drill the pipe hole 65 mm at a slight downward slant to the outdoor side NOTE When drilling a wall that contains a metal lath wire lath or metal plate be sure to use a pipe hole brim ring sold separately Mounting the installation plate Fig 10 3 3 Fig 10 3 2 Remote ...

Page 60: ... Drain Hose Forming Since dewing results in a machine trouble make sure to insulate both the connecting pipes Use polyethylene foam as insulating material Fig 10 3 6 Fig 10 3 7 How to remove the drain hose Fig 10 3 8 The drain hose can be removed by removing the screw securing the drain hose and then pulling out the drain hose When removing the drain hose be careful of any sharp edges of steel pla...

Page 61: ... unit R 30 mm Use polisin polyethylene core or the like for bending pipe Liquid side CAUTION Bind the auxiliary pipes two and connecting cable with facing tape tightly In case of leftward piping and rear leftward piping bind the auxiliary pipes two only with facing tape Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit Carefully connect the auxiliary ...

Page 62: ...slight downward slant on the outdoor side Fig 10 3 16 2 Put water in the drain pan and make sure that the water is drained out of doors 3 When connecting extension drain hose insulate the connecting part of extension drain hose with shield pipe Fig 10 3 17 CAUTION Arrange the drain pipe for proper drainage from the unit Improper drainage can result in dew dropping This air conditioner has the stru...

Page 63: ...on plate Snow protection hood At least 50 cm Snow accumulation line Holding frame Front Anchor bolts Install at least 50 cm above the snow accumulation line Fig 10 4 1 CAUTION 1 Install the outdoor unit without anything blocking the air discharging 2 When the outdoor unit is installed in a place exposed always exposed to strong wind like a coast or on a high storey of a building secure the normal ...

Page 64: ...nutes if the piping length is 20 meters 15 minutes for 20 meters assuming a pump capacity of 27 liters per minute Then confirm that the compound pressure gauge reading is 101 kPa 76 cmHg 5 Close the low pressure side valve handle of gauge manifold 6 Open fully the valve stem of the packed valves both side of Gas and Liquid 7 Remove the charging hose from the service port 8 Securely tighten the cap...

Page 65: ...14 H17 14 18 N m 1 4 to 1 8 kgf m 33 42 N m 3 3 to 4 2 kgf m 8 12 N m 0 8 to 1 2 kgf m 14 18 N m 1 4 to 1 8 kgf m A H Hexagon wrench is required Service Port Cap Valve Rod Cap CAUTION KEEP IMPORTANT 5 POINTS FOR PIPING WORK 1 Take away dust and moisture Inside of the connecting pipes 2 Tight connection between pipes and unit 3 Evacuate the air in the connecting pipes using VACUUM PUMP 4 Check gas ...

Page 66: ... the connecting cable with the cord clamp 8 Fix the terminal cover and air inlet grille on the indoor unit Cord clamp Terminal cover Screw Screws Air inlet grille Front panel Valve cover Terminals block 1 Remove the valve cover the electric parts cover and the cord clamp from the outdoor unit 2 Connect the connecting cable to the terminal as identif edbythematchingnumbersontheterminal block of ind...

Page 67: ...necting cable 3 50 mm Earth line 10 mm 70 mm 10 mm Power Supply Input at Outdoor Unit Terminal Block Optional Outdoor Unit Indoor Unit Connecting cable connect to L 2 3 Terminal block L N 1 2 3 Earth line Connecting cable Connecting cable Stripping length of the connecting cable 3 2 L Earth line 50 mm 10 mm 70 mm 10 mm Connecting cable Earth line Earth line Connecting cable Power cord Terminal blo...

Page 68: ...tioner 3 Circuit breaker must be used for the power supply line of this air conditioner 4 Be sure to comply power supply and connecting cable for size and wiring method 5 Every wire must be connected firmly 6 Perform wiring works so as to allow a general wiring capacity 7 Wrong wiring connection may cause some electrical part burn out 8 Incorrect or incomplete wiring is carried out it will cause a...

