– 80 –
11-8-3. Indoor Unit (Other Parts)
11-8-4. Outdoor Unit
No.
1
Part name
Room temp. (TA) sensor
Heat exchanger (TC) sensor
Checking procedure
Disconnect the connector and measure the resistance value with tester.
(Normal temp.)
Temperature
Sensor
TA, TC (k
Ω
)
10°C
20°C
25°C
30°C
40°C
20.7
12.6
10.0
7.9
4.5
5
4
3
2
1
White
Yellow
Yellow
Yellow
Yellow
5
4
3
2
1
Refer to 11-5-1. (5).
Measure the resistance value of each winding coil by using the tester.
(Under normal temp. 25°C)
Position
1 to 2
1 to 3
1 to 4
1 to 5
Resistance value
250
Ω
± 7%
Refer to 11-5-1. (3) and (4).
2
3
Remote controller
Louver motor
24BYJ48-HTP
4
Indoor fan motor
FILE NO. SVM-1
5004
1 Compressor
(Model : ASM89D16UEZ)
No.
Part name
Checking procedure
White
Red
Back
Position
Resistance value
Red - White
White - Black
1.44
Ω
(20°C)
Black - Red
Measure the resistance value of each winding by using the tester.
Under 20
°
C
Measure the resistance value of winding by using the tester.
Red
White
Black
Measure the resistance value of winding by using the tester.
Resistance value
2210 ± 221
Ω
Under 2
0°C
Measure the resistance value of winding by using the tester.
COM
COM
2
5
4
Y
W
GR
BL
1
GR
6
O
3
Position
Gray - White
Gray - Orange
Gray- Yellow
Gray- Blue
Resistance value
42 to 50
Ω
42 to 50
Ω
42 to 50
Ω
42 to 50
Ω
Under 20°C
Position
Red - White
White - Black
Black- Red
Resistance value
20 to 22
Ω
20 to 22
Ω
20 to 22
Ω
2
3
4
Outdoor fan motor
(Model : ICF-140-43-4R)
4-way valve coil
(Model : SQ-A2522G-000352)
Pulse modulating valve coil