Page 69: ...appear and the air conditioner will turn OFF The Remote Control B NOTE 1 Repeat above step to reset Remote Control to be A 2 Remote Control A has not A display 3 Default setting of Remote Control from factory is A 10 6 2 Remote Control A B Selection is memorized Picture Picture 1 2 10 6 3 Test operation To switch the TEST RUN COOL mode press RESET button for 10 sec The beeper will make a short bee...

Page 70: ...in case of touching parts on the P C board by hand The new inverter will be incorporated starting with this unit K The control circuitry has an uninsulated construction No 1 2 3 4 5 Troubleshooting Procedure First Confirmation Primary Judgment Judgment by Flashing LED of Indoor Unit Self Diagnosis by Remote Controller Judgment of Trouble by Every Symptom No 6 7 8 9 10 Troubleshooting Procedure How...

Page 71: ...circuit board is to be replaced place the circuit board assembly in a vertical position Laying the board flat on an electrically conductive object such as the top panel of the air conditioner s outdoor unit while a charge is still retained by the electrolytic capacitors of the inverter s main circuit may cause short circuiting between the electrolytic capacitors and secondary circuit components an...

Page 72: ...etely by using soldering iron etc Discharging method 1 Remove the inverter cover plating by opening four mounting claws 2 As shown below connect the discharge resistance approx 100Ω40W or plug of the soldering iron to voltage between terminals of the C07 WARNING ELECTRIC SHOCK is indicated electrolytic capacitor 760µF 400V on P C board and then perform discharging Fig 11 5 RAS 05 07 10 13BAVG E In...

Page 73: ...speed stops approx 30 seconds after operation started and then compressor motor speed increases again approx 30 seconds after In AUTO mode the operation mode is changed In HEAT mode the compressor motor speed does not increase up to the maxi mum speed or decreases before the temperature arrives at the set temperature Description The OPERATION lamp of the indoor unit flashes when power source is tu...

Page 74: ...rrently priority is given to the block of item B 3 The check codes can be confirmed on the remote controller for servicing OPERATION Flashing display 1 Hz OPERATION TIMER Flashing display 5 Hz OPERATION Flashing display 5 Hz OPERATION TIMER White Flashing display 5 Hz OPERATION Flashing display 5 Hz Protective circuit operation for indoor P C board Protective circuit operation for connecting cable...

Page 75: ...with a code the indoor unit will beep once Beep and the display of the remote controller will change as follows The TIMER indicator of the indoor unit flashes continuously 5 times per 1 sec Check the unit with all 52 check codes to as shown in Table 11 4 1 Press TEMP or TEMP button to change the check code backward If there is a fault the indoor unit will beep for 10 seconds Beep Beep Beep Note th...

Page 76: ... Check the sensor TA and connection board temperature sensor is continues error is detected 2 In case of the sensor and its short Circuit or disconnection connection is normal check the P C board TC sensor The heat Operation Flashes when 1 Check the sensor TC and connection exchanger temperature continues error is detected 2 In case of the sensor and its sensor of the indoor unit connection is nor...

Page 77: ...it abnormal stop at circuit of signal some time Signal circuit of indoor If the other check codes are found P C board or outdoor concurrently check them together P C board is failure Check protector hardware such in some period as Hi Pressure switch Thermal Relay etc Check refrigerant amount or any possibility case which may caused high temperature or high pressure Check operation signal of the in...

Page 78: ...perate again all inverter P C board error error is detected operations stop replace inverter 4 times P C board All OFF Flashes after error is detected 4 times 1 Check sensors TE TS connection In case of sensors and it s connection is normal check the inverter P C board 2 Check 4way valve operation position In case TE TS detected temperature relationship are different from normal operation 18 might...

Page 79: ...s record error to check code But after re starting operation if no error is detected and air conditioner can operate more than 6 minutes error count is cleared The others Return signal of the outdoor Indoor unit Flashes when 1 Check power supply Rate 10 including unit has been sent when operates error is detected 2 If the air conditioner repeat operates compressor operation start But after continu...

Page 80: ... TD exceeded 117o C error is detected 2 Check refrigerant amount 4 times 3 Check P M V by measure the resistance of the coil and confirm its operation sound of initial operation etc 4 Observe any possibility cause which may affect high temperature of compressor Compressor is high current All OFF Flashes after 1 Check installation conditions such as though operation Hz is error is detected packed v...

Page 81: ... Measure voltage at terminal block of the indoor unit between No 2 and No 3 or L2 and S If signal is varied 15 60V continuously replace inverter P C board If signal is not varied replace indoor P C board 4 Check and clean heat exchanger area Indoor and Outdoor unit Instantaneous power failure Some protector hardware of the outdoor unit open circuit of signal Signal circuit of indoor P C board or o...

Page 82: ...ssible to turn on power supply by pressing button on remote control Does transmission mark on remote control flash normally and is its signal transmitted properly Remote control is defective Refer to 4 Remote Control Is fuse F01 of indoor control board blown Is voltage DC 12V or 5V indicated on rear of indoor control board normal Microcomputer is defective Replace main P C board Refer to Primary c...

Page 83: ...YES YES NO NO Turn on power supply Does operation lamp flash Is it wired as shown in Figure below Return the wiring of the power relay is returned to the normal procedure To the paragraph of No Power turns on FILE NO SVM 16030 83 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 84: ...ing to high fan Operation stops Shut off the power supply Motor control circuit failure IC03 Q39 and D01 or 12 V Switching power supply failure Does the cross flow fan rotate normally Is the rotation signal DC 5 V 0 V output between 2 gray lead wire and 3 brown lead wire of the motor connector CN11 when rotating the cross flow fan by hand in no operating status 1 pulse one turn Turn on the power s...

Page 85: ...RW GRY YEL For AC fan motor Do not disconnect the connector while the fan motor is rotating For P C board side proceed to the item Only indoor fan does not operate of Judgment of Trouble by Every Symptom SJM 240 25 RAS 05 07 10 13 SJM 240 35 RAS 16 Resistance value RAS 05 07 10 13 Position P C board Between 3 Black 1 Red Between 3 Black 5 White Between 1 Red 5 White 120 6 8 4 Ω 244 2 17 Ω 364 8 25...

Page 86: ...nsmitting within 5 cm distance from the radio P C board is failure Replace P C board Is operation possible when the transmitter is moved nearer to the infrared signal receiver of the air conditioner Battery life Replace the batteries Dose the transmission indicator light Is there any beep and operation Normal Remote control is failure Replace remote control Push the button YES There is no beep fro...

Page 87: ... outdoor unit is correctly performed based upon the follow ing diagram NOTE Measurement should be performed 2 minutes and 30 seconds after starting of the operation Be sure to prepare a diode for judgment Normal time Voltage swings between DC15 and 60V Inverter Assembly check 11 7 1 Abnormal time Voltage does not vary 2 Outdoor unit stops in a little while after operation started Check procedure S...

Page 88: ...ecter of coil connected to inverter Is coil of the pulse motor valve P M V correctly set Existence of condensation at outlet of P M V If there is condensation at outlet 1 4 inch Ø6 35mm valve side the valve is clogged Are temp sensors of indoor outdoor units correctly set to the holder NOTE The temperature sensors which are used to control pulse motor valve include indoor heat exchanger sensor TC ...

Page 89: ... 100Ω 40W or soldering iron plug between terminals of the electro lytic capacitor 760µF of C07 with printed WARNING ELECTRIC SHOCK on P C board OK if 760µF DC290 to 400V Remove CN31 while pushing the part indicated by an by an arrow because CN31 is a connector with lock Resistance between phases should be approx 16 to 51Ω Should be 100MΩ or more Replace outdoor fan motor Remove connector of compre...

Page 90: ...eck the electrolytic capacitor and diode block DB01 Connect discharge resistance approx 100Ω 40W or soldering iron plug between terminals of the electro lytic capacitor 760µF of C07 with printed WARNING ELECTRIC SHOCK on P C board OK if 760µF DC280 to 380V Remove CN31 whilepushing the part indicated by an by an arrow because CN31 is a connector with lock Resistance between phases should be approx ...

Page 91: ...8 1 How to Check the P C Board Indoor Unit 1 Operating precautions 1 When removing the front panel or the P C board be sure to shut off the power supply breaker 2 When removing the P C board hold the edge of the P C board and do not apply force to the parts 3 When connecting or disconnecting the connectors on the P C board hold the whole housing Do not pull at the lead wire 2 Inspection procedures...

Page 92: ...nds and they return to normal 3 seconds later 1 Check whether or not the compressor operates 2 Check whether or not the OPERATION indicator flashes 1 Check whether or not the compressor operates 2 Check whether or not the OPERATION indicator flashes 1 Check it is impossible to detect the voltage AC120V or higher voltage between red and black 2 The motor does not operate or the fan motor does not r...

Page 93: ...TD 1 Sensor characteristic table 11 8 2 P C Board Layout TD Discharge temp sensor TA Room temp sensor TC Heat exchanger temp sensor TO Outdoor temp sensor TS Suction temp sensor TE Outdoor heat exchanger temp sensor GND 12V 5V FILE NO SVM 16030 93 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 94: ... 1 Red White White Black Black Red 3 4 Way valve coil Model DXQ 939 at 20 C 4 Pulse Modulating Valve PMV coil Model PQ M10012 000313 5 Outside air temp sensor TO Discharge temp sensor TD Suction temp sensor TS Exchanger temp sensor TE 1 57Ω Resistance value 1450 150Ω 16 to 51Ω Resistance value Position 3 19Ω 3 36Ω Position White Red Back Measure the resistance value of each winding by using the te...

Page 95: ...pply breaker 2 Discharge all three capacitors completely 3 Check that the normal rectification characteristics are shown in continuity test by the tester 11 8 5 Checking Method for Each Part Case that product is good Pointer swings once and returns slowly When performing test once again under another polarity the pointer should return No Part name Checking procedure Diode check 1 2 Tester rod Resi...

Page 96: ...r drive circuit failure of the outdoor P C board 3 How to simply judge whether outdoor fan motor is good or bad NOTE However GND circuit error inside of the motor may be accepted in some cases when the above check is performed When the fan motor does not become normal even if P C board is replaced replace the outdoor fan motor If the resistance value between 1 Red lead 2 White lead 2 White lead 3 ...

Page 97: ...z function Timer LED Flash 1 Hz OFF flash 1 Hz not flash ON OFF ON OFF Setting diagnosis code 06 on remote controller See detail of setting diagnosis code in 11 4 1 Take the remote controller to direction of LED display on air conditioner press TEMP of the remote controller Fig 11 10 2 1 time to send the code 07 then air conditioner will shutdown automatically Also LED display will show flash foll...

Page 98: ...uipment near flammable objects Flames from the equipment may cause the flammable objects to catch fire If keeping the power on is absolutely unavoidable while doing a job such as inspecting the cir cuitry wear rubber gloves to avoid contact with the live parts Electric shocks may be received if the live parts are touched High voltage circuits are contained inside this unit Proceed very carefully w...

Page 99: ...l toward you to remove it as shown on figure 3 4 1 Follow the procedure item 3 2 Remove screw holding the electric part cover 3 Disconnect the connectors for the fan motor and louver motor from P C board assembly 4 Remove the earth screw and earth line from evaporator 5 Pull out TC sensor from sensor holder of the evaporator 6 Remove the 2 fixing screws that secures the electric parts box assembly...

Page 100: ...ow fan Set screw Fan motor Body back Horizontal louver 6 1 Remove shaft of the horizontal louver from the back body First remove 2 the center shafts then remove the other shafts Horizontal louver Drain pan To re installation Check the type name of fan motor Keep connector position and arrange fan motor wires follow figure For SJM 240 25 4 5 Fan motor connector 4 5 Fan motor connector For SJM 240 3...

Page 101: ...d remove unit display 7 5 Remove the drain pan from the back body Electric part cover Screw Connectors Louver motor connector P C board To re installation Press the drain pan into the back body Please make sure ribs of drain pan in left and right side must be install to lock position Press the center arm of drain pan to back body Center arm of drain pan Back body Drain pan Back body Back body Drai...

Page 102: ...ow fan so that the right end of the 1st joint from the right of the Cross flow fan is keep 3 5mm from closed wall of the main unit Holding the set screw install the cross flow fan so that flat area on shaft of the fan motor comes to the mounting hole of the set screw 4 Lift up the heat exchanger follow the figure Pull out the left hand side until the cross flow fan is released from the shaft of th...

Page 103: ...the hook of the motor cover then pull out the upper side of heat exchanger To re installation Put the evaporator hins seal on the body back before assembly the heat exchanger Please keep assembly heat exchanger follow figure as below Cross flow fan Heat exchanger Evaporator hins seal Please make sure that the hook of motor cover must be installed into the locking slot of heat exchanger Hook Heat e...

Page 104: ...ration of air conditioner 2 Remove the front panel Remove the 2 fixing screws 3 Remove the electrical part base Remarks Replace terminal block microcomputer ass y and the P C board ass y 12 2 Microcomputer FILE NO SVM 16030 104 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 105: ...ach the cord clamp and wiring cover Put the wiring cover into the front cabinet and insert the claw which has been hooked to the lower part into the square hole and then fix it with screw ST2T 4 x 10s 2 pc 3 Attach the valve cover ST2T 4 x 10s 1 pc Insert the upper part to the front cabinet set the hook claw of the valve cover to square holes at three positions of the main unit and attach it pushi...

Page 106: ...TE This capacitor is one with mass capacity Therefore it is dangerous that a large spark generates if short circuiting between Requirement As each connector has a lock mecha nism avoid to remove the connector by holding the lead wire but by holding the connector The connector is one with lock so remove it while pushing the part indicated by an arrow Be sure to remove the connector by holding the c...

Page 107: ...g the closed end splice Fan motor Compressor 1 0 0 Fan motor Propeller fan Flange nut Closed end splice 1 Perform work of item 1 of 1 1 of 2 and ƒ 2 Extract refrigerant gas 3 Remove the partition board ST2T 4 x 10s 3 pcs 4 Remove the sound insulation material 5 Remove the terminal cover of the compressor and disconnect the lead wire of the compressor thermo and the compressor from the terminal 6 R...

Page 108: ...ont cabinet Push the hooking claws 8 positions by your hand and fix the claws Requirement This completes all the attaching work Check that all the hooking claws are fixed to the specified positions Fan guard Minus screwdriver Hooking claw 6 Pulse Modulating Valve coil 7 1 Detachment 2 Attachment 1 Insert the coil at position which perpendicular with pipe of PMV then turn the coil by 180 degrees Ma...

Page 109: ...uch the lock on their housing must be released before they are disconnected 2 Remove the control board assembly from the spacer Remove the heat sink and control board assembly while keeping them screwed together 3 Remove the two fixing screws used to secure the heat sink and control board assembly 4 Mount the new control board assembly NOTE When mounting the new control board assembly ensure that ...

Page 110: ...ach the upper cabinet ST2TØ4 10L 5 pcs 3 Perform cabling of connecting cable and attach the cord clamp Fix the cord clamp by tightening the screws ST2TØ4 x 14L 3 pcs fitting 2 concave parts of the cord clamp to each connecting cables 4 Attach the valve cover ST2TØ4 x 10L 2 pcs Insert the upper part into the square hole of the side cabinet set hook claws of the valve cover to square holes at three ...

Page 111: ...ide cabinet left at the front left side so pull up the top of the front cabinet to remove it 2 Attachment 1 Insert the claw on the front left side into the side cabinet left 2 Hook the bottom part of the front right side onto the concave section of the bottom plate Insert the claw of the side cabinet right into the square hole in the front cabinet 3 Return the screws that were removed above to the...

Page 112: ...cases 4 Remove screw ST2TØ4 x 10L 4pcs fixing the terminal part of inverter box to the main body 5 Remove the front cabinet by performing step 1 in 2 and remove the fixing screws ST2TØ4 x 10L for securing the main body and inverter box 6 Remove various lead wires from the holder at upper part of the inverter box 7 Pull the inverter box upward 8 Disconnect connectors of various lead wires The conne...

Page 113: ...assembly ensure that the P C board is inserted properly into the P C board support groove NOTE P C board base P C board NOTE NOTE 1 Disconnect the leads and connectors connected to the other parts from the control board assembly 1 Leads 3 leads black white orange connected to terminal block Lead connected to compressor Disconnect the connector 3P Lead connected to reactor Disconnect the two connec...

Page 114: ...motor 1 Perform work of item 1 of 1 and 2 2 Remove the flange nut fixing the fan motor and the propeller Flange nut is loosened by turning clockwise To tighten the flange nut turn counterclockwise 3 Remove the propeller fan 4 Disconnect the connector for fan motor from the inverter 5 Remove the fixing screws 4 pcs holding by hands so that the fan motor does not fall Precautions when assembling the...

Page 115: ...ve pipe connected to the compressor with a burner 7 Remove the fixing screw of the bottom plate and heat exchanger ST2TØ4 10L 1 pc 8 Remove the fixing screw of the bottom plate and valve fixing plate ST2TØ4 10L 1 pc 9 Pull upward the refrigeration cycle 8 Reactor 1 Perform work of item 1 of 2 and 3 2 Remove screws fixing the reactors ST2TØ4 10L 2 pcs Compressor Reactor 10 Remove NUT 3 pcs fixing the ...

Page 116: ... Fan Guard 1 Detachment 1 Perform work of item 1 of 2 2 Remove the front cabinet and put it down so that fan guard side directs downward Perform work on a corrugated cardboard cloth etc to prevent flaw to the product 3 Remove the hooking claws by pushing minus screwdriver according to the arrow mark in the right figure and remove the fan guard 2 Attachment 1 Insert claws of the fan guard in the ho...

Page 117: ...holder and install the holder onto the heat exchanger CAUTION During the installation work and on its completion take care not to damage the coverings of the sensor leads on the edges of the metal plates or other parts It is dangerous for these coverings to be damaged since damage may cause electric shocks and or a fire CAUTION After replacing the parts check whether the positions where the sensor...

Page 118: ...inals of the protective tube when colored protective tube is used 10 Fix the sensor again Remarks 1 2 3 4 5 6 Parts name Sensor Sensor Spring A Sensor Spring B Thermal constringent tube Color tape Terminal Q ty 1 1 1 3 1 3 Cutting here Cutting here Cutting here Soldered part Dryer Winding the color tape 100 200 Connector Thermal sensor part Thermal constringent tube 70 15 100 70 15 NOTE 1 Store th...

Page 119: ...G E REFRIGERATION CYCLE ASSY For RAS 10 13BKVG E REFRIGERATION CYCLE ASSY For RAS 16BKVG E EVAPORATOR HINS SEAL For RAS 05 07 10 13BKVG E HOLDER SENSOR PIPE SHIELD INSTALLATION PLATE PIPE HOLDER TERMINAL COVER ASSY WIRELESS REMOTE CONTROL HOLDER REMOTE CONTROL PACKING SLEEVE PACKING CUSHION RIGHT PACKING CUSHION LEFT 216 43T39366 FRONT PANEL ASSY GRILLE OF AIR INLET ASSY AIR FILTER BACK BODY ASSY ...

Page 120: ...TEMPERATURE SENSOR TERMINAL 5P TF TEMPERATURE SENSOR CORD CLAMP 406 43T6V759 Description Description 405 43T6V681 PC BOARD ASSY WRS LED 406 43T6V760 PC BOARD FOR RAS 05BKVG E PC BOARD FOR RAS 07BKVG E PC BOARD FOR RAS 10BKVG E PC BOARD FOR RAS 13BKVG E PC BOARD FOR RAS 16BKVG E FILE NO SVM 16030 120 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 121: ...LVE COVER UPPER CABINET ASSEMBLY FIXING PLATE VALVE BASE PLATE ASSEMBLY DRAIN NIPPLE 4 WAY VALVE 4 WAY VALVE COIL PARTITION ASSEMBLY MOTOR BASE MOTOR BASE CONNECTION PLATE CARTON BOX ASM FBBRD UD CUSHION PKG UPR PE SHEET 18 43T41487 18 43T41486 FAN GUARD PROPELLER FAN FRONT CABINET ASSEMBLY CONDENSER ASSEMBLY TERMINAL COVER VALVE PACKED 9 52 DIA BONNET 9 52 DIA VALVE PACKED 6 35 DIA BONNET 6 35 DI...

Page 122: ...63360 33 43T91301 PACKED VALVE COVER UPPER CABINET ASSEMBLY FIXING PLATE VALVE BASE PLATE ASSEMBLY DRAIN NIPPLE 4 WAY VALVE 4 WAY VALVE COIL PARTITION ASSEMBLY MOTOR BASE MOTOR BASE CONNECTION PLATE CARTON BOX ASM FBBRD UD CUSHION PKG UPR PE SHEET 18 43T41486 FAN GUARD PROPELLER FAN FRONT CABINET ASSEMBLY CONDENSOR ASSEMBLY TERMINAL COVER VALVE PACKED 9 52 DIA BONNET 9 52 DIA VALVE PACKED 6 35 DIA...

Page 123: ...90 33 43T63318 16 43T46469 34 43T79305 17 43T63360 35 43T46470 18 43T58306 36 43T63361 FAN MOTOR NUT FLANGE NUT RUBBER CUSHION HOLDER SENSOR MOTOR BASE CONNECTION PLATE HOLDER SENSOR HOLDER SENSOR PARTITION ASSEMBLY CARTON BOX ASM FBBRD UD CUSHION PKG UPR PE SHEET HOLDER SENSOR DRAIN NIPPLE 4 WAY VALVE 4 WAY VALVE COIL 19 43T20319 CONDENSOR ASSEMBLY VALVE PACKED 6 35 DIA VALVE PACKED 12 7 DIA BONN...

Page 124: ...OR SENSOR HEAT EXCHANGER SPACER KGES 702 43T60753 HEATSINK PC BOARD FOR RAS 05BAVG E PC BOARD FOR RAS 07BAVG E PC BOARD FOR RAS 10BAVG E PC BOARD FOR RAS 13BAVG E TERMINAL 5P Description Description TE Sensor Ø6 TS Sensor Ø6 TD Sensor Ø6 TD Sensor Ø4 701 702 703 704 705 706 707 703 43T60392 RAS 05 07 10 13BAVG E FILE NO SVM 16030 124 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 125: ...0304 703 43T60392 707 43T62313 704 43T60326 TEMPERATURE SENSOR SENSOR HEAT EXCHANGER BASE PLATE PC HEATSINK PC BOARD TERMINAL 5P FUSE Description Description RAS 16BAVG E TE Sensor Ø6 TS Sensor Ø6 TO Sensor Ø6 703 705 706 TD Sensor Ø4 FILE NO SVM 16030 125 AMP Air Conditioning www ampair co uk sales ampair co uk ...

Page 126: ...TOSHIBA CARRIER THAILAND CO LTD AMP Air Conditioning www ampair co uk sales ampair co uk ...

Reviews: